TNC-EASYCONTROL_Z03_img_02jpg.jpg
TNC_EC_img_04psd.png
LED/buzzer combination

Signal lamp

Switch functions

S1 Shut-off CLOSED

S2 Maximum volume flow rate qᵥmax

S3 Damper blade OPEN

All open: Bus operation

When combining several override controls the switches must be interlocked to prevent short-circuits.

Diode: e.g. 1N 4007

TNC_EC-AZM_gc_01psd.png
Display module

Display module

Anzeigemodul

TNC-EASYCONTROL_Z03_img_02jpg.jpg
TNC_EC_img_04psd.png
TNC_EC-AZM_gc_01psd.png

TNC-EC-Z00–Z03 

System for controlling and monitoring fire dampers with and without a 24 V actuator


Stand-alone solution for control input signal and monitoring of up to 12 fire dampers with 24 V actuator or up to 24 damper blade end positions

  • Easy electrical installation with coded plug connections
  • Pre-installed application software
  • No additional programming required
  • Improves fire safety

General Information

Application

  • For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)
  • With installed user software, ready to use
  • Topology: star-shaped with 4-wire line
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Processing of a signal from the smoke detector or central fire alarm system
  • Automated and time-controlled functional test using external control by central BMS and manual triggering
  • Menu-driven operation and error display with integral LCD and softkeys
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Monitoring of the fire damper opening and closure times
  • Simple plug-in connection
  • Control system encased in sheet steel casing with cutout window, including power supply unit, completely wired and ready for plug-in
  • Output of alarm messages: fire, smoke, fire damper closed, fault during functional test, running/limit switch faults, duct smoke detector contamination

Technical information

Order code

  • ORDER CODE
TNC-EC-Z00
|
1
1 Product
TNC-EC-Z00 Standard construction in casing
TNC-EC-Z01 Standard construction with signal lamp
TNC-EC-Z02 Standard construction with display module
TNC-EC-Z03 Standard construction with signal lamp and display module
TNC-EC-GP Main PCB
TNC-EC-AZM Display module
TNC LINKBOX Linkbox/wiring aid
TP070EC Display and control panel as communication master

PRODUCT DATA

  • PRODUCT DATA

Application

  • For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)
  • With installed user software, ready to use
  • Topology: star-shaped with 4-wire line
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Processing of a signal from the smoke detector or central fire alarm system
  • Automated and time-controlled functional test using external control by central BMS and manual triggering
  • Menu-driven operation and error display with integral LCD and softkeys
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Monitoring of the fire damper opening and closure times
  • Simple plug-in connection
  • Control system encased in sheet steel casing with cutout window, including power supply unit, completely wired and ready for plug-in
  • Output of alarm messages: fire, smoke, fire damper closed, fault during functional test, running/limit switch faults, duct smoke detector contamination


Specification text

For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator - or up to 12 fire dampers with parallel operation); alternatively for capturing one end position each for up to 12 mechanical dampers (up to 24 limit switches with parallel operation); complete with switching power supply unit in a sheet steel casing, powder-coated RAL 9010 and with an acrylic glass window.



  • With installed user software, ready to use
  • CAN interface for connecting the external display
  • Supply voltage: 230 V AC ±10 %
  • Current consumption: < 150 mA (without external load)
  • Dimensions: 400 × 220 × 84 mm (B x H x T)
  • Installation: on a wall
  • Protection level: IP 40
  • Power supply: 230 V AC/50 Hz
  • Operating manual
  • Make: TROX GmbH or equivalent
  • Type: TNC-EC-Z00


