Application
Special features
Nominal sizes
Construction
Parts and characteristics
Attachments
Construction features
Materials and surfaces
Galvanised sheet steel construction
Stainless steel construction (A2)
Standards and guidelines
Maintenance
Functional description
For balancing the volume flow rates of duct sections and air terminal devices the differential pressure must be set on the flow adjustment dampers. The value to be set for a certain required volume flow rate at a given differential pressure can be taken from the diagram that each flow adjustment damper carries. This value can then be set using the rotary knob with the position indicator (stepless adjustment between 0 and 10).
Nominal sizes | 80 – 250 mm |
Volume flow rate range | 20 – 485 l/s or 72 – 1746 m³/h |
Minimum differential pressure | 20 Pa |
Maximum differential pressure | 1000 Pa |
Operating temperature | 10 – 50 °C |
Closed blade air leakage
80 | 9 | 32 | 13 | 46 | 20 | 72 |
100 | 13 | 45 | 18 | 64 | 28 | 101 |
125 | 16 | 58 | 23 | 82 | 36 | 130 |
140 | 17 | 61 | 25 | 89 | 39 | 140 |
150 | 18 | 66 | 26 | 93 | 41 | 148 |
160 | 21 | 76 | 30 | 107 | 47 | 169 |
180 | 19 | 69 | 27 | 98 | 43 | 155 |
200 | 21 | 74 | 29 | 105 | 46 | 166 |
224 | 22 | 80 | 32 | 114 | 50 | 180 |
250 | 25 | 89 | 35 | 125 | 55 | 198 |
Quick sizing tables provide a good overview of the room sound pressure levels that can be expected. Approximate intermediate values can be interpolated.
Quick sizing: Sound pressure level
80 | 20 | 72 | 25 | 28 | 30 | 32 | 35 | 36 | 41 |
80 | 30 | 108 | 30 | 33 | 35 | 37 | 40 | 41 | 45 |
80 | 40 | 144 | 33 | 36 | 38 | 41 | 43 | 45 | 49 |
80 | 50 | 180 | 36 | 40 | 42 | 44 | 47 | 48 | 53 |
100 | 30 | 109 | 27 | 29 | 31 | 34 | 36 | 38 | 44 |
100 | 45 | 163 | 32 | 35 | 37 | 39 | 42 | 43 | 48 |
100 | 60 | 217 | 36 | 39 | 41 | 44 | 46 | 48 | 52 |
100 | 75 | 272 | 40 | 43 | 45 | 48 | 50 | 52 | 56 |
125 | 50 | 180 | 28 | 31 | 33 | 36 | 39 | 41 | 47 |
125 | 70 | 252 | 33 | 36 | 38 | 41 | 44 | 46 | 51 |
125 | 95 | 342 | 37 | 41 | 43 | 46 | 49 | 50 | 55 |
125 | 120 | 432 | 41 | 45 | 47 | 50 | 53 | 54 | 59 |
140 | 60 | 215 | 25 | 29 | 31 | 34 | 38 | 40 | 47 |
140 | 90 | 323 | 31 | 34 | 37 | 40 | 44 | 45 | 51 |
140 | 120 | 431 | 35 | 39 | 42 | 45 | 48 | 50 | 56 |
140 | 150 | 538 | 39 | 43 | 45 | 49 | 52 | 54 | 59 |
150 | 70 | 252 | 26 | 30 | 32 | 36 | 39 | 41 | 48 |
150 | 105 | 378 | 31 | 35 | 37 | 41 | 44 | 46 | 52 |
150 | 140 | 504 | 35 | 39 | 42 | 45 | 48 | 50 | 56 |
150 | 170 | 612 | 37 | 42 | 44 | 48 | 51 | 53 | 58 |
160 | 80 | 288 | 27 | 30 | 33 | 36 | 39 | 41 | 48 |
160 | 120 | 432 | 33 | 37 | 39 | 42 | 45 | 47 | 53 |
160 | 155 | 558 | 38 | 41 | 44 | 47 | 50 | 51 | 57 |
160 | 195 | 702 | 41 | 45 | 47 | 50 | 53 | 54 | 59 |
180 | 100 | 358 | 25 | 29 | 32 | 35 | 39 | 41 | 48 |
180 | 150 | 540 | 31 | 35 | 38 | 41 | 45 | 47 | 53 |
180 | 200 | 720 | 35 | 39 | 42 | 45 | 48 | 50 | 56 |
180 | 250 | 900 | 38 | 42 | 45 | 48 | 51 | 53 | 59 |
