Application
Special characteristics
Classification
Nominal sizes
Filter classes
Filter groups
Filter classes
Options
Construction
Useful additions
Construction features
Compact V-design
Fine dust filter (filter groups according to ISO 16890) as standard without seal, optionally with flat seal
Filter classes E10, E11, H13 and H14 as standard with flat seal
Material and surfaces
Standards and guidelines
Fractional efficiency ePM10 [%] to ISO 16890 | 55 | – | – |
Fractional efficiency ePM1 [%] to ISO 16890 | – | 60 | 85 |
Initial differential pressure [Pa] at nominal volume flow rate | 80 | 105 | 130 |
Final differential pressure [Pa] | 450 | 450 | 450 |
Maximum operating temperature [°C] | 80 | 80 | 80 |
Maximum relative humidity [%] | 100 | 100 | 100 |
Filter class according to EN 1822 | E10 | E11 | H13 | H14 |
Efficiency [%] according to EN 1822 | > 85 | > 95 | > 99.95 | > 99.995 |
Initial differential pressure [Pa] at nominal volume flow rate | 160 | 160 | 265 | 300 |
Final differential pressure [Pa] | 450 | 450 | 600 | 600 |
Maximum operating temperature [°C] | 80 | 80 | 80 | 80 |
Maximum relative humidity [%] | 100 | 100 | 100 | 100 |
Specification text
Mini Pleat filter insert type MFI for the separation of fine dust and suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply and extract air in ventilation systems. Used as fine dust filters, prefilters or final filters in AHU units; or as particulate filters, main or final filters for highest requirements of air purity and sterility, in areas such as industry, research, medicine, pharmaceuticals, and nuclear technology. Low installation depth due to compact V-design, for systems with high volume flow rates and long filter service lives. Filter media made of high-quality, wet-strength glass fibre papers, with spacers. Optimum pleat position and largest possible filter area allow low initial differential pressures. Mini Pleat filter inserts available in market sizes, filter groups ISO ePM10, ISO ePM1 (fine dust filters) and EPA, HEPA (particulate filters). As a fine dust filter (filter groups according to ISO 16890) as standard without seal, optionally available with flat seal, as a particulate filter, Mini Pleat filter inserts are equipped with a flat seal. Filter classes E11, H13 and H14 as standard with protection grid on the downstream side. Mini Pleat filter insert as fine dust filters are certified according to Eurovent. Mini Pleat filter inserts MFI are hygiene-compliant according to VDI 6022.
The filter insert MFI with optional EX protection MFI-EX may be used in areas with a potentially explosive atmosphere of zones 1 and 2 and zones 21 and 22 (EX II 2G Ex h IIC Gb and EX II 2D Ex h IIIB Db).
The filter must be connected to the ground potential. All conductive and dissipative parts must be connected to each other and to earthed. Conductive dusts are excluded from the application. Make sure that no metal particles can get into the filter. Ambient temperature range: -40 °C ≤ Ta ≤ +80 °C.
Special features
Materials and surfaces
Construction
Sizing data
Life cycle assessment
A life cycle assessment is available for the product series in form of an Environmental Product Declaration (EPD) that has been checked and published by a programme holder.
MFI | – | H13 | – | – | GAL | / | 592 × 592 × 292 | × | 8 | / | PD | / | FNU | / | OT | |
| | | | | | | | | | | | | | | | | | ||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
1 Type
MFI Mini Pleat filter insert
2 Classification
ePM1 Fractional efficiency ePM1 acc. to ISO 16890
ePM10 Fractional efficiency ePM10 acc. to ISO 16890
E10 Filter class E10 according to EN 1822
E11 Filter class E11 according to EN 1822
H13 Filter class H13 according to EN 1822
H14 Filter class H14 according to EN 1822
3 Separation efficiency
Specify the separation efficiency [%] according to ISO 16890 (not for E10, E11, H13, H14)
4 Construction
PLA Frame made of plastic
PLA-ECO Plastic frame, optimised energy efficiency
GAL Frame made of galvanised sheet steel
SPC Frame made of galvanised sheet steel, powder-coated RAL 9010 (pure white)
EX Frame made of galvanised sheet steel, for zones 1 and 2 as well as 21 and 22 in areas with potentially explosive atmospheres (EX)
5 Nominal size [mm]
Specify width × height × depth
6 Number of filter packs
6, 8
7 Protection grid
No entry: without protection grid
PD Protection grid on the downstream side (E11, H13, H14 only)
8 Seal
No entry: without seal
FNU Flat seal on the upstream side
FND Flat seal on the downstream side
9 Testing
No entry: no leakage test
OT Oil mist test (only H13, H14)
OTC Oil mist test with certificate (only H13, H14)
Order example: MFI-H13-GAL/592×592×292×8/PD/FNU/OT
Type | MFI |
Classification | Filter class H13 according to EN 1822 |
Separation efficiency | - |
Variant | Frame made of galvanised sheet steel |
Nominal size [mm] | Width 592, height 592, depth 292 |
Number of filter packs | 8 |
Protection grid | Protection grid on the upstream side |
Seal | Flat seal on the downstream side |
Testing | Oil mist test |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be