Technical data, main PCB


Electrical design16 inputs/outputs
Supply voltage24 V DC, -15 – 25%
Current consumption< 150 mA
Operating temperature0 – 40 °C
ConstructionOpen PCB
Protection levelIP 00
Dimensions B x H x T162 × 126 × 75 mm
ConnectionScrew terminals
FixingOn mounting rail (if mounted with casing)
Program memory256 kB
Data memorySRAM 2 × 128 kByte, EEPROM 1 kByte 256 kB
Interface1× RS232C, 9.6 kBaud, CAN1, CAN2, CANopen protocol
Status displayPower LED - green; status LEDs - green and red; programmed 8-digit LCD
Operating buttons3 Softkeys
Number of inputs16, common reference point (GND)
DisplayYellow LED
Input voltage24 V DC nominal
Input currentTypically 10 mA
Activation level high15 – 30 V DC
Deactivation level low0 – 5.5 V DC
Number of outputs16 (2 × 8), 24 V DC for 8 outputs each
DisplayLED red
Switching voltage12 – 34 V DC, 24 V DC nominal
Switching current1.1 A per output
Coincidence factor100 %
Short circuit protection>6 A (electronic) per channel


Technical data, switching power supply unit


Input voltage230 V AC
Output voltage

24 V DC


Output current

6.5 A


External fuse, outputT4 L/250 V (fuse in switch box)

Ambient temperature



-25 to 75 °C


Protection levelIP20
Dimensions B x H x T97 × 174 × 38 mm
ConnectionScrew terminals up to 2.5 mm²
FixingOn mounting rail


Technical data, casing


Dimensions (B × H × T)400 × 220 × 84 mm
Casing materialGalvanised sheet steel, powder-coated RAL 9010
Inspection windowPlexiglass XT, colourless
ComponentsInstalled on mounting rail
Protection levelIP 40



Control system TNC-EC-Z01

Application

  • For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)
  • With installed user software, ready to use
  • Topology: star-shaped with 4-wire line
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Processing of a signal from a duct smoke detector or central fire alarm system
  • Automated and time-controlled functional test using external control by central BMS and manual triggering
  • Menu-driven operation and error display with integral LCD and softkeys
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Monitoring of the fire damper opening and closure times
  • Simple plug-in connection
  • Control system encased in sheet steel casing with cutout window, including power supply unit, completely wired and ready for plug-in
  • Output of alarm messages: fire, smoke, fire damper closed, fault during functional test, running/limit switch faults, duct smoke detector contamination
  • Signal lamp for alarm signalling, mounted into the cover plate and completely wired (ready to use)


Specification text

For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers in parallel operation) or optionally for end position detection of up to 12 mechanical dampers with one end position each (up to 24 limit switches in parallel operation); complete with switching power supply unit in a sheet steel casing, powder-coated RAL9010 and with an acrylic glass window; with a signal lamp for alarm signalling, mounted into the cover plate and completely wired (ready to use)



  • With installed user software, ready to use
  • CAN interface for connecting the external display
  • Supply voltage: 230 V AC ±10 %
  • Current consumption: < 150 mA (without external load)
  • Dimensions: 400 × 220 × 84 mm (B x H x T)
  • Installation: on a wall
  • Protection level: IP 40
  • Power supply: 230 V AC/50 Hz
  • Operating manual
  • Make: TROX GmbH or equivalent
  • Type: TNC-EC-Z01

Technical data, main PCB


Electrical design16 inputs/outputs
Supply voltage24 V DC, -15 – 25%
Current consumption< 150 mA
Operating temperature0 – 40 °C
ConstructionOpen PCB
Protection levelIP 00
Dimensions B x H x T162 × 126 × 75 mm
ConnectionScrew terminals
FixingOn mounting rail (if mounted with casing)
Program memory256 kB
Data memorySRAM 2 × 128 kByte, EEPROM 1 kByte 256 kB
Interface1× RS232C, 9.6 kBaud, CAN1, CAN2, CANopen protocol
Status displayPower LED - green; status LEDs - green and red; programmed 8-digit LCD
Operating buttons3 Softkeys
Number of inputs16, common reference point (GND)
DisplayYellow LED
Input voltage24 V DC nominal
Input currentTypically 10 mA
Activation level high15 – 30 V DC
Deactivation level low0 – 5.5 V DC
Number of outputs16 (2 × 8), 24 V DC for 8 outputs each
DisplayLED red
Switching voltage12 – 34 V DC, 24 V DC nominal
Switching current1.1 A per output
Coincidence factor100 %
Short circuit protection>6 A (electronic) per channel



