Application
Special characteristics
Nominal sizes
Variants
Connection
Vertical connection:
Direct installation of the spigot to the on-site duct network with suspension lugs
With suspension lugs on the spigot (only serves to support the dead weight of the air diffuser)
Horizontal connection:
Combination with a suitable plenum box from the AK-Uni series (supply package)
Perforated sheet metal front (perforated sheet metal types see link)
Without perforated sheet metal front
For installation behind standard perforated metal ceiling tiles provided by the customer
Free area ≥ 15 %
Required thickness ≤ 1 mm, preferably ≤ 0.7 mm
LBK (perforated sheet metal front stapled)
Included in supply package: Perforated sheet metal front RV 6.0 - 8.0
Free area approx. 51 %
Attachment to discharge nozzle with brackets
Particularly suited for inserting into T-bar ceilings
Fixed connection of the diffuser face to the plenum box or spigot
LBS (perforated sheet metal front screwed)
Included in supply package: Perforated sheet metal front RV 6.0 - 8.0
Free area approx. 51 %
Attachment using lugs in the edge area of the discharge nozzle
For direct installation below the suspended ceiling
Fastening the air diffuser to the crossbar in the plenum box (-H) or spigot (-V) using a central fixing screw
Detachable and removable air diffuser
Parts and characteristics
Attachments
Perforated sheet metal front
Accessories
Construction features
Standards and guidelines
Maintenance
Ceiling swirl diffusers allow the supply air from ventilation systems to flow into the room in a swirl pattern. The resulting airflow induces high levels of indoor air, thereby rapidly reducing the airflow velocity and the temperature difference between supply air and room air. Ceiling swirl diffusers enable large volume flow rates. The result is a mixed flow ventilation in comfort zones, with good overall indoor ventilation, creating only low turbulence in the occupied zone. TROX INVISIBLE DIFFUSER (TID) are characterised by their unobtrusive or inconspicuous installation. The swirl unit required for the swirling air discharge is not visible from the room. The special shape of the discharge nozzle allows the swirl effect to be used even behind standard perforated metal ceiling tiles or factory-made perforated metal sheet fronts. Type TID ceiling swirl diffusers have fixed air control blades. Air distribution is horizontal, with an omni-directional flow. The supply air to room air temperature difference may range from –12 to +10 K. A damper element in the plenum box simplifies volume flow rate balancing for commissioning. To give rooms an aesthetic, uniform look, Type TID diffusers may also be used for extract air.
Nominal sizes | 160, 250, 300, 400, 600, 625 mm |
Nominal diameter | 125, 160, 200, 250, 315 mm |
Supply air to room air temperature difference | -12 – +10 K |
The quick sizing table gives a good overview of the possible volume flow rates and the corresponding sound power levels and differential pressure levels for the combinations with the different perforated sheet metal fronts. The minimum volume flow rates apply to a supply air to room air temperature difference of -6 K. The maximum volume flow rates apply to a sound power level of approx. 50 dB (A) with damper blade position 0°. Exact values for all parameters can be determined with our Easy Product Finder design program. The quick sizing tables for various sample perforations are listed below:
