VAV terminal unit, variant TVZ

  • VAV terminal unit for variable supply air volume flow control

Easyregler-Compactregler_img_01_2020_01_DE__5_psd.psd.link
Easy controller, Compact controller

Easy controller, Compact controller

TU-ELAB-Regler_img_01_2020_01_DE__8_psd.psd.link

TROX UNIVERSAL controller,

TROX LABCONTROL controller

TVZ_img_06psd.png
Circular connection on the fan end

Circular connection on the fan end

 

 

TVZ_img_07psd.png
Rectangular connection on the room end

Rectangular connection on the room end

 

00073144_0ai.ai.link
Tested to VDI 6022

Tested to VDI 6022

TVZ_img_01psd.png
Easyregler-Compactregler_img_01_2020_01_DE__5_psd.psd.link
TU-ELAB-Regler_img_01_2020_01_DE__8_psd.psd.link
TVZ_img_06psd.png
TVZ_img_07psd.png
00073144_0ai.ai.link

TVZ   

For supply air systems with demanding acoustic requirements


VAV terminal units for the supply air control in buildings with variable air volume systems and demanding acoustic requirements

  • Highly effective integral attenuator
  • Box style construction for the reduction of the airflow velocity
  • Electronic control components for different applications (Easy, Compact, Universal, and LABCONTROL)
  • Closed blade air leakage to EN 1751, up to class 4
  • Casing air leakage to EN 1751, up to class C

 

Optional equipment and accessories

  • Acoustic cladding for the reduction of case-radiated noise
  • Secondary silencer Type TS for the reduction of air-regenerated noise
  • Hot water heat exchanger of Type WT for reheating the airflow

 

 

 


General information

Application

  • Rectangular VAV terminal units for use in ventilation and air conditioning systems
  • For controlling, restricting or shutting off the supply air flow in systems with high acoustic requirements
  • Integral attenuator
  • Closed-loop volume flow control using an external power supply
  • For variable or constant volume flow systems
  • Shut-off by means of switching (by others)
  • Can also be used for duct or room pressure control with suitable control components



Special features

  • Integral attenuator with at least 26 dB insertion loss at 250 Hz
  • Hygiene tested and certified
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component; additional adjustment device may be necessary
  • Inspection access according to VDI 6022



Nominal sizes

  • 125, 160, 200, 250, 315, 400



Variants

  • TVZ: Supply air unit
  • TVZ-D: Supply air unit with acoustic cladding
  • Units with acoustic cladding and/or secondary silencer Type TS for very demanding acoustic requirements
  • Acoustic cladding cannot be retrofitted



Parts and characteristics

  • Ready-to-commission unit which consists of mechanical parts and control components.
  • Averaging effective pressure sensor for volume flow rate measurement
  • Damper blade
  • Integral attenuator
  • Inspection access
  • Factory assembled control components complete with wiring and tubing
  • Aerodynamic functional testing on a special test rig before shipping of each unit
  • Set-up data is given on a label or volume flow rate scale affixed to the unit
  • High control accuracy (even with upstream bend R = 1D)



Attachments

  • EASY controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Compact controller: Compact unit consisting of controller with potentiometers, effective pressure transducer and actuator
  • Universal controller: Controller, effective pressure transducer and actuators for special applications
  • LABCONTROL: Control components for air management systems



Accessories

  • Double lip seal (factory fitted)



Useful additions

  • Secondary silencer Type TS
  • Heat exchanger Type WT



Construction features

  • Rectangular casing
  • Spigot on the fan end suitable for circular ducts to EN 1506 or EN 13180
  • Spigot with groove for double lip seal
  • Connection on the room end suitable for ducts
  • Baffle plate, downstream of the damper blade, for achieving the best possible acoustic and aerodynamic performance
  • Position of the damper blade indicated externally at shaft extension
  • Thermal and acoustic insulation (lining)



Materials and surfaces

  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Lining is mineral wool
  • Effective pressure sensor made of aluminium
  • Plastic plain bearings
  • Shaft and linkage: Galvanised steel


Variant with acoustic cladding (-D)

  • Acoustic cladding made of galvanised sheet steel
  • Lining is mineral wool
  • Rubber elements for the insulation of structure-borne noise


Mineral wool

  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
  • Faced with glass fibre fabric as a protection against erosion from airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth



Standards and guidelines

Fulfils the hygiene requirements of

  • EN 16798, Part 3
  • VDI 6022, Sheet 1
  • DIN 1946, Part 4
  • Further standards, guidelines in accordance with hygiene certificate


Casing leakage:

