Application
Special characteristics
Variants
Heat exchanger
Arrangement of water connections
Left and right as viewed from the inside towards the outside. Right-hand version: Water connections and exhaust air opening on the right. Left-hand version: Water connections and exhaust air opening on the left.
Parts and characteristics
Useful additions
Construction features
Materials and surfaces
Mineral wool
Standards and guidelines
Maintenance
Underfloor unit for decentralised ventilation for installation in the system floor (cavity or raised floor). The casing is made of painted sheet steel and provides noise and thermal insulation. The supply air opening in the floor can be covered with either a linear grille or a roll down grille. The outdoor air is drawn in by an EC centrifugal fan and flows through the motorised shut-off damper and the fine dust filter. The outdoor air then flows through the recuperative cross-flow heat recovery unit. There, part of the extract air heat is transferred to the outdoor air flow. The filtered and heated outdoor air is then directed into the rooms as supply air. If necessary, the air is heated or cooled by the heat exchanger before it is supplied into the room as a displacement flow. The extract air first passes through the extract air filter, then flows through the heat recovery unit, the extract air fan and the motorised shut-off damper before it is discharged to the outside as exhaust air. If the room air quality is sufficient, FSL-CONTROL III closes the outdoor air dampers and changes to secondary air operation mode, which is more energy efficient. The control system compares the room air quality setpoint value to the actual value measured by the CO2 sensor, and switches automatically between outdoor air and secondary air operation. In case of a power failure, the outdoor air and exhaust air dampers are closed to ensure fire protection, frost protection and to avoid draughts. This is ensured by a capacitor in each actuator. The supply air flows into the room close to the façade, at medium velocity. Due to the induction effect, the supply air velocity is rapidly reduced after entering the room. As a result, in cooling mode, the supply air spreads out like a displacement flow over the entire floor area. Near heat sources such as people or equipment, a lift current is formed by natural convection, so that the air is exchanged primarily in these areas.
Width | 1150 mm |
Height | 150 mm below the system floor (cavity or raised floor), upper edge of ventilation grille project-specific, at least 196 mm |
Depth | 860 mm |
Depth ventilation grilles | 340 mm |
Outdoor air flow rate | 0 – 120 m³/h |
Supply air flow rate | 60 – 200 m³/h |
Nominal volume flow rate | 120 m³/h |
Sound power level | 28 – 47 dB(A) |
Degree of heat recovery efficiency | 60 % |
Maximum operating pressure, water side | 6 bar |
Maximum operating temperature | 75 °C |
Supply voltage | 230 V AC ±10 %, 50/60 Hz |
Power rating | 326 VA |
Weight | 75 kg |
X-CUBE/ROOMAIR-U-ZAS: 4-Leiter-Ausführung
Zuluftvolumenstrom | m³/h | 60 | 90 | 120 |
Gesamtkühlleistung | W | 200 | 310 | 410 |
Raumkühlleistung | W | 160 | 240 | 313 |
Temperatur der Luft im Gerät | °C | 28 | 28,4 | 28,6 |
relative Feuchte | % | 50 | 49 | 48,6 |
Wassergehalt der trockenen Luft | g/kg | 11,9 | 11,9 | 11,9 |
Zulufttemperatur | °C | 18 | 18 | 18,2 |
Kondensat | g/h | |||
Kaltwassermenge | l/h | 70 | 150 | 250 |
Wassereintrittstemperatur | °C | 16 | 16 | 16 |
Wasseraustrittstemperatur | °C | 18,4 | 17,8 | 17,4 |
Druckverlust wasserseitig | kPa | 1,7 | 6,4 | 15,7 |
Gesamtheizleistung | W | 800 | 1240 | 1760 |
Raumheizleistung | W | 351 | 499 | 689 |
Temperatur der Luft im Gerät | °C | 10,1 | 8,4 | 7,4 |
Zulufttemperatur | °C | 38,5 | 37,6 | 38,2 |
Warmwassermenge | l/h | 40 | 70 | 150 |
Wassereintrittstemperatur | °C | 60 | 60 | 60 |
Wasseraustrittstemperatur | °C | 42,5 | 44,6 | 49,8 |
Druckverlust wasserseitig | kPa | 0,4 | 1 | 3,5 |
Schallleistungspegel Lw,a | dB(A) | 28 | 36 | 43 |
