DID-E2 

ACTIVE CHILLED BEAM WITH ONE-WAY AIR DISCHARGE AS A QUIET ALTERNATIVE TO FAN COIL UNITS, WITH 2 HORIZONTAL HEAT EXCHANGER VARIANTS FOR DIFFERENT OUTPUT RANGES

Active chilled beam for heating and cooling with 2- or 4-pipe heat exchanger for installation in ceiling bulkheads, e.g. in hotel rooms and hospital bed rooms in nominal lengths of 1000, 1125 and 1250 mm

  • Preferably for room heights up to 4.00 m
  • High heating and cooling capacity with a low conditioned primary air volume flow rate and low sound power level
  • Media supply on the reverse or from the corridor side
  • Compact appliance dimensions, orientated on the basic dimensions
  • 2 different widths or depths for the heat exchanger, to cover different output ranges
  • Fixing bracket for various suspension systems/points
  • Combination with different control systems, e.g. X-AIRCONTROL or air-water systems possible


Optional equipment and accessories

  • Integrated volume flow controller
  • Ventilation grille for supply air and secondary air from the TROX grille product range
  • Various water connections, smooth CU tube, external thread G1/2" and flat seal, or union nut G1/2" and flat seal
  • The supply air spigot is extendable (sliding) to compensate for structural tolerances
Updating order code
Save configuration
Calculate price
Updating technical data
  • Media
Specification text:
Updating specification text
Show complete text Hide complete text
Initialize order code

General information

Application

  • Active chilled beams for installation into ceiling bulkheads, preferably for room heights up to 4.00 m
  • Especially for hotel rooms and hospital wards
  • Demand-based supply of primary air or supply air
    • The additional thermal load is dissipated by water
  • 2-pipe or 4-pipe heat exchangers enable good comfort levels with a low conditioned primary air flow rate
  • Energy-efficient solution as water is used for heating and cooling


Special characteristics

  • One-way air discharge
  • Horizontal heat exchanger as 2-pipe or 4-pipe system
  • Connections on the rear of the device
    • Therefore with short cable runs
    • Connection possible in the corridor area
  • The supply air spigot is extendable (sliding) to compensate for structural tolerances
  • Nominal sizes are based on the basic dimensions
  • Integrated volume flow controller as an option


Nominal sizes

  • 1000, 1125, 1250 mm


Variants

Water connection

  • Position right (-R) or left (-L)
  • Smooth copper tube Ø12 mm
  • A1: external thread G½”, with flat seal
  • A2: union nut G½”, with flat seal

Heat exchanger

  • 2: 2-pipe systems
  • 4: 4-pipe systems

Nozzle variants

  • HE: small
  • S1: medium
  • S2: large
  • HP: extra large
  • H2: nozzle mix (50 % S2 nozzle and 50 % HP nozzle)

Other nozzle mixes available on request.

Attachments

  • VC: integrated flow rate control unit


Accessories

  • Z: sliding spigot for the supply air (mandatory when using a supply air grille with concealed screw fastening)
  • ERS: installation subframe for secondary air grille


Useful additions

  • Connecting hoses Type FS
  • Control (air-water systems), consisting of:
    • Control panel with integrated room temperature sensor and controller
    • Valves and valve actuators
    • Lockshields
  • Ventilation grille for supply air and secondary air from the TROX grille product range
  • Control system X-AIRCONTROL for water-side and airside control, with the option of a connection to the MCE
  • For further information on the X-AIRCONTROL and for information relevant to the design, please refer to the installation and operating manual.


Construction features

  • Spigot is suitable for circular ducts according to EN 1506 or EN 13180
  • 5 nozzle variants to optimise induction demand-based.
  • Side-mounted fixing brackets for suspension with various fixing systems
  • A mixture of nozzles is possible
  • Devices without flow rate control unit: primary air connection in the centre
  • Devices with flow rate control unit: primary air connection left or right


Materials and surfaces

  • Casing, nozzle plate, supply air spigot and installation subframe for secondary air grille made of galvanised sheet steel
  • Heat exchanger consisting of copper tubes and aluminium fins
  • Surface of the casing and heat exchanger optionally available in black (RAL 9005)


Standards and guidelines

  • Products are certified by Eurovent no. 09.12.432 and listed on the Eurovent website
  • Declaration of hygiene conformity according to VDI 6022
  • Sound power level of the air-regenerated noise measured according to DIN EN ISO 5135