Nominal sizes 125 – 200

  • EN 1751, Class C

Nominal sizes 250 – 400

  • EN 1751, Class B

Closed blade air leakage:

Nominal sizes 125 – 160

  • EN 1751, Class 3
  • Meets the general requirements of DIN 1946, Part 4, with regard to the acceptable closed damper blade air leakage

Nominal sizes 200 – 400

  • EN 1751, Class 4
  • Meets the increased requirements of DIN 1946, Part 4, with regard to the acceptable closed blade air leakage



Maintenance

  • Maintenance-free as construction and materials are not subject to wear


Technical information

Function, Technical data, Quick sizing, Specification text, Order code, Related Products

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE
  • RELATED PRODUCTS
Schematic illustration of the TVZ TVZ_gc_04ai.png

① Effective pressure sensor

② Double lip seal

③ Inspection access

④ Damper blade

⑤ Integral attenuator

⑥ Control components, e.g. an Easy controller


The VAV terminal unit is fitted with an effective pressure sensor for measuring the volume flow rate.

The control components (attachments) include an effective pressure transducer that transforms the effective pressure into an electric signal, a controller, and an actuator; the control functions can be achieved with an Easy controller or with a Compact controller or with individual components (Universal or LABCONTROL).

For most applications, the setpoint value comes from a room temperature controller.

The controller compares the actual value with the setpoint value and alters the control signal of the actuator if there is a difference between the two values.

An integral attenuator reduces the noise that is created by the restriction of the airflow.

The airflow velocity at the room end is, due to the larger rectangular cross section, about half the velocity in the circular duct.

 


Technical data TVZ


Quick sizing tables provide a good overview of the minimum differential pressures, the volume flow rate accuracy and the room sound pressure levels that can be expected. Intermediate values may be achieved by interpolation.

The sound power levels for calculating the sound pressure levels were measured in the TROX laboratory according to DIN EN ISO 5135 - see "Basic information and nomenclature".

Precise results and spectral data for all control components can be calculated with our Easy Product Finder design program. The first selection criteria for the nominal size are the actual volume flow rates qvmin and qvmax.

Volume flow rate ranges and minimum differential pressure values
The minimum differential pressure of VAV terminal units is an important factor in designing the ductwork and in rating the fan including speed control. It must be ensured that for all operating conditions and for all terminal units a sufficient pressure differential is applied to each controller (Δpstat,min). The measurement points for fan speed control must be selected accordingly. The volume flow rates given for VAV terminal units depend on the nominal size and on the control component (attachment) that is installed.

Volume flow rate ranges and minimum differential pressure values
Control component for dynamic pressure measurements – Easy (potentiometers)


Attachment: Easy


NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12514501220
1255620113189
1259835339557
125140504791115
16024831219
1609433912189
16016559535536
160236851721095
200371331219
20015054011229
20026394834656
2003761355701335
250582081219
25023684812249
250413148837726
2505912128741465
315963441219
315390140512209
315685246736596
3159803528731215
4001575631119
400638229812179
4001120403336516
40016025768731045

① Basic unit
② Basic unit with secondary silencer TS

 

Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle – qv Extended


Attachments: BC0, BL0 **, BM0, BM0-J6


NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12514501220
1256824419268
12512143759846
1251756311231745
16024831219
16011441117268
16020573854826
16029610661131705
200371331219
20018265517318
2003271176531006
20047116981092085
250582081219
250285102718348
2505131847561106
25074026661162295
315963441219
315473170317298
315851306255916
315122844211141905
4001575631119
400774278517258
4001391500655786
400200772281151625

① Basic unit
② Basic unit with secondary silencer TS

** Control component to be discontinued - do not include in new projects


Volume flow rate ranges and minimum differential pressure values
Control component dynamic measurement principle - qv As standard


Attachments: BUDN, BUDNF, LN0, LK0, LB0, XB0, XB4, (B13 *, B1B *)


NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12514501220
1255820714199
12510136542596
125145522841195
16024831219
1609734913199
16017161638576
160245882771175
200371331219
20015555712239
20027298037706
2003901404751435
250582081219
25024387413259
250428153939776
2506122205801575
315963441219
315402144813218
315709255338646
31510153657781305
4001575631119
400658236813188
4001159417339546
40016605978791115

① Basic unit
② Basic unit with secondary silencer TS

* Control component already discontinued


Volume flow rate ranges and minimum differential pressure values
Control component of static measurement principle


Attachments: BUSN, BUSNF, BUSS, XD0, XD4, TUN, TUNF, TUS, TUSD, ELAB (BP3 *, BPG *, BPB *, BB3 *, BBB *)