TID (RG 2516 or RG 2.5–5.5), sound power level and total differential pressure
DN | qv [l/s] | qv [m³/h] | Damper blade position | |||||
---|---|---|---|---|---|---|---|---|
0° Δpt [Pa] | 0° LWA [dB(A)] | 45° Δpt [Pa] | 45° LWA [dB(A)] | 90° Δpt [Pa] | 90° LWA [dB(A)] | |||
125 | 21 | 76 | 41 | 38 | 49 | 40 | 72 | 39 |
25 | 90 | 56 | 43 | 68 | 44 | 100 | 43 | |
29 | 103 | 75 | 47 | 90 | 48 | 133 | 47 | |
32 | 117 | 95 | 50 | 116 | 51 | 170 | 50 | |
160 | 23 | 83 | 17 | 27 | 21 | 29 | 33 | 28 |
33 | 118 | 34 | 37 | 41 | 38 | 66 | 38 | |
42 | 152 | 58 | 44 | 69 | 46 | 111 | 46 | |
52 | 187 | 87 | 50 | 103 | 51 | 167 | 52 | |
200 | 37 | 132 | 19 | 28 | 19 | 28 | 30 | 29 |
51 | 182 | 36 | 37 | 37 | 38 | 57 | 38 | |
65 | 233 | 59 | 44 | 60 | 45 | 94 | 46 | |
79 | 284 | 87 | 50 | 90 | 50 | 139 | 51 | |
250 | 58 | 207 | 20 | 28 | 24 | 29 | 32 | 31 |
77 | 276 | 35 | 37 | 42 | 39 | 57 | 40 | |
96 | 344 | 54 | 44 | 65 | 46 | 89 | 47 | |
115 | 413 | 78 | 50 | 93 | 52 | 128 | 53 | |
315 | 90 | 325 | 25 | 33 | 28 | 34 | 37 | 34 |
112 | 402 | 38 | 39 | 43 | 40 | 57 | 41 | |
133 | 480 | 54 | 45 | 62 | 46 | 81 | 46 | |
155 | 557 | 73 | 50 | 83 | 51 | 110 | 50 |
TID (RD 2820 or RD 2.8–5.5), sound power level and total differential pressure
DN | qv [l/s] | qv [m³/h] | Damper blade position | |||||
---|---|---|---|---|---|---|---|---|
qv [m³/h] | 0° Δpt [Pa] | 0° LWA [dB(A)] | 45° Δpt [Pa] | 45° LWA [dB(A)] | 90° Δpt [Pa] | 90° LWA [dB(A)] | ||
125 | 17 | 63 | 24 | 32 | 30 | 33 | 46 | 33 |
23 | 83 | 43 | 39 | 53 | 41 | 80 | 40 | |
29 | 103 | 66 | 45 | 81 | 47 | 123 | 46 | |
34 | 123 | 93 | 50 | 116 | 51 | 175 | 51 | |
160 | 27 | 97 | 21 | 30 | 25 | 32 | 43 | 32 |
36 | 130 | 38 | 38 | 45 | 40 | 77 | 40 | |
45 | 163 | 59 | 45 | 71 | 46 | 122 | 47 | |
55 | 196 | 86 | 50 | 103 | 51 | 176 | 52 | |
200 | 39 | 139 | 19 | 28 | 20 | 29 | 31 | 30 |
53 | 191 | 36 | 37 | 37 | 38 | 59 | 39 | |
68 | 243 | 58 | 44 | 60 | 45 | 96 | 46 | |
82 | 296 | 86 | 50 | 89 | 51 | 142 | 51 | |
250 | 54 | 194 | 16 | 25 | 19 | 27 | 27 | 28 |
76 | 272 | 30 | 36 | 38 | 37 | 52 | 39 | |
97 | 349 | 50 | 44 | 62 | 45 | 86 | 47 | |
119 | 427 | 75 | 50 | 93 | 52 | 128 | 53 | |
315 | 87 | 312 | 20 | 30 | 23 | 31 | 31 | 32 |
111 | 401 | 33 | 38 | 39 | 39 | 52 | 39 | |
136 | 491 | 50 | 45 | 58 | 46 | 78 | 46 | |
161 | 580 | 70 | 50 | 81 | 51 | 109 | 51 |
TID (RV 5046 or RV 5–7), sound power level and total differential pressure
DN | qv [l/s] | qv [m³/h] | Damper blade position | |||||
---|---|---|---|---|---|---|---|---|
qv [m³/h] | 0° Δpt [Pa] | 0° LWA [dB(A)] | 45° Δpt [Pa] | 45° LWA [dB(A)] | 90° Δpt [Pa] | 90° LWA [dB(A)] | ||
125 | 14 | 49 | 12 | 25 | 15 | 27 | 25 | 27 |
21 | 76 | 29 | 36 | 38 | 38 | 61 | 37 | |
29 | 104 | 54 | 44 | 70 | 45 | 112 | 45 | |
36 | 131 | 87 | 50 | 112 | 51 | 180 | 51 | |
160 | 23 | 83 | 12 | 25 | 16 | 27 | 29 | 27 |
34 | 123 | 27 | 36 | 34 | 38 | 63 | 38 | |
45 | 163 | 47 | 44 | 60 | 45 | 110 | 46 | |
56 | 203 | 74 | 50 | 93 | 51 | 170 | 52 | |
