00137751_0
IDB


00132715_0
Tested to VDI 6022


00137207_0
Eurovent certification


00137752_0
Levelling feet


00131177_0
Row of nozzles


00137751_0
00132715_0
00137207_0
00137752_0
00131177_0

IDB 

Brüstungsinduktionsdurchlass für Nennlängen von 600, 900, 1200, 1350 mm mit vertikalem Wärmeübertrager und Kondensatwanne

Under sill induction unit with 2-pipe or 4-pipe heat exchanger, of compact height, for installation under a sill or on a wall. The condensate drip tray is useful if the temperature temporarily falls below the dew point.

  • High heating and cooling capacity with a low conditioned primary air volume flow rate and low sound power level
  • High comfort levels due to low airflow velocity in the occupied zone
  • Four nozzle variants to optimise induction based on demand


Optional equipment and accessories

  • Control equipment
  • Lint screen to protect the heat exchanger from contamination
  • Powder coating in many different colours, e.g. RAL CLASSIC

Application

Application

  • Type IDB under sill induction units of compact height, for installation on an external wall, e.g. under a sill.
  • Inducing displacement flow
  • 2-pipe or 4-pipe heat exchangers enable good comfort levels with a low conditioned primary air volume flow rate
  • Energy-efficient solution since water is used for heating and cooling

Special characteristics

  • Supply air discharge as inducing displacement flow
  • Vertical heat exchanger as 2-pipe or 4-pipe system, optional condensate drip tray including condensate drain that can be connected to a condensate pipe (to be provided by others)
  • Water connections at the narrow side, Ø12 mm Cu pipe, with plain tails or with G½" external thread, or with a G½" union nut; with flat seal

Nominal sizes

  • 600, 900, 1200 mm

Description

Variants

Heat exchanger

  • 2: 2-pipe systems
  • 4: 4-pipe systems


Nozzle variants

  • M: Medium
  • G: Large
  • U: Extra large
  • 2U: Two nozzle rows, extra large nozzles

Construction

  • Galvanised
  • P1: Powder-coated RAL 9005, black, gloss level 70 %

Attachments

  • Water connection A1: G½" external thread and flat seal
  • Water connection A2: G½" union nut and flat seal
  • Condensate drip tray
  • Lint screen

Accessories

  • Wall and floor fixing

Useful additions

  • Connecting hoses
  • Control equipment consisting of a control panel including a controller with integral room temperature sensor; valves and valve actuators; and lockshields
  • X-AIRCONTROL control system

Construction features

  • Spigot is suitable for circular ducts to EN 1506 or EN 13180
  • Four nozzle variants to optimise induction based on demand
  • Vent valves on the heat exchanger

Materials and surfaces

  • Casing, primary air plenum and feet made of galvanised sheet steel
  • Lint screen made of stainless steel
  • Heat exchanger with copper tubes and aluminium fins
  • Exposed surfaces either untreated or powder-coated black (RAL 9005)
  • Heat exchanger also in black (RAL 9005)

Standards and guidelines

  • Products are certified by Eurovent (no. 09.12.432) and listed on the Eurovent website
  • Declaration of hygiene conformity to VDI 6022

Maintenance

  • No moving parts, hence low maintenance
  • The heat exchanger can be vacuumed with an industrial vacuum cleaner if necessary
  • VDI 6022, Part 1, applies (Hygiene requirements for ventilation and air-conditioning systems and units)

Technical information

Function, Technical data, Quick sizing, Specification text, ORDER CODE, Related products

  • Function
  • Technical data
  • Quick sizing
  • Specification text
  • ORDER CODE

Functional description

Under sill induction units provide centrally conditioned primary air (fresh air) to the room and use heat exchangers for cooling and/or heating.

The primary air is discharged through nozzles and induces secondary air (room air), which passes through the heat exchanger.

Primary and secondary air mix and are then supplied to the room as an inducing displacement flow.

Nominal length

600, 900, 1200 mm

Length

643, 943, 1243 mm

Height

Min. 555 mm, max. 605 mm

Width

155 mm

Primary air volume flow rate

4 – 40 l/s or 14 – 144 m³/h

Cooling capacity

Up to 950 W

Heating capacity

Up to 470 W

Max. operating pressure, water side

6 bar

Max. operating temperature, water side

75 °C


The quick sizing table contains operating points for defined reference units.

Quick sizing – spigot diameter 100 mm

LN Primary air Cooling Heating
LN VPr Δpt LWA 2-pipe and 4-pipe systems 4-pipe system
LN VPr Δpt LWA Qtot QWK ΔtW ΔpW QWH = Qtot ΔtW ΔpW
LN l/s m³/h Pa dB(A) W K kPa W K kPa