NSqv [l/s]qv [m³/h]Δpstmin [Pa]Δqv [±%]
12521732316
1256222316228
12510337243616
125145522841195
160351232316
16010437614228
16017562940606
160245882771175
200551952316
20016659814268
200278100138736
2003901404751435
250853062416
25026193915298
250437157241806
2506122205801575
3151425082315
315433155815248
315724260740666
31510153657781305
4002318302315
400707254615218
4001184426240576
40016605978791115

① Basic unit
② Basic unit with secondary silencer TS

* Control component already discontinued


Quick sizing table for sound pressure level


The quick sizing tables are based on generally accepted attenuation and insulation levels. If the sound pressure level exceeds the required level, a larger air terminal unit and/or a silencer or acoustic cladding is required. For more information on the acoustic data, see basic information and nomenclature.



Quick sizing table for air-regenerated noise LPA
Controller including silencer
(total flow rate range of type)


NSqv [l/s]qv [m³/h]150 Pa500 Pa
1251450< 15< 1517< 15
1256824427163120
12512143731213525
12517563134n.V.3728
160248316< 1520< 15
16011441131213424
16020573835253828
160296106637n.V.4030
20037133< 15< 1518< 15
20018265523< 152816
200327117626183120
200471169828n.V.3225
25058208< 15< 15< 15< 15
250285102720< 152716
250513184726183220
250740266630n.V.3526
31596344< 15< 1522< 15
315473170323< 153017
315851306227203322
3151228442130n.V.3626
400157563< 15< 1522< 15
400774278523< 153118
4001391500627223424
4002007722831n.V.3729

Air-regenerated noise LPA [dB(A)] at static differential pressure Δpst of 150 or 500 Pa

① Basic unit

② Basic unit with secondary silencer TS

n.a.: The specified static differential pressure Δpst is lower than the minimum differential pressure Δpst min.



Quick sizing table for case-radiated noise LPA
Controller including acoustic cladding
(total flow rate range of type)


NSqv [l/s]qv [m³/h]150 Pa500 Pa
125145017< 1524< 15
1256824425153221
12512143729203525
12517563132233728
160248315< 1523< 15
16011441125173324
16020573830233728
160296106634274032
2003713318< 152715
20018265528203626
200327117633253930
200471169836294233
2505820818< 152818
250285102727203728
250513184732254032
250740266636294335
3159634419< 153019
315473170329203930
315851306234264334
3151228442139314638
40015756323< 153424
400774278531234133
4001391500636284537
4002007722840334740

Case-radiated noise LPA [dB(A)] at static differential pressure Δpst of 150 or 500 Pa

① Basic unit

② Basic unit with acoustic cladding

n.a.: The specified static differential pressure Δpst is lower than the minimum differential pressure Δpst min.

 

Note:

Information on case-radiated noise for combinations of basic unit and optional acoustic cladding and secondary silencer can be found in the Easy Product Finder design program.


Rectangular VAV terminal units for variable and constant air volume systems, suitable for supply air, available in 6 nominal sizes. High control accuracy (even with upstream bend R = 1D). Ready-to-commission unit which consists of the mechanical parts and the electronic control components. Each unit contains an averaging effective pressure sensor for volume flow rate measurement, a damper blade, and an integral sound attenuator. Factory-assembled control components complete with wiring and tubing. Effective pressure sensor with 3 mm measuring holes, hence resistant to contamination. Baffle plate is fitted after the damper blade for optimum acoustic and aerodynamic performance. Casing with acoustic and thermal insulation. Position of the damper blade indicated externally at shaft extension. The damper blade is factory set to open position, which allows a ventilation airflow even without control; this does not apply to variants with defined safe position NC (normally closed). Meets the hygiene requirements of EN 16798, Part 3, of VDI 6022, Sheet 1, and of DIN 1946, Part 4.


Special features


  • Integral attenuator with at least 26 dB insertion loss at 250 Hz
  • Hygiene tested and certified
  • Factory set-up or programming and aerodynamic function testing
  • Parameters can also later be set on the control component; additional adjustment device may be necessary
  • Inspection access according to VDI 6022


Materials and surfaces



  • Casing and damper blade made of galvanised sheet steel
  • Damper blade seal made of TPE plastic
  • Lining is mineral wool
  • Effective pressure sensor made of aluminium
  • Plastic plain bearings
  • Shaft and linkage: Galvanised steel


Mineral wool:

  • To EN 13501, fire rating Class A1, non-combustible
  • RAL quality mark RAL-GZ 388
  • Non-hazardous to health thanks to being highly biosoluble in accordance with the Ordinance on Hazardous Substances and Note Q of the European Directive (EC) No. 1272/2008
  • Faced with glass fibre fabric as protection against erosion from airflow velocities of up to 20 m/s
  • Inert to fungal and bacterial growth



Connection



  • Spigot with groove for double lip seal on the fan end, suitable for connecting ducts according to EN 1506 or EN 13180. Room end suitable for the connection of ducts.



