Eka2-EU
EK2-EU_img_01psd.png
Smoke control damper EK2-EU
EK-JZ_img_19psd.png

EK-JZ smoke control dampers with ventilation function for heat and smoke exhaust

EK-JS_Titelbild_Kapselung_1ai.png
img_pro_TLT00101.png
BVDAX for smoke extract in combination with a frequency inverter

BVDAX for smoke extraction operation with frequency converter, CE certified in accordance with EN 12101-3 Temperature category F400

Conforms to VDI 6022

Eka2-EU
EK2-EU_img_01psd.png
EK-JZ_img_19psd.png
EK-JS_Titelbild_Kapselung_1ai.png
img_pro_TLT00101.png

EKA2-EU               

FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND AS AN ADDITIONAL SUPPLY AIR INLET     

Rectangular smoke control dampers with air extract function, for smoke extract with mechanical smoke extract systems or as an additional supply air inlet

  • Complies with product standard DIN EN 12101-8 and is classified in accordance with DIN EN 13501-4
  • Classified EI 90/120 (vew,how i<->o) S 1500 Cmod AA multi
  • Pressure level 3 (-1500 Pa ..... 500 Pa)
  • Can be used in smoke extract systems or in heating and ventilation systems or in a combination of these
  • For systems that require automatic activation (AA)
  • Wide range of application options for fire compartment separation
  • Single-blade room partitioning with mechanical resistance
  • Sheet steel construction in lightweight design
  • Silicone free
  • No stop bars, therefore large free area
  • Leakage tightness class at least 3C for casing and damper tightness, in accordance with DIN EN 1751
  • Thermal insulation with insulating wool (optionally, as it depends on the airflow direction)
  • Connection to air ducts in accordance with DIN EN 1366-1 and DIN EN 1366-8 (self-contained duct system or thermally insulated) or tested in accordance with DIN EN 1366-9
  • For smoke extract ducts made of sheet steel, or self-contained duct system with a wall thickness of 35 mm or more
  • Integration into the management and control equipment with TROXNETCOM or with various control bus systems possible

General information

Application

  • TROX smoke control dampers of Type EKA2-EU, with CE marking and Declaration of Performance, for smoke extraction via mechanical smoke extract systems
  • Provision of outdoor air supply for mechanical smoke extract systems
  • Can be used with ventilation function if the mechanical smoke extract system is approved for ventilation by the building authorities
  • Integration into the management and control equipment with TROXNETCOM


Special characteristics

  • Declaration of Performance according to Construction Products Regulation
  • Complies with the European product standard DIN EN 12101-8
  • Tested for fire resistance properties according to DIN 1366-10 and DIN EN 1366-2
  • Hygiene requirements conform to VDI 6022 part 1, VDI 3803, DIN 1946 part 4 and DIN EN 13779
  • Corrosion protection according to DIN EN 15650 in connection with DIN EN 60068-2-52
  • Closed blade air leakage to DIN EN 1751, class 3
  • Casing air leakage according to DIN EN 1751, class C
  • Low differential pressure and sound power level
  • Any airflow direction
  • Integration into the management and control equipment with TROXNETCOM


Classification

EI 90/120 (vew,how i<->o) S 1500 Cmod AA multi

Nominal sizes

  • B × H: 200 × 200 – 1500 × 800 mm (in increments of 1 mm)
  • L: 305 mm or 500 mm#


Parts and characteristics

  • The damper casing, including all mechanical components, is made of lightweight steel or sheet steel.
  • The damper blade is made of a special insulating material, optionally also available in an impregnated version.
  • Depending on the ambient temperature, the closed damper blade is sealed with a hot seal or a cold seal to prevent the spread of heat and smoke.
  • The design variants with powder-coated casings meet increased requirements for corrosion protection


Attachments 1

  • Cover grille
  • Cover grille without minimisation of free area
  • Extension piece


Attachments 2

  • OPEN/CLOSE actuator, with 24 V AC/DC or 230 V AC supply voltage


Optional products

  • Circular spigots


Technical data

  • Nominal sizes: 200 × 200 – 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Volume flow rate range: up to 12000 l/s or up to 43200 m³/h at 10 m/s
  • Differential pressure range: pressure level 3: -1500 to 500 Pa
  • Temperature range: at least -30 to 50 °C
  • Upstream velocity: ≤ 15 m/s