Maintenance

  • Variants without flow rate control unit (VC) are lowmaintenance, as there are no moving parts.
  • Variants with flow rate control unit: flow rate control unit accessible via separate casing cover for maintenance purposes
  • The heat exchanger can be vacuumed with an industrial vacuum cleaner if necessary
  • VDI 6022, Part 1 applies - hygiene requirements for ventilation and air-conditioning systems and units

Technical information

Function, Technical data, Quick sizing, Specification text, Order code

  • FUNCTION
  • TECHNICAL DATA
  • QUICK SIZING
  • SPECIFICATION TEXT
  • ORDER CODE

Active chilled beams provide centrally conditioned primary air (supply air) to the room and use heat exchangers for additional cooling and/or heating. The primary air is discharged through nozzles into the mixing chamber. This induces secondary air from the room. The secondary air flows through the horizontal heat exchanger. There it is heated or cooled as required. Primary air and secondary air are mixed in the mixing chamber and flow horizontally into the room as supply air.

Nominal length

1000, 1125, 1250 mm

Length

1000, 1125, 1250 mm

Width

519, 616, 711, 808 mm

Height

207, 212 mm

Primary air spigot, diameter (ØD)

123, 158 mm

Primary air volume flow rate

8 – 57 l/s or 29 – 205 m³/h

Cooling capacity

up to 1600 W

Heating capacity

up to 1000 W

maximum operating pressure, water side

10 bar (6 bar in combination with connection hoses)

maximum operating temperature

75 °C (55 °C in combination with connection hoses)

The quick sizing table contains operating points for defined reference units, whereby the data applies for devices without flow rate control units (VC). Further operating points can be calculated using our Easy Product Finder design programme.

Quick sizing heat exchanger width 320 mm and primary air spigot diameter 123 mm


LN


1

Primary air

2

Cooling

Heating


qvPr [l/s]


qvPr [m³/h]


Δpt [Pa]

LWA [dB(A)]

2-pipe and 4-pipe system

4-pipe system


Qtotal [W]

QWK [W]

ΔtW [K]

Δpw [kPa]

Qtotal = QW [W]

ΔtW [K]

Δpw [kPa]

1000

HE

8

29

56

<15

406

309

2.4

2.1

456

7.8

0.1

1000

HE

14

50

167

27

635

468

3.7

2.1

600

10.3

0.1

1000

S1

10

37

37

<15

427

303

2.4

2.1

456

7.9

0.1

1000

S1

21

76

157

26

770

515

4

2.1

635

10.9

0.1

1000

S2

12

43

23

<15

415

272

2.1

2.1

435

7.5

0.1

1000

S2

30

108

146

29

907

546

4.3

2.1

654

11.2

0.1

1000

HP

17

61

22

<15

485

280

2.2

2.1

453

7.8

0.1

1000

HP

43

155

144

37

1083

564

4.4

2.1

674

11.6

0.1

1000

H2

14

50

21

<15

433

266

2.1

2.1

444

7.6

0.1

1000

H2

37

133

148

33

1012

567

4.4

2.1

671

11.5

0.1

1125

HE

9

33

67

<15

406

346

2.7

2.4

508

8.7

0.1

1125

HE

15

53

172

26

674

497

3.9

2.4

643

11.1

0.1

1125

S1

12

43

44

<15

492

348

2.7

2.4

514

8.8

0.1

1125

S1

23

83

162

27

835

557

4.4

2.4

690

11.9

0.1

1125

S2

13

47

23

<15

448

291

2.3

2.4

473

8.1

0.1

1125

S2

33

118

146

29

984

590

4.6

2.4

711

12.2

0.1

1125

HP

19

68

22

<15

535

308

2.4

2.4

498

8.6

0.1

1125

HP

48

174

145

39

1199

617

4.8

2.4

738

12.7

0.1

1125

H2

16

58

22

<15

501

307

2.4

2.4

500

8.6

0.1

1125

H2

41

148

144

37

1113

617

4.8

2.4

733

12.6

0.1

1250

HE

11

39

69

<15

532

401

3.1

2.7

574

9.9

0.1

1250

HE

17

62

173

29

764

557

4.4

2.7

714

12.3

0.1

1250

S1

13

47

38

<15

532

374

2.9

2.7

556

9.6

0.1

1250

S1

26

94

154

28

925

610

4.8

2.7

754

13

0.1

1250

S2

15

54

24

<15

513

333

2.6

2.7

528

9.1

0.1

1250

S2

37

132

146

30

1082

641

5

2.7

773

13.3

0.1

1250

HP

21

75

22

<15

585

334

2.6

2.7

542

9.3

0.1

1250

HP

54

194

145

41

1318

669

5.2

2.7

801

13.8

0.1

1250

H2

18

65

23

<15

558

340

2.7

2.7

549

9.4

0.1

1250

H2

45

162

144

35

1206

664

5.2

2.7

791

13.6

0.1

  1. 1 Nozzle type
  2. 2 Air-regenerated noise


Reference values

Parameter

Cooling

Heating

tR

26 °C

22 °C

tPr

16 °C

22 °C

tWV

16 °C

50 °C

qvW

110 l/h

50 l/h


Quick sizing heat exchanger width 512 mm and primary air spigot diameter 158 mm


LN


1

Primary air

2

Cooling

Heating


qvPr [l/s]


qvPr [m³/h]