Equivalence criteria



  • Declaration of hygiene conformity in accordance with VDI 6022, Sheet 1 (01/2018), ÖNORM H 6020 (02/2007) and ÖNORM H 6021 (09/2003)
  • Setting of the volume flow rates without an adjustment device using Vmin-  and Vmax- potentiometer
  • Electrical connections with screw terminals, no additional terminal boxes required
  • Aerodynamic functional testing of each volume flow controller on test rigs at the factory, before a label is affixed to the controller
  • Acoustic data measured to ÖNORM EN ISO 5135:1999



Technical data



  • Nominal sizes: 125 to 400 mm
  • Volume flow rate range:  14 – 1602 l/s or 50 – 5768 m³/h
  • Minimum differential pressure: up to 123 Pa (without secondary silencer)
  • Maximum differential pressure: 1000 Pa
  • Closed blade air leakage to EN 1751, class 4 (nominal sizes 125 and 160, class 3).
  • Casing air leakage to EN 1751, class 4 (nominal size 250, 315, 400, class B)



Specification text for attachment



Variable volume flow control with electronic Easy controller to connect an external control signal; actual value signal can be integrated into the central BMS.

  • Supply voltage 24 V AC/DC
  • Signal voltages 0 – 10 V DC
  • Possible override controls with external switches using volt-free contacts: CLOSED, OPEN, qᵥmin and qᵥmax
  • Potentiometers with percentage scales to set the volume flow rates qᵥmin and qᵥmax without an adjustment device
  • The actual value signal relates to the nominal volume flow rate such that commissioning and subsequent adjustment are simplified
  • Volume flow rate control range: approx. 10 – 100 % of the nominal volume flow rate
  • Clearly visible external indicator light for signalling the functions: Set, not set, and power failure
  • Electrical connections with screw terminals
  • Double terminals for looping the supply voltage, i.e. for the simple connection of voltage transmission to the next controller



Sizing data



  • qᵥ _______________________ [m³/h]
  • Δpst _______________________ [Pa]

Air-regenerated noise

  • LPA _______________________

    [dB(A)]

Case-radiated noise

  • LPA _______________________

    [dB(A)]







Order code for volume flow control (with Easy attachment)
TVZD / 160 / D1 / Easy
|||||
12345

1 Type

TVZ 
VAV terminal unit, supply air 

2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]1
25
160200250315400 

4 Accessories
No entry required: None
D1 Double lip seal 

5 Attachments (control components)
Easy Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax with potentiometers


Order example: TVZ-D/200/Easy
Acoustic claddingWith
Nominal size200 mm
Attachments (control components)Easy volume flow controller, dynamic, analogue interface,
setting of qvmin  and qvmax  with potentiometers
 
,
Order code for volume flow control (with VARYCONTROL attachment)
TVZD / 160 / D1 / XB4 / V0 / 200 – 900 [m³/h] / NO
|||||||||
1234578910

1 Type
TVZ 
VAV terminal unit, supply air
 


2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]
125160200250315400 

4 Accessories
No entry required: None
D1 Double lip seal 

5 Attachments
(control components)

For example
BC0 Compact controller
XB4 Universal controller (VARYCONTROL) 

7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range) 

8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC 

9 Operating values for factory setting
Volume flow rate [m³/h or l/s] 
qᵥconst (in operating mode F)
qᵥmin – qᵥmax (in operating mode V) 

10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE

 Order example: TVZ-D/160/D1/BC0/V0/180–850 m³/h
Acoustic claddingwith
Nominal size160 mm
AccessoriesDouble lip seal
Attachments (control component)Compact controller, dynamic, analogue interface
Operating modeVariable
Signal voltage range0 – 10 V DC
Operating valuesqᵥmin = 180 m³/hqᵥmax = 850 m³/h
,
Order code for volume flow control (with TROX UNIVERSAL attachment)
TVZD / 160 / D1 / TUNF / RS /M /0 / UMZ / / NC
|||||||||||
1234567891011

1 Type
TVZ 
VAV terminal unit, supply air
 


2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]
125160200250315400 

4 Accessories
No entry required: None
D1 Double lip seal 

5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD)