Technical data, power supply unit


Input voltage230 V AC
Output voltage

24 V DC


Output current

6.5 A


External fuse, outputT4 L/250 V (fuse in switch box)

Ambient temperature



-25 to 75 °C


Protection levelIP20
Dimensions B x H x T97 × 174 × 38 mm
ConnectionScrew terminals up to 2.5 mm²
FixingOn mounting rail



Technical data, casing


Dimensions (B × H × T)400 × 220 × 84 mm
Casing materialGalvanised sheet steel, powder-coated RAL 9010
Inspection windowPlexiglass XT, colourless
ComponentsInstalled on mounting rail
Protection levelIP 40



Technical data, signal lamp


CasingPC-ABS blend
Dome capPC, transparent
Illumination patternLED continuous
Type of toneContinuous tone
Dimensions (Ø × H)49.5 × 75 mm
Noise level80 dB
Tone frequency3 kHz
Switch-on current0.5 A
Current consumption80 mA
Supply voltage24 V DC
Protection levelIP65
Service life50,000 h
ConnectionPlug with screw terminal, max. 0.5 mm²
,

Control system TNC-EC-Z02

,

Application

  • For controlling and monitoring of up to 6 motorised fire dampers with a 24-V actuator (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)
  • With installed user software, ready to use
  • Topology: star-shaped with 4-wire line
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Processing of a signal from a duct smoke detector or central fire alarm system
  • Automated and time-controlled functional test using external control by central BMS and manual triggering
  • Menu-driven operation and error display with integral LCD and softkeys
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Monitoring of the fire damper opening and closure times
  • Simple plug-in connection
  • Control system encased in sheet steel casing with cutout window, including power supply unit, completely wired and ready for plug-in
  • Output of alarm messages: fire, smoke, fire damper closed, fault during functional test, running/limit switch faults, duct smoke detector contamination
  • With 2.8 inch display module mounted into the cover plate and completely wired (ready to use), for displaying damper blade positions
  • For controlling individual fire dampers
  • For starting a functional test


Specification text

For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers in parallel operation) or optionally for capturing of the end positions of up to 12 mechanical dampers with one end position each (up to 24 limit switches in parallel operation); with a switching power supply unit in a sheet steel casing, powder-coated RAL9010 and with an acrylic glass window, with a 2.8 inch display module mounted into the cover plate and completely wired (ready to use), for displaying damper blade positions, for controlling individual fire dampers, and for starting a functional test



  • With installed user software, ready to use
  • CAN interface for connecting the external display
  • Supply voltage: 230 V AC ±10 %
  • Current consumption: < 150 mA (without external load)
  • Dimensions: 400 × 220 × 84 mm (B × H × T)
  • Installation: on a wall
  • Protection level: IP 40
  • Power supply: 230 V AC/50 Hz
  • Operating manual
  • Make: TROX GmbH or equivalent
  • Type: TNC-EC-Z02


Technical data, main PCB


Electrical design16 inputs/outputs
Supply voltage24 V DC, -15 – 25%
Current consumption< 150 mA
Operating temperature0 – 40 °C
ConstructionOpen PCB
Protection levelIP 00
Dimensions B x H x T162 × 126 × 75 mm
ConnectionScrew terminals
FixingOn mounting rail (if mounted with casing)
Program memory256 kB
Data memorySRAM 2 × 128 kByte, EEPROM 1 kByte 256 kB
Interface1× RS232C, 9.6 kBaud, CAN1, CAN2, CANopen protocol
Status displayPower LED - green; status LEDs - green and red; programmed 8-digit LCD
Operating buttons3 Softkeys
Number of inputs16, common reference point (GND)
DisplayYellow LED
Input voltage24 V DC nominal
Input currentTypically 10 mA
Activation level high15 – 30 V DC
Deactivation level low0 – 5.5 V DC
Number of outputs16 (2 × 8), 24 V DC for 8 outputs each
DisplayLED red
Switching voltage12 – 34 V DC, 24 V DC nominal
Switching current1.1 A per output
Coincidence factor100 %
Short circuit protection>6 A (electronic) per channel