Δpt [Pa]

LWA [dB(A)]

2-pipe and 4-pipe system

4-pipe system


Qtotal [W]

QWK [W]

ΔtW [K]

Δpw [kPa]

Qtotal = QW [W]

ΔtW [K]

Δpw [kPa]

1000

HE

9

32

75

<15

549

442

3.5

3.5

569

9.8

0.1

1000

HE

14

50

183

26

761

593

4.6

3.5

704

12.1

0.1

1000

S1

12

43

51

<15

591

447

3.5

3.5

584

10.1

0.1

1000

S1

21

76

160

27

920

665

5.2

3.5

774

13.3

0.1

1000

S2

13

47

28

<15

527

370

2.9

3.5

499

8.6

0.1

1000

S2

30

108

148

28

1075

714

5.6

3.5

804

13.8

0.1

1000

HP

18

65

24

<15

593

375

2.9

3.5

547

9.4

0.1

1000

HP

45

162

148

35

1293

751

5.9

3.5

868

14.9

0.1

1000

H2

15

54

24

<15

531

350

2.7

3.5

511

8.8

0.1

1000

H2

38

137

152

32

1207

748

5.9

3.5

838

14.4

0.1

1125

HE

10

36

78

<15

607

486

3.8

3.9

627

10.8

0.2

1125

HE

15

54

177

26

816

635

5

3.9

759

13.1

0.2

1125

S1

13

47

50

<15

636

478

3.7

3.9

632

10.9

0.2

1125

S1

24

86

167

27

1015

727

5.7

3.9

848

14.6

0.2

1125

S2

14

50

25

<15

546

378

3

3.9

526

9

0.2

1125

S2

34

122

150

29

1186

777

6.1

3.9

879

15.1

0.2

1125

HP

20

72

24

<15

647

406

3.2

3.9

596

10.3

0.2

1125

HP

50

180

148

36

1413

811

6.3

3.9

941

16.2

0.2

1125

H2

17

61

24

<15

594

389

3

3.9

566

9.7

0.2

1125

H2

42

151

149

32

1310

805

6.3

3.9

906

15.6

0.2

1250

HE

11

40

74

<15

663

529

4.1

4.3

682

11.7

0.2

1250

HE

17

62

177

26

906

698

5.5

4.3

833

14.3

0.2

1250

S1

15

54

51

<15

718

537

4.2

4.3

701

12.1

0.2

1250

S1

27

97

164

28

1113

789

6.2

4.3

921

15.8

0.2

1250

S2

16

58

28

<15

633

439

3.4

4.3

595

10.8

0.2

1250

S2

37

135

143

30

1273

828

6.5

4.3

941

16.2

0.2

1250

HP

22

80

22

<15

711

444

3.5

4.3

649

11.2

0.2

1250

HP

57

205

147

38

1565

879

6.9

4.3

1021

17.6

0.2

1250

H2

19

68

24

<15

655

427

3.3

4.3

618

10.6

0.2

1250

H2

47

170

147

34

1438

869

6.8

4.3

981

16.9

0.2

  1. 1 Nozzle type
  2. 2 Air-regenerated noise


Reference values

Parameter

Cooling

Heating

tR

26 °C

22 °C

tPr

16 °C

22 °C

tWV

16 °C

50 °C

qvW

110 l/h

50 l/h

This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.

Specification text

Active chilled beams with one-way air discharge, are a low-noise alternative to fan coil units, providing high thermal output and high thermal comfort levels. For installation into ceiling bulkheads, preferably in rooms with a height up to 4.00 m. The units consist of a casing with 4 fixing brackets, spigot, noncombustible nozzles, and horizontal heat exchanger. 5 nozzle variants for demand-based, optimal induction.