6 Equipment function Room control
RS Supply air control (Room Supply) 

7 Volume flow rate setting
M Master (RMF function)
S Slave
F Constant flow rate controller 

8 Signal voltage range
0 0 – 10 V DC
2 2 – 10 V DC 

9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS) 
Option 2: Digital communication interface
No entry required: None
B
EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock 
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO with solenoid valve 

10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Master (RMF function)
qᵥmin: Minimum volume flow rate
qᵥmax: Maximum volume flow rate
qᵥconst_CLOSED: Constant supply air
qᵥconst_Exhaust: Constant extract air
qᵥDiff: Supply air/extract air difference Constant value
qᵥconst: Constant volume flow rate Slave
No entry required 

11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE 
Useful additions Room control panel
BE-LCD 40-character display


Order example: TVZ 200/TUS/RS/M/0/UMZ/600/1250/0/0/-100
Nominal size200 mm
Attachments (control components)TROX UNIVERSAL controller, fast-running actuator (3 s)
Equipment functionSupply air control
Volume flow rate settingMaster (RMF function)
Signal voltage range0 – 10 V DC
Expansion moduleswith expansion module EM-TRF-USV
Transformer for 230 V AC supply with UPS functionwith expansion module EM-BAC-MOD
Modbus RTU interfacewith expansion module EM-AUTOZERO
Solenoid valve for automatic zero point correction
Operating valuesqᵥmin = 600 m³/h, qᵥmax = 1250 m³/h
qᵥconst_CLOSED = 0 m³/h, qᵥconst_Exhaust = 0 m³/h
qᵥDiff = -100 m³/h
 
,
Order code for differential pressure control (with VARYCONTROL attachment)
TVZD / 160 / D1 / XF4 / PRS / F0 / 30 – 60 [Pa] / NO
||||||||||
12345678910

1 Type
TVZ 
VAV terminal unit, supply air
 
2 Acoustic cladding
No entry required: None
D With acoustic cladding 


3 Nominal size [mm]
125160200250315400 

4 AccessoriesNo entry required: None
D1 Double lip seal 

5 Attachments (control components)
For example
XF0 Compact controller for duct pressure
XF4 Universal controller for duct pressure (VARYCONTROL) 

6 Equipment function/installation location
PDS Duct pressure control, supply air
PRS Room pressure control, supply air 

7 Operating mode
F Constant value (a setpoint value)
V Variable (setpoint value range) 

8 Signal voltage range
For the actual and setpoint value signals
0 0 – 10 V DC
2 2 – 10 V DC 

9 Operating values for factory setting
Differential pressure [Pa]
For duct pressure control, enter the differential pressure [Pa] as an absolute value 
Δpconst (in operating mode F)
Δpmin – Δpmax (in operating mode V) 

10 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE


Order example: TVZ/160/D1/XF4/PDS/F/2/470 Pa/NO
Nominal size160 mm
AccessoriesDouble lip seal (one end)
Attachments (control components)VARYCONTROL Universal controller for duct pressure
Equipment functionDuct pressure control, supply air
Operating modeConstant value
Signal voltage range2 – 10 V DC
Operating value470 Pa
Damper blade positionPower off to OPEN
 
,
Order code for differential pressure control (with TROX UNIVERSAL attachment)
TVZD / 160 / D1 / TUNF / PRS /MFP /0 / UMZ / / NC
|||||||||||
1234567891011

1 Type
TVZ 
VAV terminal unit, supply air
 


2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]
125160200250315400 

4 Accessories
No entry required: None
D1 Double lip seal 

5 Attachments (control components)
TROX UNIVERSAL controller with
TUN Actuator (150 s)
TUNF Spring return actuator (150 s)
TUS Fast-running actuator (3 s)
TUSD Fast-running actuator (3 s), with digital communication interface (TROX HPD) 

6 Equipment functionY
Pressure control
PRS Room pressure control, supply air
PDS Duct pressure control, supply air 

7 Differential pressure setting
MFP Master, constant pressure control
MVP Master, variable differential pressure control
SFP Slave, constant pressure control
SVP Slave, variable differential pressure control 

8 Signal voltage range
0 0 - 10 V DC
2 2 - 10 V DC 

9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS) 
Option 2: Digital communication interface
No entry required: None
B
EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock 
Option 3: Volume flow rate measurement
No entry required: None
V  EM-V Volume flow rate measurement for differential pressure control 
Option 4: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO solenoid valve (only with V) 

10 Operating values for factory setting
Pressure [Pa], volume flow rate [m³/h or l/s]
Slave SVP
Δpmin: minimum differential pressure
Δpmax: maximum differential pressure Slave SFP
Δpconst: Constant differential pressure Master MFP and MVP like Slave, but additionally
qᵥmin: minimum volume flow rate
qᵥmax: maximum volume flow rate
qᵥconst_CLOSED: constant supply air
qᵥconst_Exhaust: constant extract air
qᵥDiff: Supply air/extract air difference 

