Application
Special features
Nominal sizes
Variants
Parts and characteristics
Accessories
Construction features
Materials and surfaces
Mineral wool
Standards and guidelines
Maintenance
Nominal sizes | 125 – 400 mm |
Operating pressure | 1000 Pa |
Operating temperature | 100 °C max. |
The stated differential pressures for circular silencers correspond to the values for smooth pipes. Deviations, if any, are of no practical relevance.
For ductwork calculation, if the length of a circular silencer is included in the total length of the ductwork, no extra length must be added.
CAK, insertion loss
125 | 500 | 1 | 6 | 7 | 14 | 25 | 23 | 14 | 12 |
125 | 1000 | 2 | 9 | 13 | 22 | 34 | 35 | 24 | 16 |
125 | 1500 | 3 | 12 | 19 | 31 | 42 | 43 | 33 | 20 |
160 | 500 | 0 | 3 | 5 | 11 | 22 | 21 | 12 | 10 |
160 | 1000 | 1 | 4 | 9 | 18 | 30 | 31 | 19 | 13 |
160 | 1500 | 2 | 7 | 13 | 25 | 38 | 41 | 27 | 17 |
200 | 500 | 0 | 2 | 4 | 10 | 21 | 17 | 10 | 8 |
200 | 1000 | 1 | 4 | 9 | 15 | 29 | 25 | 16 | 11 |
200 | 1500 | 1 | 6 | 12 | 21 | 36 | 33 | 20 | 14 |
250 | 500 | 0 | 2 | 4 | 9 | 19 | 13 | 9 | 8 |
250 | 1000 | 0 | 4 | 8 | 14 | 26 | 22 | 15 | 11 |
250 | 1500 | 1 | 6 | 11 | 20 | 35 | 30 | 20 | 15 |
315 | 500 | 0 | 2 | 3 | 8 | 18 | 12 | 7 | 6 |
315 | 1000 | 0 | 4 | 6 | 14 | 26 | 17 | 11 | 8 |
315 | 1500 | 1 | 6 | 9 | 19 | 34 | 23 | 15 | 10 |
400 | 500 | 0 | 2 | 3 | 6 | 14 | 8 | 6 | 4 |
400 | 1000 | 0 | 3 | 6 | 11 | 25 | 13 | 10 | 7 |
400 | 1500 | 1 | 4 | 8 | 16 | 29 | 15 | 11 | 8 |
CAK, differential pressure
125 | 50 | 180 | 2 | 2 | 4 |
125 | 95 | 342 | 4 | 6 | 10 |
125 | 120 | 432 | 6 | 10 | 14 |
125 | 145 | 522 | 6 | 14 | 20 |
160 | 80 | 288 | 2 | 2 | 2 |
160 | 155 | 558 | 2 | 6 | 8 |
160 | 195 | 702 | 4 | 8 | 10 |
160 | 235 | 846 | 6 | 10 | 14 |
200 | 125 | 450 | 2 | 2 | 2 |
200 | 245 | 882 | 2 | 4 | 6 |
200 | 310 | 1116 | 4 | 6 | 8 |
200 | 370 | 1332 | 4 | 8 | 10 |
250 | 195 | 702 | <2 | <2 | <2 |
250 | 385 | 1386 | <2 | 4 | 4 |
250 | 485 | 1746 | 2 | 4 | 6 |
250 | 580 | 2088 | 4 | 6 | 8 |
315 | 310 | 1116 | <2 | <2 | <2 |
315 | 615 | 2214 | <2 | 2 | 4 |
315 | 770 | 2772 | <2 | 4 | 4 |
315 | 925 | 3330 | 2 | 4 | 6 |
400 | 500 | 1800 | <2 | <2 | <2 |
400 | 995 | 3582 | <2 | <2 | 2 |
400 | 1245 | 4482 | <2 | 2 | 4 |
400 | 1495 | 5382 | <2 | 4 | 4 |
Plastic circular silencers for use in extract air systems subject to aggressive media; they reduce the air-regenerated noise in plastic ducts (absorption principle).
Insertion loss measured according to ISO 7235.
Absorption material is mineral wool with RAL quality mark RAL-GZ 388.
Spigot, suitable for ducts according to DIN 8077.
Casing air leakage to EN 15727, class D.
Special features
Materials and surfaces
Mineral wool
Technical data
Sizing data
Order example: CAK/200×1000
Nominal size | 200 mm |
Length | 1000 mm |
Type of connection | Spigot |
CAK
Variant
CAK/.../VF2
Variant
CAK, dimensions
mm | mm | mm | mm | mm | ||
CAK, lengths
mm LN | mm | mm |
CAK, weights
500 kg |
1000 kg |
1500 kg | |
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
|
CAK/.../VF2, weights
500 kg |
1000 kg |
1500 kg | |
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
| |
|
|
|
Installation and commissioning
Principal dimensions
ØD [mm]
Outer diameter of the spigot
ØD₃ [mm]
Outer diameter of circular silencers
L [mm]
Length of attenuator/silencer including spigot (in airflow direction)
L₁ [mm]
Length of acoustic cladding and acoustically effective length
B [mm]
Attenuator width and duct width (upright splitters)
H [mm]
Attenuator height and duct height (upright splitters)
T [mm]
Splitter thickness
S [mm]
Airway width
n [ ]
Number of flange screw holes
m [kg]
Weight
Nomenclature
fm [Hz]
Octave band centre frequency
LWA [dB(A)]
A-weighted sound power level of air-regenerated noise
De [dB]
Insertion loss
V [m³/h] and [l/s]
Volume flow rate
Δpst [Pa]
Static differential pressure
All sound power levels are based on 1 pW.
All values were measured in a TROX lab and to EN ISO 7235. Intermediate values may be achieved by interpolation.
Lab measurements exceeding 50 dB are indicated as 50 dB, in line with common practice.
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be