Technical data, power supply unit


Input voltage230 V AC
Output voltage

24 V DC


Output current

6.5 A


External fuse, outputT4 L/250 V (fuse in switch box)

Ambient temperature



-25 to 75 °C


Protection levelIP20
Dimensions B x H x T97 × 174 × 38 mm
ConnectionScrew terminals up to 2.5 mm²
FixingOn mounting rail



Technical data, casing


Dimensions (B × H × T)400 × 220 × 84 mm
Casing materialGalvanised sheet steel, powder-coated RAL 9010
Inspection windowPlexiglass XT, colourless
ComponentsInstalled on mounting rail
Protection levelIP 40


Technical data, display module


Display2.8 inch TFT colour LCD
Resolution320 × 240 pixels
Colours256
BacklightingLED
Dimensions B x H x T87.5 × 87.5 × 37.7 mm
Casing materialPlastic, black
Buttons5 function buttons
Rocker switchCursor functions (UP, DOWN, LEFT, RIGHT)
Protection levelIP 67 when installed in the front panel of the casing, otherwise IP 65
Operating temperature-20 to 30 °C
Supply voltage8 – 32 V DC
Current consumption70 mA at 24 V DC
CAN interfaceCANopen protocol


Control system TNC-EC-Z03

Application

  • For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)
  • With installed user software, ready to use
  • Topology: star-shaped with 4-wire line
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Processing of a signal from a duct smoke detector or central fire alarm system
  • Automated and time-controlled functional test using external control by central BMS and manual triggering
  • Menu-driven operation and error display with integral LCD and softkeys
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Monitoring of the fire damper opening and closure times
  • Simple plug-in connection
  • Control system encased in sheet steel casing with cutout window, including power supply unit, completely wired and ready for plug-in
  • Output of alarm messages: fire, smoke, fire damper closed, fault during functional test, running/limit switch faults, duct smoke detector contamination
  • Signal lamp for alarm signalling, mounted into the cover plate and completely wired (ready to use)
  • With 2.8 inch display module mounted into the cover plate and completely wired (ready to use), for displaying damper blade positions
  • For controlling individual fire dampers
  • For starting a functional test


Specification text

For controlling and monitoring up to 6 motorised fire dampers with a 24 V actuator (up to 12 fire dampers in parallel operation) or optionally for capturing of the end positions of up to 12 mechanical dampers with one end position each (up to 24 limit switches in parallel operation); with a switching power supply unit in a sheet steel casing, powder-coated RAL9010 and with an acrylic glass window; with a signal lamp for alarm signalling, mounted in the front cover and functionally wired, with a 2.8 inch display module mounted into the cover plate and completely wired (ready to use), for displaying damper blade positions, for controlling individual fire dampers, and for starting a functional test



  • With installed user software, ready to use
  • CAN interface for connecting the external display
  • Supply voltage: 230 V AC ±10 %
  • Current consumption: < 150 mA (without external load)
  • Dimensions: 400 × 220 × 84 mm (B x H x T)
  • Installation: on a wall
  • Protection level: IP 40
  • Power supply: 230 V AC/50 Hz
  • Operating manual
  • Make: TROX GmbH or equivalent
  • Type: TNC-EC-Z03