11 Damper blade position
Only spring return actuators
NO Power off to OPEN
NC Power off to CLOSE 
Useful additions Room control panel
BE-LCD 40-character display 
The differential pressure transducer required for room or duct pressure control has to be ordered separately, e.g.
PT-699 for room pressure control
PT-699-DUCT for duct pressure control, including tube and pressure tap 


Order example: TVZ/200/TUS/PRS/MVP/0/B/-10/-60/ 600/1250/ 0/ 0/-100

Nominal size200 mm
Attachments (control components)TROX UNIVERSAL controller, fast-running actuator (3 s)
Equipment functionRoom pressure control, supply air
Differential pressure settingMaster, variable differential pressure control
Signal voltage range0 – 10 V DC
Expansion moduleswith expansion module EM-BAC-MODBACnet MS/TP interface card
Operating valuesΔpmin = -10 Pa, Δpmax = -60 Paqᵥmin = 600 m³/h,qᵥmax = 1250 m³/hqᵥconst_Supply air = 0 m³/h, qᵥconst_Extract air = 0 m³/hqᵥDiff = - 100 m³/h
 
,
Order code for room control (with EASYLAB attachment)
TVZD/160/D1/ELAB/S/RS/UMZ/LAB/
| | | | | | | | | |
1 2 3 4 5 6 7 9 10 11

1 Type
TVZ
VAV terminal unit, supply air
 
2 Acoustic cladding
No entry required: None
D With acoustic cladding 


3 Nominal size [mm]
125160200250315400 

4 Accessories
No entry required: None
D1 Double lip seal

 5 Attachments (control components)
ELAB EASYLAB controller TCU3 

6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD) 

7 Equipment function Room control
RS Supply air control (Room Supply)
PC Differential pressure control (Pressure Control) 

9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS) 
Option 2: Digital communication interface
No entry required: None

B
EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock 
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO
Solenoid valve for automatic zero point correction
 

10 Additional functions
Without room management function
LAB Extract air led system (laboratories)
CLR Supply air led system (clean rooms) 
With room management function
LAB-RMF Extract air led system
CLR-RMF Supply air led system 

11 Operating values for factory setting
(only required when room management function is active) 
Volume flow rate [m³/h or l/s], pressure [Pa] 
Total extract air/supply air of room:
qv1: Standard mode
qv2: reduced operation
qv3: increased operation
qv4: constant supply air
qv5: constant extract air
qv6: Supply air/extract air difference
ΔpSet: Setpoint pressure (only with differential pressure control) 
Useful additions
Room control panel (only for devices with RMF)
BE-LCD 40-character display 
The differential pressure transducer required for room pressure control (equipment function) has to be ordered separately, e.g.
PT-699 Measuring range ±50 Pa or ±100 Pa
PT-GB604 Measuring range ±100 Pa


Order example: TVZ/200/ELAB/SD/RS/CLR-RMF/3500/1000/5000/250/0/-150
Acoustic claddingwithout
Nominal size200 mm
Attachments (control components)EASYLAB controller TCU3 with fast-running actuator (3 s)
ActuatorFast-running actuator (3 s), with digital communication interface
Equipment functionSupply air control (Room Supply)
Additional functionSupply air led system with room management function
Operating valuesqv1 = 3500 m³/hqv2 = 1000 m³/hqv3 = 5000 m³/hqv4 = 250 m³/hqv5 = 0qv6 = -150 m³/h


Order code for single operation (with EASYLAB attachment)
TVZD/160/D1/ELAB/S/SCE0/UMZ/
| | | | | | | | | |
1 2 3 4 5 6 7 8 9 11

1 Type
TVZ
VAV terminal unit, supply air
 


2 Acoustic cladding
No entry required: None
D With acoustic cladding 

3 Nominal size [mm]
125160200250315400 

4 Accessories
No entry required: None
D1 Double lip seal 

5 Attachments (control components)
ELAB EASYLAB controller TCU3 

6 Actuators
S Fast-running actuator (3 s)
SD Fast-running actuator (3 s), with digital communication interface (TROX HPD) 

7 Equipment function
Single operation
SC Supply air controller

 8 External volume flow rate setting
E0 Voltage signal 0 – 10 V DC
E2 Voltage signal 2 – 10 V DC
2P Switch contacts (provided by others) for 2 switching steps
3P Switch contacts (provided by others) for 3 switching steps
F Volume flow rate constant value, without signalling 