200 | 37 | 132 | 13 | 27 | 14 | 27 | 24 | 28 |
54 | 195 | 29 | 37 | 31 | 38 | 54 | 38 | |
72 | 259 | 51 | 44 | 54 | 45 | 94 | 46 | |
90 | 322 | 79 | 50 | 83 | 51 | 146 | 51 | |
250 | 52 | 187 | 11 | 24 | 13 | 24 | 21 | 26 |
77 | 277 | 25 | 35 | 30 | 36 | 47 | 38 | |
102 | 367 | 43 | 44 | 52 | 44 | 82 | 46 | |
127 | 457 | 67 | 50 | 81 | 51 | 127 | 53 | |
315 | 69 | 249 | 10 | 23 | 12 | 25 | 17 | 25 |
103 | 372 | 22 | 35 | 27 | 36 | 38 | 36 | |
138 | 495 | 39 | 43 | 48 | 45 | 68 | 45 | |
172 | 618 | 61 | 50 | 75 | 51 | 106 | 51 |
TID (RV 6051 or RV 6–8), sound power level and total differential pressure
DN | qv [l/s] | qv [m³/h] | Damper blade position | |||||
---|---|---|---|---|---|---|---|---|
qv [m³/h] | 0° Δpt [Pa] | 0° LWA [dB(A)] | 45° Δpt [Pa] | 45° LWA [dB(A)] | 90° Δpt [Pa] | 90° LWA [dB(A)] | ||
125 | 14 | 49 | 10 | 23 | 14 | 25 | 23 | 24 |
22 | 79 | 27 | 36 | 37 | 37 | 61 | 37 | |
31 | 110 | 52 | 44 | 71 | 46 | 118 | 45 | |
39 | 141 | 86 | 50 | 116 | 52 | 194 | 51 | |
160 | 23 | 83 | 10 | 23 | 14 | 24 | 26 | 26 |
36 | 129 | 25 | 35 | 33 | 37 | 64 | 37 | |
49 | 175 | 46 | 44 | 61 | 45 | 117 | 45 | |
61 | 221 | 74 | 50 | 97 | 52 | 187 | 51 | |
200 | 37 | 132 | 11 | 23 | 12 | 24 | 22 | 25 |
57 | 205 | 26 | 35 | 28 | 36 | 54 | 37 | |
77 | 278 | 48 | 44 | 52 | 45 | 99 | 46 | |
98 | 351 | 77 | 50 | 82 | 51 | 158 | 52 | |
250 | 52 | 187 | 9 | 22 | 12 | 23 | 19 | 24 |
80 | 290 | 22 | 34 | 30 | 36 | 46 | 37 | |
109 | 393 | 40 | 43 | 54 | 45 | 85 | 46 | |
138 | 496 | 64 | 50 | 87 | 52 | 136 | 53 | |
315 | 69 | 249 | 8 | 21 | 10 | 23 | 15 | 23 |
109 | 392 | 19 | 34 | 25 | 36 | 37 | 36 | |
148 | 534 | 36 | 43 | 46 | 45 | 69 | 45 | |
188 | 676 | 57 | 50 | 73 | 52 | 111 | 52 |
Specification text
Ceiling swirl diffusers for invisible or inconspicuous installation behind standard metal ceiling tiles or factory-made perforated sheet metal fronts. The ceiling swirl diffuser is suitable for comfort and industrial zones and is installed as a supply or extract air diffuser in the suspended ceiling. The swirling element with fixed air control blades enable a horizontal swirling supply air discharge creating high induction levels so that the airflow velocities and temperature differences are quickly reduced. The special shape of the discharge nozzle allows the swirl diffuser to be used behind standard perforated metal ceiling tiles. To ensure a visually uniform ceiling appearance, the standard metal ceiling tiles must not be thicker than 1.0 mm. Preferred thickness: ≤ 0.7 mm. The ceiling swirl diffuser can be combined with ceilings of all types using a factory-fitted perforated sheet metal front. The ready-to-install functional unit consists of the specially moulded discharge nozzle, the swirl element with fixed air control blades and spigot and is always coated black. The functional unit can be connected directly to the on-site air duct system or combined with a plenum box from the AK-Uni series. In case of a vertical connection, suspension lugs are provided for on-site fixing to the spigot. The plenum box has drilled holes for on-site fixing. All spigots are suitable for ducts according to EN 1506 or EN 13180. The sound power level of the air-regenerated noise is measured according to EN ISO 5135.