600

M

3

10.8

71

<20

193

157

- 1.2

2.44

180

3.1

0.19

600

M

5

18.0

199

22

275

214

-1.7

2.44

246

4.2

0.19

600

M

7

25.2

389

32

346

262

-2.0

2.44

301

5.2

0.19

600

G

5

18.0

51

<20

238

178

-1.4

2.44

203

3.5

0.19

600

G

9

32.4

166

23.5

365

256

-2.0

2.44

294

5.1

0.19

600

G

12

43.2

295

32

450

305

-2.4

2.44

351

6.0

0.19

600

U

10

36.0

67

<20

346

226

-1.8

2.44

259

4.5

0.19

600

U

15

54.0

152

27

473

292

-2.3

2.44

336

5.8

0.19

600

U

20

72.0

270

35

590

349

-2.7

2.44

403

6.9

0.19

900

M

5

18.0

83

<20

304

243

-1.9

3.13

279

4.8

0.24

900

M

7.5

27.0

187

24

399

308

-2.4

3.13

355

6.1

0.24

900

M

10

36.0

333

32

484

362

-4.8

3.13

420

7.2

0.24

900

G

10

36.0

86

<20

427

307

-2.4

3.13

353

6.1

0.24

900

G

15

54.0

194

29

570

389

-3.0

3.13

449

7.7

0.24

900

G

20

72.0

345

38

699

458

-3.6

3.13

531

9.1

0.24

900

U

15

54.0

64

<20

505

324

-2.5

3.13

374

6.4

0.24

900

U

20

72.0

115

28

628

386

-3.0

3.13

446

7.7

0.24

900

U

25

90.0

180

35

743

441

-3.4

3.13

511

8.8

0.24

1200

M

5

18.0

45

<20

326

266

-2.1

3.83

306

5.3

0.29

1200

M

10

36.0

182

25

516

395

-3.1

3.83

457

7.9

0.29

1200

M

15

54.0

410

37

674

493

-3.9

3.83

572

9.8

0.29

1200

G

10

36.0

47

<20

453

332

-2.6

3.83

383

6.6

0.29

1200

G

15

54.0

107

23

601

320

-3.3

3.83

486

8.4

0.29

1200

G

20

72.0

190

32

735

494

-3.9

3.83

573

9.9

0.29

1200

U

20

72.0

64

25

656

415

-3.2

3.83

480

8.3

0.29

1200

U

30

108.0

145

37

886

524

-4.1

3.83

609

10.5

0.29

1200

U

40

144.0

257

46

1097

614

-4.8

3.83

717

12.3

0.29

① Nozzle variant ② Air-regenerated noise


Quick sizing – spigot diameter 125 mm

LN Primary air Cooling Heating
LN VPr Δpt LWA 2-pipe and 4-pipe systems 4-pipe system
LN VPr Δpt LWA Qtot QWK ΔtW ΔpW QWH = Qtot ΔtW ΔpW
LN l/s m³/h Pa dB(A) W K kPa W K kPa

600

2U

20

72.0

71

<20

496

255

-2.0

2.44

254

4.4

0.19

600

2U

28

100.8

139

30

652

315

-2.5

2.44

316

5.4

0.19

600

2U

35

126.0

218

36

783

361

-2.8

2.44

364

6.3

0.19

900

2U

20

72.0

30

<20

525

283

-2.2

3.13

283

4.9

0.24

900

2U

30

108.0

67

26

726

364

-2.8

3.13

367

6.3

0.24

900

2U

40

144.0

120

35

915

432

-3.4

3.13

439

7.5

0.24

1200

2U

26

93.6

28

20

674

360

-2.8

3.83

362

6.2

0.29

1200

2U

30

108.0

38

25

753

391

-3.1

3.83

395

6.8

0.29

1200

2U

40

144.0

67

34

946

463

-3.6

3.83

472

8.1

0.29

① Nozzle variant ② Air-regenerated noise


Reference values

Parameter Cooling Heating

tR

16 °C

22 °C

tPr

26 °C

22 °C

tWV

16 °C

50 °C

VW

110 l/h

50 l/h


Induction units of Type IDB, for under sill or wall installation, with one-way discharge and high thermal output, providing high thermal comfort levels.

For installation under the sill or on a wall.

The units consist of a casing with a primary air plenum, spigot, non-combustible nozzles, and vertical heat exchanger; a condensate drip tray is optional.

Special characteristics

  • Supply air discharge as inducing displacement flow
  • Vertical heat exchanger as 2-pipe or 4-pipe system, optional condensate drip tray including condensate drain that can be connected to a condensate pipe (to be provided by others)
  • Water connections at the narrow side, Ø12 mm Cu pipe, with plain tails or with G½" external thread, or with a G½" union nut; with flat seal

Materials and surfaces

  • Casing, primary air plenum and feet made of galvanised sheet steel
  • Lint screen made of stainless steel
  • Heat exchanger with copper tubes and aluminium fins
  • Exposed surfaces either untreated or powder-coated black (RAL 9005)
  • Heat exchanger also in black (RAL 9005)

Construction

  • Galvanised
  • P1: Powder-coated RAL 9005, black, gloss level 70 %

Technical data

  • Nominal length: 600, 900, 1200 mm
  • Length: 643, 943, 1243 mm
  • Height: Min. 555 mm, max. 605 mm
  • Width: 155 mm
  • Primary air volume flow rate: 4 – 40 l/s or 14 – 144 m³/h
  • Cooling capacity: up to 950 W
  • Heating capacity: up to 470 W
  • Max. operating pressure: 6 bar
  • Max. operating temperature: 75 °C

This specification text describes the general properties of the product.