200 | 125 | 450 | 26 | 30 | 33 | 37 | 41 | 43 | 51 |
200 | 185 | 665 | 32 | 36 | 39 | 42 | 46 | 48 | 55 |
200 | 245 | 882 | 36 | 40 | 43 | 47 | 50 | 52 | 59 |
200 | 310 | 1116 | 39 | 44 | 46 | 50 | 54 | 56 | 62 |
224 | 155 | 557 | 24 | 28 | 31 | 35 | 39 | 41 | 47 |
224 | 230 | 828 | 28 | 32 | 35 | 39 | 42 | 44 | 50 |
224 | 310 | 1115 | 32 | 36 | 38 | 42 | 45 | 47 | 53 |
224 | 385 | 1386 | 34 | 38 | 41 | 44 | 48 | 49 | 55 |
250 | 195 | 702 | 24 | 28 | 32 | 36 | 41 | 43 | 52 |
250 | 290 | 1043 | 28 | 33 | 36 | 40 | 45 | 47 | 56 |
250 | 385 | 1386 | 31 | 36 | 40 | 44 | 49 | 51 | 59 |
250 | 485 | 1746 | 34 | 39 | 43 | 47 | 52 | 54 | 62 |
Circular flow adjustment dampers for the simple balancing of volume flow rates in air conditioning systems, for supply air and extract air, available in 10 nominal sizes.
Suitable for duct pressures up to 1000 Pa.
Ready-to-install unit consists of the casing with damper blade and rotary knob for the stepless adjustment of volume flow rates.
Spigot with lip seal, for circular connecting ducts to EN 1506 or EN 13180.
Casing air leakage to EN 1751, class C.
Special features
Materials and surfaces
Galvanised sheet steel construction
Stainless steel construction (A2)
Construction
Technical data
Sizing data
Air-regenerated noise
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Order example: VFR/160/M01
Nominal size | 160 mm |
Actuator | 24 V AC/DC, mechanical stops |
Attachments
Min/Max actuators | |||
E01 | Actuator with potentiometers TROX/Gruner | 24 V AC/DC | – |
E02 | Actuator with potentiometers TROX/Gruner | 230 V AC | – |
M01 | Actuator with mechanical stops TROX/Belimo | 24 V AC/DC | – |
M02 | Actuator with mechanical stops TROX/Belimo | 230 V AC | – |
Modulating actuators | |||
E03 | Actuator with potentiometers TROX/Gruner | 24 V AC/DC | – |
Installation and commissioning
Space required
Without actuator | 200 | 200 | 200 |
With actuator E0* | 200 | 200 | 300 |
With actuator M0* | 200 | 200 | 230 |
Principal dimensions
ØD [mm]
Shut-off and flow adjustment dampers made of stainless steel: Outer diameter of the connecting spigot
Shut-off dampers made of plastic: Inside diameter of the connecting spigot
ØD₁ [mm]
Pitch circle diameter of flanges
ØD₂ [mm]
Outer diameter of flanges
ØD₄ [mm]
Inside diameter of the screw holes of flanges
L [mm]
Length of unit including connecting spigot
L₁ [mm]
Length of casing or acoustic cladding
n [ ]
Number of flange screw holes
T [mm]
Flange thickness
m [kg]
Unit weight including the minimum required attachments
Acoustic data
LPA [dB(A)]
A-weighted sound pressure level of air-regenerated noise of the shut-off or flow adjustment damper, system attenuation taken into account
All sound pressure levels are based on 20 μPa.
Volume flow rates
V [m³/h] and [l/s]
Volume flow rate
Differential pressure
Δpst [Pa]
Static differential pressure
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be