Technical data, main PCB


Electrical design16 inputs/outputs
Supply voltage24 V DC, -15 – 25%
Current consumption< 150 mA
Operating temperature0 – 40 °C
ConstructionOpen PCB
Protection levelIP 00
Dimensions B x H x T162 × 126 × 75 mm
ConnectionScrew terminals
FixingOn mounting rail (if mounted with casing)
Program memory256 kB
Data memorySRAM 2 × 128 kByte, EEPROM 1 kByte 256 kB
Interface1× RS232C, 9.6 kBaud, CAN1, CAN2, CANopen protocol
Status displayPower LED - green; status LEDs - green and red; programmed 8-digit LCD
Operating buttons3 Softkeys
Number of inputs16, common reference point (GND)
DisplayYellow LED
Input voltage24 V DC nominal
Input currentTypically 10 mA
Activation level high15 – 30 V DC
Deactivation level low0 – 5.5 V DC
Number of outputs16 (2 × 8), 24 V DC for 8 outputs each
DisplayLED red
Switching voltage12 – 34 V DC, 24 V DC nominal
Switching current1.1 A per output
Coincidence factor100 %
Short circuit protection>6 A (electronic) per channel



Technical data, power supply unit


Input voltage230 V AC
Output voltage

24 V DC


Output current

6.5 A


External fuse, outputT4 L/250 V (fuse in switch box)

Ambient temperature



-25 to 75 °C


Protection levelIP20
Dimensions B x H x T97 × 174 × 38 mm
ConnectionScrew terminals up to 2.5 mm²
FixingOn mounting rail



Technical data, casing


Dimensions (B × H × T)400 × 220 × 84 mm
Casing materialGalvanised sheet steel, powder-coated RAL 9010
Inspection windowPlexiglass XT, colourless
ComponentsInstalled on mounting rail
Protection levelIP 40



Technical data, signal lamp


CasingPC-ABS blend
Dome capPC, transparent
Illumination patternLED continuous
Type of toneContinuous tone
Dimensions (Ø × H)49.5 × 75 mm
Noise level80 dB
Tone frequency3 kHz
Switch-on current0.5 A
Current consumption80 mA
Supply voltage24 V DC
Protection levelIP65
Service life50,000 h
ConnectionPlug with screw terminal, max. 0.5 mm²



Technical data, display module


Display2.8 inch TFT colour LCD
Resolution320 × 240 pixels
Colours256
BacklightingLED
Dimensions B x H x T87.5 × 87.5 × 37.7 mm
Casing materialPlastic, black
Buttons5 function buttons
Rocker switchCursor functions (UP, DOWN, LEFT, RIGHT)
Protection levelIP 67 when installed in the front panel of the casing, otherwise IP 65
Operating temperature-20 to 30 °C
Supply voltage8 – 32 V DC
Current consumption70 mA at 24 V DC
CAN interfaceCANopen protocol



Connection box – TNC-LINKBOX

Application

Module to be combined with TNC-EASYCONTROL for controlling motorised fire dampers and for capturing the damper blade end positions.


  • Quick and easy connection of actuator cables to TNC-EASYCONTROL (as connection box)
  • 24 V DC power supply to actuator
  • Ready to be used with actuators with AMP plug
  • Capturing damper blade positions OPEN and CLOSED
  • Parallel operation of 2 damper actuators (as distribution box)
  • Easy function change with a jumper on the PCB

Specification text

Module for quick and easy connection of the actuator control cables to TNC-EASYCONTROL (as connection box); if there are 2 motorised fire dampers in parallel operation, the LINKBOX acts as a distributor box. Can be attached to fire dampers with a mounting bracket (accessory ZA14).



  • Supply voltage: 24 V DC
  • Current consumption: ≤ 850 mA
  • Ambient temperature: -5 – 75 °C
  • Protection level: IP 42
  • Make: TROX GmbH or equivalent
  • Type: TNC-LINKBOX


Technical data


DescriptionTNC-LINKBOX

Supply voltage

24 V DC

Current consumption

≤ 850 mA
IEC protection classIP 42
Double-stack terminal block4-pole; 0.12 – 1.5 mm²
Socket, type AMP Mate-N-LOKControl cable, 3-pole; end positions, 6-pole