00135927_0

 Type
IDB       Under sill induction units

 Heat exchanger
2       2-pipe
4       4-pipe

 Nozzle variants
M       Medium
G       Large
U       Extra large
2U       2 rows, extra large

 Arrangement of the water connection
RE       Right side
LI       Left side

 Water connections
       No entry: Ø12 mm pipe with plain tails
A1       With G½" external thread and flat seal
A2       With G½" union nut and flat seal

 Arrangement of air connections
SL       Left side
SR       Right side
VM       Front, centre

 

 Condensate drip tray
       No entry: none
KW       With

 Nominal length [mm]
600
900
1200
1350

 Spigot diameter [mm]
98
123

 Fixing material (supplied separately)
       No entry: none
W0       Wall fixing
B0       Floor fixing
WB       Wall and floor fixing

 Surface of casing and heat exchanger
       No entry: untreated
G1       RAL 9005, black
G3       RAL 9005, black, heat exchanger only

 Lint screen
       No entry: none
FS       With

 Valves and actuators
       No entry: none
VS       With

IDB–2–G–RE–SL/1200×123

Heat exchanger

2-pipe

Nozzle variant

Large

Arrangement of the water connection

Right side

Arrangement of the air connection

Left side

Nominal length

1200 mm

Spigot diameter

Ø123 mm


IDB–4–U–LI–SL–KW/1200×123/WB/G1/FS/VS

Heat exchanger

4-pipe

Nozzle variant

Extra large

Arrangement of the water connection

Left side

Arrangement of the air connection

Left side

Condensate drip tray

With

Nominal length

1200 mm

Spigot diameter

Ø123 mm

Wall and floor fixing

With

Surface of casing and heat exchanger

Black

Lint screen

With

Valves and actuators

With


 

Dimensions and weight

  • Dimensions and weight
IDB 00133779_0


Weight [kg]

LN [mm] 600 900 1200

Unit

9

15

21

Contained water

1.2

1.8

2.4

Condensate drip tray

0.6

0.9

1.2

Lint screen

0.8

1.1

1.4


Dimensions [mm]

LN ØD

600, 900, 1200

98

600, 900, 1200

123


Installation examples, Installation details, Basic information and nomenclature

  • Installation examples
  • Installation details
  • Basic information and nomenclature

Installation and commissioning

  • Under sill or wall installation
  • Side entry primary air spigot at the narrow side or front
  • Installation and connections to be performed by others; fixing, connection and sealing material to be provided by others
  • The unit can be fixed to the floor and/or to the wall with the fixing material supplied (accessory)
  • Heat exchangers are fitted with water flow and water return connections at the narrow side

LN [mm]

Nominal length

LWA [dB(A)]

Sound power level

tPr [°C]

Primary air temperature

tWV [C°]

Water flow temperature – cooling/heating

tR [C°]

Room temperature

tR [C°]

Room temperature

tAN [C°]

Secondary air intake temperature

QPr [W]

Thermal output – primary air

Qtot [W]

Thermal output – total

QW [W]

Thermal output – water side, cooling/heating

VPr [l/s]

Primary air volume flow rate

VPr [m³/h]

Primary air volume flow rate

VW [l/h]

Water flow rate – cooling/heating

V [l/h]

Volume flow rate

∆tW [K]

Temperature difference – water

∆pW [kPa]

Pressure drop, water side

∆pt [Pa]

Total pressure drop, air side

∆tPr = tPr - tR [K]

Difference between primary air temperature and room temperature

∆tRWV = tWV - tR [K]

Difference between water flow temperature and room temperature

∆tWm-Ref [K]

Difference between mean water temperature and reference temperature

LN [mm]

Nominal length

Inducing displacement flow

The supply air is discharged near the external wall and with a medium velocity between 1.0 and 1.5 m/s. Due to the induction effect the supply air velocity is rapidly reduced such that, in cooling mode, the supply air displaces the room air over the entire floor area. The convection from people and other heat sources causes the fresh air from the pool to rise and create comfortable conditions in the occupied zone.

Heat exchanger

The maximum water-side operating pressure for all heat exchangers is 6 bar.

The maximum water flow temperature (heating circuit) for all heat exchangers is 75 °C; if flexible hoses are used, the water flow temperature should not exceed 55 °C. Units for other pressures and temperatures are available on request.

The water flow temperature (cooling circuit) should be at least 16 °C such that it does not permanently fall below the dew point. For units with a condensate drip tray the water flow temperature may be reduced to 15 °C.

Heat exchanger as 2-pipe system

Air-water systems with a 2-pipe heat exchanger may be used for either heating or cooling. In changeover mode it is possible to use all units within a water circuit exclusively for cooling in summer and exclusively for heating in winter.

Heat exchanger as 4-pipe system

Air-water systems with a 4-pipe heat exchanger may be used for both heating and cooling. Depending on the season, i.e. especially in spring and autumn, it may be possible that an office has to be heated in the morning and cooled in the afternoon.

Downloads

product information

certificates

operation manuals

References

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be