Application
Nominal sizes
Parts and characteristics
Construction features
Material and surfaces
Standards and guidelines
Maintenance
Useful additions
Nominal sizes | 100 – 400 mm |
Volume flow rate range | 12 - 750 l/s or 41 - 2700 m3/h |
Electrical power consumption | 0.4 – 9 kW |
Minimum airflow velocity | 1.5 m/s (airflow monitoring required, by others) |
Maximum outlet airflow temperature | 50 °C (capacity control required, by others) |
Maximum operating temperature | Without integral control = 40 °C max. |
Release temperature – temperature monitor TW | Approx. 60 °C (automatic reset if the value falls below this temperature; hysteresis approx. 15 K) |
Release temperature for thermal cut-out | Approx. 90 °C (manual reset on the air heater required) |
Air-side static differential pressure | 1 – 20 |
Supply voltage NS 100 | 230 V AC, 400 W |
Supply voltage NS 125 | 230 V AC, 900 W |
Supply voltage NS 160 | 230 V AC, 1,200 W |
Supply voltage NS 200 | 230 V AC, 2,100 W |
Supply voltage NS 250 | 400 V AC 2-phase, 3,000 W |
Supply voltage NS 315 | 400 V AC 3-phase, 6,000 W |
Supply voltage NS 400 | 400 V AC 3-phase, 9,000 W |
Protection level | IP 43 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU |
Licence | CE, UKCA, S, EAC |
Technische Daten zum Elektrolufterhitzer
Grundgeräte: TVR, RN und VFC
NG | qv | ∆pst [Pa] | te = 16 °C | ||
---|---|---|---|---|---|
l/s | m³/h | P [kW] | ta [°C] | ||
100 | 12 | 43 | 5 | 0,4 | 44 |
100 | 20 | 72 | 10 | 0,4 | 33 |
100 | 30 | 108 | 15 | 0,4 | 27 |
100 | 40 | 144 | 25 | 0,4 | 24 |
100 | 45 | 162 | 30 | 0,4 | 23 |
125 | 24 | 85 | 5 | 0,9 | 48 |
125 | 35 | 126 | 20 | 0,9 | 37 |
125 | 50 | 180 | 40 | 0,9 | 31 |
125 | 65 | 234 | 60 | 0,9 | 27 |
125 | 75 | 270 | 80 | 0,9 | 26 |
160 | 30 | 108 | 5 | 1,2 | 49 |
160 | 50 | 180 | 10 | 1,2 | 36 |
160 | 70 | 252 | 15 | 1,2 | 30 |
160 | 95 | 342 | 25 | 1,2 | 26 |
160 | 115 | 414 | 35 | 1,2 | 25 |
200 | 59 | 210 | 5 | 2,1 | 46 |
200 | 80 | 288 | 20 | 2,1 | 38 |
200 | 115 | 414 | 35 | 2,1 | 31 |
200 | 150 | 540 | 55 | 2,1 | 28 |
200 | 180 | 648 | 80 | 2,1 | 26 |
250 | 77 | 275 | 5 | 3 | 49 |
250 | 125 | 450 | 15 | 3 | 36 |
250 | 180 | 648 | 25 | 3 | 30 |
250 | 235 | 846 | 40 | 3 | 27 |
250 | 290 | 1044 | 60 | 3 | 25 |
315 | 153 | 550 | 5 | 6 | 49 |
315 | 200 | 720 | 15 | 6 | 41 |
315 | 285 | 1026 | 25 | 6 | 33 |
315 | 375 | 1350 | 40 | 6 | 29 |
315 | 460 | 1656 | 60 | 6 | 27 |
400 | 228 | 820 | 5 | 9 | 49 |
400 | 325 | 1170 | 15 | 9 | 39 |
400 | 465 | 1674 | 30 | 9 | 32 |
400 | 605 | 2178 | 50 | 9 | 28 |
400 | 750 | 2700 | 75 | 9 | 26 |
P: elektrische Leistung
te: Lufteinströmtemperatur
ta: Luftausströmtemperatur
qv: Volumenstrom
Δpst: statische Druckdifferenz
Specification text
Electric air heater for reheating airflows in ventilation and air conditioning systems. Dimensions fit VAV terminal units TVR as well as CAV controllers RN and VFC. Integral twofold overheating protection with temperature monitor and thermal cut-out. Spigot with lip seal for ducts according to EN 1506 or EN 13180. Casing leakage according to EN 15727, class C.
Materials and surfaces
Technical data
Sizing data
EL | / | 160 |
| | | | |
1 | 2 |
Nominal size | 160 mm |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be