 Main PCB – TNC-EC-GP

Application

  • Single PCB control for installation on a mounting rail
  • Stand-alone solution for controlling and monitoring up to 6 motorised fire dampers with 24 V DC (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)
  • With installed user software, ready to use
  • Menu-driven operation with integral LCD and softkeys on the main PCB, signalling with LEDs
  • Topology: star-shaped with 4-wire line
  • Processing of a signal from the duct smoke detector or central fire alarm system (smoke detection, contamination of duct smoke detector)
  • Manual control (OPEN/CLOSE) of individual fire dampers
  • Automatic functional test


Specification text

Single PCB control for controlling and monitoring up to 6 motorised fire dampers with 24 V DC (up to 12 fire dampers with parallel operation); alternatively for capturing the end positions of up to 12 mechanical dampers with one limit switch (up to 24 limit switches with parallel operation)



  • With installed user software
  • CAN bus interface for the connection of an external display and control panel
  • Supply voltage: 24 V DC, -15 – 25 %
  • Current consumption: < 150 mA (without external load)
  • Dimensions: 162 × 126 × 75 mm (B x H x T)
  • Installation: on mounting rail
  • Make: TROX GmbH or equivalent
  • Type: TNC-EC-GP

Display module – TNC-EC-AZM








Application

  • Display module for menu-driven operation and error display
  • 2.8 inch colour LED and backlit function buttons with rocker switch for cursor allow for menu-driven operation and error display
  • Language selection (German, English, Finnish; other languages upon request)
  • Connecting cable for data and supply voltage, standard length of 5 m
  • Menu-driven functional test
  • Manual control of fire dampers
  • Password protection



Specification text

Menu-driven operation and display of the TNC-EASYCONTROL control system.



  • 2.8 inch colour LCD with 5 function buttons and rocker switch for cursor
  • Language selection (for operation and display): German, English, Finnish
  • CAN bus interface
  • Supply voltage: 8 – 32 V DC
  • Current consumption: 70 mA at 24 V DC
  • Dimensions: 87.5 × 87.5 × 37.5 mm (B x H x T)
  • Casing: plastic, black
  • Protection level: IP 67 when installed in the front panel of the casing, otherwise IP 65
  • Operating manual
  • Make: TROX GmbH or equivalent
  • Type: TNC-EC-AZM

Display and control panel – TP070EC




















Application

  • 7.0 inch MMI system for display, operation and as communication master for up to 2 TNC-EASYCONTROL units
  • ModBus TCP and BACnet/IP interfaces for integration with central BMS without additional project engineering work
  • With integral TNC Basic User Software/EC


Specification text

MMI system for display, operation and as communication master for up to 2 TNC-EASYCONTROL units



  • 7.0 inch colour display, touchscreen
  • Interfaces: ModBus RTU/TCP and BACnet/IP interfaces for integration with the central BMS (no additional design effort required)
  • With Basic User Software/EC for controlling and for the display of all system status values
  • Automatic functional test, including documentation
  • Real time clock
  • Ethernet, USB
  • Dimensions of front panel (B x H x T): 197 × 136 × 3 mm
  • Protection level: Front IP 65; back IP 20
  • Supply voltage 24 V DC
  • Make: TROX GmbH or equivalent
  • Type: TP070EC


Technical data


DescriptionTP070EC
DisplayWidescreen 16:9
OperationTouch screen (PCAP multi touch sensor)
CasingMetal
Front panel materialAnti-reflective and tempered glass
Front panel B × H × T197 × 136 mm × 3 mm
Cut-out B × H184 × 122 mm
Installation depth44.5 mm
Protection levelIP65 front, IP20 back
Total weightApprox. 450 g
InterfacesCAN bus Ethernet, USB
Memory1 GB (4 GB max.) NAND flash (optional), 1 x SD card slot
Temperature range

0 to 55 °C


Supply voltage24 V DC via control unit

Current consumption



0.5 A


Power requiredApprox. 12 W

TNC Easycontrol Commissioning

Downloads

product information

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be