Special features
Materials and surfaces
Technical data
Sizing data
qv [m³/h]
Δpt [Pa]
air-regenerated noise
LWA [dB(A)]
TID | – | Z | – | H | – | M | – | L | / | 600 | × | 160 | / | LBS | / | P1 - RAL 9016 |
| | | | | | | | | | | | | | | | | | ||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
Order example: TID–Z–V/600×160
System | Supply air |
Connection | vertical |
Nominal size | 600 |
Nominal width | 160 |
Dimension Q₁
NS | Q1 | ||
---|---|---|---|
LBK | LBS | ||
300 | 290 | - | - |
400 | 390 | - | - |
600 | 590 | 593 | 598 |
625 | 615 | 618 | 623 |
Dimensions horizontal connection
DN= ØD4 | ØD | LBK | LBK | LBS | H4 | H3 | Q3 | C | A | b | AK | |||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
H | H5 | H | H5 | H | H5 | |||||||||
125 | 98 | 66 | 8 | 66 | 10 | 67 | 8 | 195 | 255 | 216 | 50 | 170 | 50 | AK028 |
160 | 123 | 69 | 8 | 69 | 10 | 70 | 8 | 220 | 280 | 266 | 48 | 182 | 50 | AK029 |
200 | 158 | 75 | 8 | 75 | 10 | 76 | 8 | 250 | 310 | 290 | 50 | 194 | 50 | AK030 |
250 | 198 | 76 | 8 | 77 | 10 | 77 | 8 | 295 | 355 | 476 | 50 | 219 | 90 | AK031 |
315 | 248 | 78 | 8 | 79 | 10 | 79 | 8 | 345 | 395 | 567 | 48 | 244 | 90 | AK032 |
Air diffuser [kg]
DN | LBK | LBS | |
---|---|---|---|
125 | 3.2 | 4.7 | 5.8 |
160 | 3.2 | 4.7 | 5.8 |
200 | 3.3 | 4.8 | 6.3 |
250 | 3.5 | 4.9 | 6.6 |
315 | 3.8 | 5.3 | 7.2 |
Plenum box [kg]
DN | AK | Weight |
---|---|---|
125 | AK028 | 2.5 |
160 | AK029 | 3 |
200 | AK030 | 3.5 |
250 | AK031 | 7.5 |
315 | AK032 | 10 |
Note: Total weight for variants with plenum box: air diffuser + plenum box
Dimension Q₁
NS | Q1 | ||
---|---|---|---|
LBK | LBS | ||
300 | 290 | - | - |
400 | 390 | - | - |
600 | 590 | 593 | 598 |
625 | 615 | 618 | 623 |
TID with vertical connection
DN | LBK | LBK | LBK | LBS | ||||||
---|---|---|---|---|---|---|---|---|---|---|
DN | ØD | H | H5 | ØD | H | H5 | ØD | ØD1 | H | H5 |
125 | 123 | 66 | 8 | 123 | 66 | 10 | 98 | 123 | 66 | 10 |
160 | 158 | 69 | 8 | 158 | 69 | 10 | 123 | 158 | 69 | 10 |
200 | 198 | 75 | 8 | 198 | 75 | 10 | 158 | 198 | 75 | 10 |
250 | 248 | 76 | 8 | 248 | 76 | 10 | 198 | 248 | 76 | 10 |
315 | 313 | 78 | 8 | 313 | 78 | 10 | 248 | 313 | 78 | 10 |
Air diffuser [kg]
DN | LBK | LBS | |
125 | 3.2 | 4.7 | 5.8 |
160 | 3.2 | 4.7 | 5.8 |
200 | 3.3 | 4.8 | 6.3 |
250 | 3.5 | 4.9 | 6.6 |
315 | 3.8 | 5.3 | 7.2 |
Note: In the case of the LBK variant, the optional flow adjustment damper can only be adjusted before installation. It is not possible to adjust the damper from the outside after installation.
These are only schematic diagrams to illustrate installation details.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be