Useful additions

  • Duct smoke detector RM-O-3-D
  • Duct smoke detector with airflow monitor RM-O-VS-D
  • Smoke control damper EK-JZ
  • Smoke control damper EK-EU

TROX-TLT smoke exhaust fans from the X-FANS subassembly

  • Smoke exhaust fan for roof installation BVDAX/BVD
  • Smoke exhaust fan for wall installation BVW/BVWAXN
  • Smoke exhaust centrifugal fan BVREH/BVRA
  • Smoke exhaust jet fans BVGAX/BVGAXN
All smoke exhaust fans are tested in accordance with DIN EN
12101-3, for F200/F300/F400 and F600, depending on the type.
With CE marking, Declaration of Performance and application
approval for the German market.

Standards and guidlines

  • Complies with the European product standard DIN EN 12101-8 Smoke and heat control - Smoke control dampers
  • Is classified according to DIN EN 13501-4 Fire classification of construction products and building elements
  • Fire protection tested in accordance with DIN EN 1366-2 and DIN 1366-10 Fire resistance tests for installations - smoke control dampers
  • DIN EN 1751 Ventilation for buildings – Air terminal devices
  • Hygienic requirements in accordance with VDI 6022 Sheet 1, VDI 3803, DIN 1946 Part 4 and DIN EN 13779
  • Corrosion protection in accordance with DIN EN 15650 in conjunction with DIN EN 60068-2-52


Maintenance

  • Smoke control dampers must be operational at all times and must be maintained regularly so that they meet the performance requirements.
  • Maintenance at least once every six months; maintenance must be recorded; documents must be kept for reference.
  • The owner of the smoke extract system must arrange for a functional check of the smoke control damper every six months. For this purposes, follow the basic maintenance specifications according to DIN EN 13306 in conjunction with DIN 31051. If two consecutive tests at intervals of 6 months do not reveal any functional defects, the smoke control damper only needs to be checked once a year.
  • Depending on the installation location, country-specific regulations may apply.
  • For details on maintenance and inspection, please refer to the installation and operating manual.


Material and surfaces

  • electrogalvanised steel parts
  • galvanised sheet steel
  • Special insulating material (cement-bonded board material)
  • intumescent strips and profiles
  • EPDM profile seal
  • PE foil tape


Equivalence criteria

  • EI 90/120 (vew,how i<->o) S 1500 Cmod AA multi
  • Fire resistance up to 120 minutes
  • Thermal insulation with insulating wool (optionally, as it depends on the airflow direction)
  • Connection to air ducts in accordance with DIN EN 1366-1 and DIN EN 1366-8 (autonomous air-ducting or thermally insulated) or tested in accordance with DIN EN 1366-9
  • no stop bars, therefore large free area
  • single-blade room partitioning with mechanical resistance
  • For smoke extract ducts made of sheet steel, or autonomous smoke extract ducts with a wall thickness of 35 mm or more
  • Pressure level 3 (-1500 Pa 500 Pa)
  • Smoke-tight with at least leakage class 3 according to DIN EN 1751
  • Silicone free

Technische informatie

  • FUNCTION
  • TECHNICAL DATA
  • SPECIFICATION TEXT
  • ORDER CODE
1 Casing
2 Damper blade
3 Product label
4 Actuator
Smoke control dampers are used in mechanical smoke extract systems. They are used for extracting smoke gases and for providing additional supply air to one or more fire compartments. The dampers are made of galvanised sheet steel and are opened by an actuator (with 24V AC/DC or 230V AC supply voltage) in the area where smoke is to be extracted, either when smoke is detected by a duct smoke detector, or activation via a fire alarm system. Smoke control dampers have two safe positions: fully open and fully closed. In the case of fire-resistant smoke control dampers for multiple compartments, the safe position is either 'open' or 'closed', depending on the fire site and the path of the smoke to be extracted. The EKA2-EU can be used in combined systems (combination damper) for ventilation and is suitable for restricting extract air volume flows, provided that the damper blade throttle position is not adjusted while the smoke extraction unit is running. In OPEN position, at least 75% of the free cross-sectional area must be maintained, even in the event of a fire. Regular maintenance of the smoke control damper is required to ensure its functional reliability.