9 Expansion modules
Option 1: Power supply
No entry required: 24 V AC/DC
T EM-TRF for 230 V AC
U EM-TRF-USV for 230 V AC, provides uninterruptible power supply (UPS) 
Option 2: Digital communication interface
No entry required: None
B
EM-BAC-MOD-01 for BACnet MS/TP
M EM-BAC-MOD-01 for Modbus RTU
I EM-IP for BACnet/IP, Modbus/IP and web server
R EM-IP with real time clock 
Option 3: Automatic zero point correction
No entry required: None
Z EM-AUTOZERO Solenoid valve for automatic zero point correction 

11 Operating values for factory setting
Volume flow rate [m³/h or l/s]
Depending on external volume flow rate setting
E0, E2: qᵥmin/qᵥmax
2P: qᵥ1/qᵥ2
3P: qᵥ1/qᵥ2 /qᵥ3
F: qᵥ1


Order example: TVZ/315/ELAB/S/SC/F/2800 m³/h
Nominal size315 mm
Attachments (control components)EASYLAB controller TCU3
ActuatorFast-running actuator (3 s)
Equipment functionSupply air controller
External volume flow rate settingVolume flow rate constant value
Operating valueqᵥ1 = 2800 m³/h
 

Variants, Dimensions and weight, Product details, Control Components

  • VARIANTS
  • DIMENSIONS AND WEIGHT
  • PRODUKT DETAILS
  • CONTROL COMPONENTS


NG
BHL∅DAB₁B₃H₁H₃Wkg
125198152118512415023230018623611521
160308152123515920034241018623611525
200458210152019920049256024428111533
250598201169024925063270023531121555
315798252169031425083290028636121573
40089835420703992509321000388446215118


Dimensions/weights of TVZ-D
NGBHL∅DAB₁B₃H₁H₃Wkg
125198152118512411023238018631615541
160308152123515916034249018631615550
200458210152019916049264024436115563
250598201169024921063278023539125595
3157982521690314210832980286441255133
40089835420703992109321080388526255193

Installation and commissioning

  • Any installation orientation (except units with static effective pressure transducer)
  • Return edges of the casing with drilled holes suitable for M10 threaded rods
  • TVZ-D: For constructions with acoustic cladding, ducts on the room side should have cladding up to the acoustic cladding of the controller


Upstream conditions

The volume flow rate accuracy Δqᵥ applies to straight upstream section of the duct. Bends, junctions or a narrowing or widening of the duct cause turbulence that may affect measurement. Duct connections, e.g. branches off the main duct, must comply with EN 1505. Some installation situations require straight duct sections upstream.


VARYCONTROL control components


AttachmentControlled variableInterfacePressure transducerActuatorManufacturer
Easy controller, dynamic
Easy

qv

0 – 10 Vintegralslow-running

integral
Compact controller, dynamic
BC0

qv

0 – 10 V or 2 – 10 V or MP bus interfaceintegralslow-running

integral

BL0 **

qv

LonWorks FTT 10 interface

integralslow-running

integral
BM0

qv



Modbus RTU/BACnet MS/TP


integralslow-running

integral
BM0-J6

qv



Modbus RTU/BACnet MS/TP with RJ12 socket (for X-AIRCONTROL)


integralslow-running

integral
LK0

qv



KNX interface


integralslow-running

integral
LN0

qv

0 – 10 V or 2 – 10 Vintegralslow-running

integral
XB0

qv

0 – 10 V or 2 – 10 Vintegralslow-running

integral
Compact controller, static
XD0

qv

0 – 10 V or 2 – 10 Vintegralslow-running

integral
XF0Δp0 – 10 V or 2 – 10 Vintegral, control range adjustable 25 - 550 Paslow-running