Schalldruckpegel inklusive 8 dB Systemdämpfung | dB(A) | 20 | 28 | 35 |
Wirkleistung Pel | W | 20 | 24 | 34 |
Luftseitige Daten Kühlbetrieb:
Luftseitige Daten Heizbetrieb:
Mindestmenge Außenluft = 60 m³/h
Kondensatfreier Betrieb durch SEC-Beimischung in Stufe 1 = 21 m³/h
Kondensatfreier Betrieb durch SEC-Beimischung in Stufe 2 = 31 m³/h
Kondensatfreier Betrieb durch SEC-Beimischung in Stufe 3 = 42 m³/h
X-CUBE/ROOMAIR-U-ZAS: 2-Leiter-Ausführung
Zuluftvolumenstrom | m³/h | 60 | 90 | 120 |
Außenluftvolumenstrom | m³/h | 60 | 90 | 120 |
Gesamtheizleistung | W | 860 | 860 | 1090 |
Raumheizleistung | W | 295 | 442 | 609 |
Temperatur der Luft im Gerät | °C | 8,3 | 8,3 | 9,2 |
Zulufttemperatur | °C | 34,7 | 34,7 | 35,2 |
Warmwassermenge | l/h | 70 | 70 | 120 |
Wassereintrittstemperatur | °C | 50 | 50 | 50 |
Wasseraustrittstemperatur | °C | 39,3 | 39,3 | 35,2 |
Druckverlust wasserseitig | kPa | 1,1 | 1,1 | 2,7 |
Schallleistungspegel Lw,a | dB(A) | 28 | 36 | 43 |
Schalldruckpegel inklusive 8 dB Systemdämpfung | dB(A) | 20 | 28 | 35 |
Wirkleistung Pel | W | 20 | 24 | 34 |
Luftseitige Daten Heizbetrieb:
Alle Angaben unter Berücksichtigung der WRG!
X-CUBE/ROOMAIR-U-ZAS-4-AR/1150x196x830/C3
Underfloor ventilation unit for installation in system floor (cavity or raised floor)
Special features:
Unit description:
Please note:
The described underfloor ventilation unit variant is equipped with individual room control. The supplied controllers contain the parameters of the standard control for operation according to our control description.
X-CUBE/ROOMAIR-U-ZAS - Master device
Decentralised underfloor ventilation unit TROX X-CUBE/ROOMAIR-U-ZAS with supply and extract air function, secondary air admixture, switchover option to secondary air mode, heat recovery as well as heating and cooling function for installation in system floor (cavity or raised floor):
Utilisation of secondary air to save energy (only in conjunction with air quality sensor): Automatic switchover to secondary air operation takes place when the room air quality (measured, for example, by the unit's internal CO2 sensor) is within the defined limits. For this purpose, the shut-off dampers are closed, the self-powered secondary air damper opens and the extract air fan is switched off
Sound power level in supply air, extract air and secondary air mode - example:
Outdoor air volume flow = exhaust air volume flow = 120 m³/h
Supply air volume flow 120/150 m³/h = 41/45 dB(A) (corresponds to a sound pressure level of = 33/37 dB(A) with a room attenuation of 8 dB)
The measurement data refer to sound power measurements of a single unit in a reverberation chamber according to accuracy class 1. Results may vary, depending on the installation situation
Rail mount terminals type Wago 260 for the on-site connection of
Digital inputs DI
Digital outputs DO
Master-slave connection RS485
RS485 (Modbus/BACnet)
Room control panel
RJ45 socket as service access to the user interface
Optional connection to MCE/BACS via Ethernet (Modbus/BACnet)
Installed components:
Dimensions and weight:
Construction
Technical data
RA-U-ZAS | – | 4 | – | AR | / | 1150 × 196 × 830 | / | C3 | / | MA | – | T | / | MR | / | C | / | Z | / | A | / | HV | – | R | – | 0.4 | / | KV | – | R | – | 0.4 |
| | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | ||||||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | ||||||||||||||||
RA-U-ZAS | decentralised underfloor ventilation unit X-CUBE/ROOMAIR-U-ZAS |
4 | with 4-pipe heat exchanger |
AR | Water connections on the right-hand side, room end |
C3 | with FSL-CONTROL III |
MA | in Master construction |
T | with real time clock |
C | with CO2 sensor |
Z | with supply air temperature sensor |
A | with outdoor air temperature sensor |
HV-R-0.40 | with straight-way valve (heating circuit) kvs 0.40 and lockshield |
KV-R-0.40 | with straight-way valve (cooling circuit) kvs 0.40 and lockshield |
Installation and commissioning
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be