Nominal sizes

200 × 200 – 1500 × 800 mm

Casing lengths

305 and 500 mm

Volume flow rate range

up to 12000 l/s / up to 43200 m³/h at 10 m/s

Differential pressure range

+/- 1500 Pa

Temperature range

-20 to 50 °C

Upstream velocity

≤ 15 m/s

For sizes, see functional description

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product
Finder design programme


Specification text

Rectangular or square smoke control dampers in accordance with product standard DIN EN 12101-8, tested according to DIN EN 1366-10 and DIN EN 1366-2, for use in smoke extract systems. In addition to maintaining compartmentalisation and removing smoke, heat and combustion products from a fire compartment, smoke control dampers enable the controlled removal of released hazardous and toxic combustion and fire gases. The smoke control damper EKA2-EU can also be used in pressurised ventilation systems and venting systems for pressurised systems and as a pressure relief damper for gas extinguishing systems. Also for the extraction of smoke gases and for providing additional supply air for the mechanical smoke extraction of one or more fire compartments, and in all listed systems of the same type that must fulfil modulation applications. EKA2-EU can be used in combined smoke exhaust systems which have been approved for controlled ventilation. The fire-resistant smoke control damper for multiple compartments is suitable for installation in solid walls, lightweight partition walls and ceilings. The damper blade is moved via an OPEN/CLOSE actuator, optionally with a pre-assembled actuator bus control module.


Materials and surfaces

Casing:

  • Hot-dip galvanised sheet steel
  • Hot-dip galvanised sheet steel with powder coating RAL 7001 and according to RAL card

Damper blade:

  • Special insulating material
  • Special insulating material with coating
  • Plastic slide bearings
  • EPDM and TPE seals


Technical data

  • Nominal sizes: 200 × 200 – 1500 × 800 mm
  • Casing lengths: 305 and 500 mm
  • Nominal sizes 200 × 200 – 1500 × 800 mm, for smoke gas flow rates up to 43,200 m³/h or 12,000 l/s at 10 m/s
  • Differential pressure range: up to 1500 Pa
  • Temperature range: -20 to 50 °C
  • Upstream velocity: standard construction up to 15 m/s

Example of technical data for nominal size 600 × 300 × 500

  • Volume flow rate qv: 2,592 m³/h
  • Airflow velocity v: 4.00 m/s
  • Free area Afr: 0.1569 m²
  • Total differential pressure Δpt: 4 Pa


Standards and guidelines

  • Classification according to DIN EN 13501-4
  • Complies with the European product standard DIN EN 12101-8
  • Tested according to DIN EN 1366-10
  • Leakage test according to DIN EN 1751


Classification

  • EI 90/120 (vew, how, i<->o) S 1500 Cmod AA multi
  • Leakage air flow with closed damper blade according to DIN EN 1751, at least class 3
  • Casing air leakage according to DIN EN 1751, class C


Nominal size

B × H : 200 × 200 – 1500 × 800 [mm] (downstream cross sectional area)

Construction length: L = 305 or 500 [mm]


Attachments

  • OPEN-CLOSE actuators with 24 V AC/DC or 230 V AC supply voltage
  • Interface Control Unit for integration in AS-i networks
  • Interface Control Unit for other standard bus systems
  • Cover grille
  • Curved perforated plate
  • Extension piece


Equivalence criteria

  • EI 90/120 (vew,how i<->o) S 1500 Cmod AA multi
  • Fire resistance: 120 minutes
  • Thermal insulation multi by means of insulating wool
  • Connection to air ducts in accordance with DIN EN 1366-1 A, B and C
  • Smoke extract ducts in accordance with DIN EN 1366-8 (selfcontained
  • duct system, or thermally insulated sheet steel duct)
  • Smoke extract ducts according to DIN EN 1366-9
  • For smoke extract ducts with 35 mm wall thickness or more
  • Pressure level 3 (-1500 Pa to 500 Pa)
  • Smoke-tight with at least leakage class 3 in accordance with DIN EN 1751
  • No stop bars, therefore large free area
  • Room partitioning via individual damper with mechanical resistance
  • Meets the hygiene requirements according to VDI 6022 Sheet 1, VDI 3803, DIN 1946 Part 4 and DIN EN 13779 and according to Ö-Norm H 6020 and H 6021
  • Silicone free