integral
Universal controller, dynamic

B13 *

qv

0 – 10 V or 2 – 10 Vintegralslow-running

separate

B1B *

qv

0 – 10 V or 2 – 10 Vintegralspring return actuator

separate
BUDN

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegralslow-running

separate
BUDNF

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegralspring return actuator

separate
XB4

qv

0 – 10 V or 2 – 10 Vintegralspring return actuator

separate
VARYCONTROL Universal controller, static

BB3 *

qv

2 – 10 Vindividual componentslow-running

separate

BBB *

qv

2 – 10 Vindividual componentspring return actuator

separate

BG3 *

Δp2 – 10 Vindividual component

100 Pa
slow-running

separate

BGB *

Δp2 – 10 Vindividual component

100 Pa
spring return actuator

separate

BH3 *

Δp2 – 10 Vindividual component

600 Pa
slow-running

separate

BHB *

Δp2 – 10 Vindividual component

600 Pa
spring return actuator

separate

BP3 *

qv

0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentslow-running

separate

BPB *

qv

0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentspring return actuator

separate

BPG *

qv

0 – 10 V or 2 – 10 V or MP bus interfaceindividual componentfast-running

separate

BR3 *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

100 Pa
slow-running

separate

BRB *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

100 Pa
spring return actuator

separate

BRG *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

100 Pa
fast-running

separate

BS3 *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

600 Pa
slow-running

separate

BSB *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

600 Pa
spring return actuator

separate

BSG *

Δp0 – 10 V or 2 – 10 V or MP bus interfaceindividual component

600 Pa
fast-running

separate
BUPNΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegral

Control range adjustable 25 – 450 Pa
slow-running

separate
BUPNFΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegral

Control range adjustable 25 – 450 Pa
spring return actuator

separate
BURNΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegral

Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa
slow-running

separate
BURNFΔp0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegral

Control range adjustable -50 ... -10 Pa or 10 ... 50 Pa
spring return actuator

separate
BUSN

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegralslow-running

separate
BUSNF

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegralspring return actuator

separate
BUSS

qv

0 - 10 V or 2 - 10 V or MP bus or Modbus RTU or BACnet MS/TPintegralfast-running

separate
XD4

qv

0 – 10 V or 2 – 10 Vintegralspring return actuator

separate
XF4Δp0 – 10 V or 2 – 10 Vintegral, control range adjustable 25 - 550 Paspring return actuator

separate

* Control component has been discontinued

** Control component to be discontinued - do not include in new projects

qv Volume flow rate
Δp Differential pressure
① TROX, ② TROX/Belimo, ③ TROX/Gruner, ⑤ Siemens


TROX UNIVERSAL control components


AttachmentControlled variableInterfacePressure transducerActuatorManufacturer
VARYCONTROL Universal controller, static
TUNqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

qv = integral

Δp = separate
slow-running

separate
TUNFqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

qv = integral

Δp = separate
spring return actuator

separate
TUSqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

qv = integral

Δp = separate
fast-running

separate
TUSDqv, Δp

TROX Plug&Play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

qv = integral

Δp = separate

fast-running with digital communication interface (TROX HPD), separate


qv Volume flow rate
Δp Differential pressure
① TROX



LABCONTROL EASYLAB control components


AttachmentControlled variableInterfacePressure transducerActuatorManufacturer
EASYLAB
ELAB

qv, Δp *

TROX plug and play communication system and 0 - 10 V or 2 - 10 V or with optional accessories: Modbus, BACnet, web server

qv = integral

Δp = separate

fast-running, separate



or



fast-running with digital communication interface (TROX HPD), separate


① TROX

 

* The controlled variable depends on the type of VAV terminal unit

  • TVR, TVRK: Fume cupboard, room supply air, room extract air, room pressure, single controller
  • TVLK: Fume cupboard, single controller
  • TVJ, TVT: Room supply air, room extract air, room pressure, single controller
  • TVZ, TZ-Silenzio: Room supply air, room pressure, single controller
  • TVA, TA-Silenzio: Room extract air, room pressure, single controller

Flange detail, Dimensions and weight

  • FLANGE DETAIL
  • DIMENSIONS AND WEIGHT
Flange detail 00078794_0ai.ai.link

1 Compressible seal, to be provided by others
2 Flanges on both ends indented by approx. 12 mm
3 Flange
4 Duct
5 VAV terminal unit


 Space required for commissioning and maintenance

Sufficient space must be kept clear near any attachments to allow for commissioning and maintenance. It may be necessary to provide sufficiently sized inspection access openings.


Space required


Attachment

VARYCONTROL












Easy controller: Easy


400300300


Compact controller: BC0, BL0 *, BM0, BM0-J6, LN0, LK0, XB0, XD0, XF0


400300300


Universal controller: B13 *, B1B *, BB3 *, BBB *, BG3 *, BGB *, BH3 *, BHB *, BP3 *, BPB *, BPG *, BR3 *, BRB *, BRG *, BS3 *, BSB *, BSG *, BUDN, BUDNF, BUSN, BUSNF, BUSS, BUPN, BUPNF, BURN, BURNF, XB4, XD4, XF4


700300300

TROX UNIVERSAL












TROX UNIVERSAL: TUN, TUS, TUSD


900350400

LABCONTROL












EASYLAB: ELAB


900350400

* Control component has been discontinued

** Control component to be discontinued - do not include in new projects


Space required for inspection access

Attachment
Inspection access

400




300




300



 

 


Downloads

product information

brochures

certificates

operation manuals

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be