Special characteristics

  • One-way air discharge
  • Horizontal heat exchanger as 2-pipe or 4-pipe system
  • Connections on the rear of the device
    • Therefore with short cable runs
    • Connection possible in the corridor area
  • The supply air spigot is extendable (sliding) to compensate for structural tolerances
  • Nominal sizes are based on the basic dimensions
  • Integrated volume flow controller as an option


Materials and surfaces

  • Casing, nozzle plate, supply air spigot and installation subframe for secondary air grille made of galvanised sheet steel
  • Heat exchanger consisting of copper tubes and aluminium fins
  • Surface of the casing and heat exchanger optionally available in black (RAL 9005)


Technical data

  • Nominal length: 1000, 1125, 1250 mm
  • Length: 1000, 1125, 1250 mm
  • Width: 519, 616, 711, 808 mm
  • Height: 207, 212 mm
  • Diameter primary air spigot: 123, 158 mm
  • Primary air flow rate: 8 – 57 l/s or 29 – 205 m³/h
  • Cooling capacity: up to 1600 W
  • Heating capacity: up to 1000 W
  • Maximum operating pressure, water side: 10 bar (in combination with connection hoses 6 bar)
  • Maximum operating temperature: 75 °C (in combination with connection hoses 55 °C)


Sizing data

Primary air

  • qv [m³/h]
  • Δpt [Pa]

Air-regenerated noise

  • LWA [dB(A)]

Cooling

  • Qtotal [W]

Heating

  • Qtotal [W]


DID-E24S2RA2/1000 x 512 x 123/VC/Z/ERS/G1
||||||||||
12345678910


1 Type
DID-E2 Active chilled beam

2 Heat exchanger
2 2-pipe
4 4-pipe

3 Nozzle variant

HE small

S1 medium

S2 large

HP extra large

H2 Nozzle mix (S2 nozzle and HP nozzle)

4 Arrangement of water connections

R right

L left

5 Water connections

No entry: Ø12 mm pipe with plain tails

A1 with G½" external thread and flat seal

A2 with G½" union nut and flat seal

6 Nominal size [mm]

Nominal length × heat exchanger depth × primary air spigot

1000 × 320 × 123 (fits grid size 1000 m)

1000 × 512 × 158 (fits grid size 1000 m)

1125 × 320 × 123 (fits grid size 1125 m)

1125 × 512 × 158 (fits grid size 1125 m)

1250 × 320 × 123 (fits grid size 1250 m)

1250 × 512 × 158 (fits grid size 1250 m)

7 Volume flow control
No entry: without volume flow control

VC With flow rate control subassembly

8 Supply air spigot

No entry: without supply air spigot

Z With extension spigot for supply air

9 Installation subframe for secondary air grille

No entry: without installation subframe
ERS With an installation subframe from our portfolio

10 Surface of casing and heat exchanger

No entry: casing made of galvanised steel, heat exchanger with copper tubes and aluminium fins

G1 Similar to RAL 9005 (jet black)


Order example: DID-E2-4-S2-R-A1/1000×320×123/VC/Z/ERS/G1

Type DID-E2 – Active Chilled Beam 
Heat exchanger 4-pipe 
Nozzle variant large 
Arrangement of water connections right 
Water connections with G½" external thread, flat seal
Nominal size [mm]Nominal length 1000, heat exchanger depth 320, primary air spigot 123
Volume flow control with integrated flow rate control unit
Supply air spigot with sliding spigot for supply air
Installation subframe for secondary air grille with an installation subframe from the TROX grille range
Surface of casing and heat exchanger Similar to RAL 9005 (jet black)

Product details 

  • INSTALLATION AND COMMISSIONING


  • Preferably for clear room heights up to 4.00 m
  • Installation into ceiling bulkheads
  • Horizontal primary air connection
  • Lengths fit basic dimensions 1000, 1125 and 1250 mm
  • Heat exchanger depths 320 mm and 512 mm
  • Primary air spigot 123 mm and 158 mm
  • Installation of all connections as well as fixing, connecting and sealing material are not included and provided by the client.
  • The active chilled beam has 4 fixing brackets (slotted hole 38 × 8.5 mm) for fixing provided by the client
  • Connections on the rear of the device
    • Therefore with short cable runs
    • Connection possible in the corridor area
  • Optional supply air spigot functions like a sliding spigot (bridgeable installation range 38 - 78 mm)
  • Possible options for the intake of secondary air:
    • Ventilation grille for supply air and secondary air from the TROX grille product range
    • Perforated metal plate specifically developed for DID-E2
    • MCE provided by the client
  • Secure the secondary air grille with safety cables: the optional installation subframe for secondary air grilles has safety cables

Downloads

product information

certificates

operation manuals

References

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be