EKA2-EU17/BE/1200 × 800 × 305/A0/B24A









|||||||




1234567




1 Type
EKA2-EU Smoke control damper

2 Casing variant

No entry: standard construction
1 powder-coated casing, RAL 7001 (silver grey)


3 Damper blade alignment

No entry: standard variant
7 coated damper blade


4 Country of destination

Specify country code

5 Nominal size [mm]

Width x height x length

Width × height

Width
200 – 1500

Height
200 – 800


Length
305, 500


6 Attachments 1

No entry: without attachment

2 entries required: attachment for operating side and for installation side

0 Side without attachment

A Crimped wire mesh (20 × 20 mm), galvanised steel

Q curved perforated metal plate with round perforations (Ø 6mm)

V Extension piece


7 Attachments 2

TROX actuator without expansion module
B24 Actuator 24 V AC/DC
B24SR1 Actuator B24 + control voltage Y = DC 2 - 10 V
B230 Actuator 230 V AC

Actuator + control module
TROX control modules with AS-i technology (TROXNETCOM)
B24A2 Actuator B24 + TROXNETCOM AS-EM/EK
B24AS2 Actuator B24 + TROXNETCOM AS-EM/SIL2
B24AM1 Actuator B24 + TROXNETCOM AS-EM/M

Communication and power supply unit
B24BKNE Actuator B24 + Belimo BKNE230-24
B24C Actuator B24 + BV-Control BC24E with SLC line

Smoke control damper module with Modbus/RTU protocol
B24D Actuator B24 + Agnosys BRM-10-F-ST
B230D Actuator B230 + Agnosys BRM-10-F


Order example: EKA2-1-7/BE/1200×800×305/A0/B24A

TypeEKA2-EU - Smoke control damper
Casing variantpowder-coated casing, RAL 7001 (silver grey)
Damper blade variantcoated damper blade
Country of destinationBelgium
Nominal size [mm]Width 1200, height 800, length 305
Attachment 1Operating side: crimped wire mesh (20 × 20 mm), galvanised steel;
installation side: no attachment


Attachment 2
Actuator 24 V AC/DC with TROXNETCOM AS-EM/EK


Downloads

Productinformatie

Certificaten

Handleidingen

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Content-Security-Policy"=>"frame-ancestors 'self' https://api.scrivito.com https://punchoutcommerce.com https://www.trox.de https://trox-extern.com https://psp40.onventis.com https://psp22.onventis.com https://trox4u.troxgroup.com", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Deel deze pagina

Beveel deze pagina aan

U kunt deze pagina delen door de link te delen.

Velden met een ster (*) zijn verplichte velden.

Contact

Bedankt voor uw bericht!

Uw aanbeveling is verzonden naar de ontvanger.

Contact

Wij zijn er om u te helpen.

Wilt u het onderwerp van uw aanvraag en uw contactgegevens specificeren a.u.b.
Tel.: +32 (0) 2/522 07 80

Velden met een ster (*) zijn verplichte velden.

Contact

Bedankt voor uw bericht!

Uw aanvraag is door ons ontvangen en wordt behandeld.
Onze afdeling voor service-aanvragen zal op korte termijn contact met u opnemen.
Voor algemene vragen over producten en diensten kunt u ons ook bereiken op:
Tel.: +32 (0) 2/522 07 80

Contact

Wij zijn er om u te helpen.

Wilt u het onderwerp van uw aanvraag en uw contactgegevens specificeren a.u.b.
Tel.: +32 (0) 2/522 07 80

Attachment (max. 10MB)

Velden met een ster (*) zijn verplichte velden.

Contact

Bedankt voor uw bericht!

Uw aanvraag is door ons ontvangen en wordt behandeld.
Onze afdeling voor service-aanvragen zal op korte termijn contact met u opnemen.
Voor algemene vragen over producten en diensten kunt u ons ook bereiken op:
Tel.: +32 (0) 2/522 07 80