00179543_0
Expansion module Type EM-IP


00182993_0
BACnet-IP-Schnittstelle


00182988_0
Modbus-IP-Schnittstelle


00179543_0
00182993_0
00182988_0

EM-IP

BACnet/IP interface, Modbus/IP interface, and webserver for EASYLAB controllers and TAM adapter modules

Expansion module for EASYLAB fume cupboard controllers, room controllers and TAM adapter modules, for the integration of rooms or individual volume flow controllers with the central BMS, and for accessing the above mentioned devices using the integral webserver.

  • Change between BACnet/IP and Modbus/IP using the integral webserver
  • BACnet Application Specific Controller (B-ASC) according to Annex L
  • Trend logging, alarming and scheduling for selected data points
  • BACnet/IP (Annex J based on IPv4)
  • BACnet/IP interface by integrating the expansion module with EASYLAB components
  • Modbus interface with individual data registers
  • Modbus/IP (according to IEC 61158)
  • Easy retrofitting
  • Two RJ45 10/100 Mbit Ethernet connections (daisy chain is possible)
  • Multi functional Reset push button
  • Power and status indicator lights
  • MicroSD card as persistent data store for firmware, trend logging, alarming, scheduling and help files
  • Real time clock expansion module (RTC) (optional)

Application

Application

  • Expansion module Type EM-IP for the EASYLAB system
  • BACnet/IP or Modbus/IP interface to the central BMS
  • Integral webserver for configuring EM-IP
  • Display of the principal device data on the web UI
  • BACnet trend logging, alarming and scheduling for selected data points
  • Data points for individual controllers or for the room
  • Room interface: Default setting of room operating modes within the EASYLAB system, increase or reduction of the air change rate, readout of the actual room operating values or evaluated damper blade positions, consolidated alarms, volume flow rates and alarms for all EASYLAB controllers in a room
  • Controller interface: Operating mode default setting for a single fume cupboard controller, readout of individual operating values such as volume flow rates for single controllers, or individual alarms
  • Can be used with fume cupboard, supply air, extract air or differential pressure controller EASYLAB TCU3 and with adapter module TAM
  • For use in laboratories, clean rooms in the pharmaceutical and semiconductor industries, operating theatres, intensive care units, and offices with very demanding control requirements
  • Factory mounted or for retrofitting into the EASYLAB base component casing

Special characteristics

  • Ready for installation, can be easily connected to the main PCB
  • Interface for IP-based networks BACnet/IP and Modbus/IP
  • BACnet Application Specific Controller (B-ASC) according to Annex L
  • Connection for access to BACnet/IP network, Modbus/IP network or integral webserver
  • BACnet/IP Protocol Revision 7.0
  • Only standard BACnet objects or Modbus registers are used for communication
  • Data interface for an EASYLAB controller or for an EASYLAB room with different functional profiles
  • Multi functional Reset push button
  • All settings for alarming, trend logging, event logging, notifications and scheduling can be accessed and changed using the integral webserver (no configuration software required)
  • 2 GB microSD card for firmware, trend logging, event logging and alarming
  • With BACnet Broadcast Managment Device (BBMD) function
  • Foreign devices are supported
  • Firmware is updated using the webserver

Description

Parts and characteristics

  • Microprocessor with setup program stored in nonvolatile memory
  • Two RJ45 10/100 Mbit Ethernet connections for accessing the BACnet/IP networks, the Modbus/IP network or the integral webserver (up to five EM-IP modules can be linked by a daisy chain)
  • Daisy chain function can be switched off
  • Reset push button for resetting EM-IP using the web UI, for activating two IP configurations and for restarting the module
  • One LED each for power and status

Construction features

  • PCB dimensions and fixing points correspond to the EASYLAB main PCB and the casing
  • Fixing with screws
  • Pin header to connect the module to the main PCB of the TCU3 or TAM

Technical information

Function, Technical data, Specification text, Order code, Related products

  • Function
  • Technical data
  • Specification text
  • Order code
EM-IP 00183004_0
① Power LED
② Plug base for connection with the EASYLAB main PCB
③ Status LED
④ RJ45 sockets for Ethernet cabling (LAN 2)
⑤ LED LAN 1
⑥ RJ45 sockets for Ethernet cabling (LAN 1)
⑦ LED LAN 2
⑧ Slot for microSD card
⑨ Reset push button, also for switching the DHCP client on/off
⑩ Plug base for optional RTC module (real time clock)


Functional description

Expansion module EM-IP is used to integrate EASYLAB controllers Type TCU3 or EASYLAB adapter modules Type TAM into an IP-based network and connect them to the central BMS using the BACnet/IP or Modbus/IP protocol.

The BACnet or Modbus interface supports the EASYLAB room operating mode concept. It is possible to set operating mode defaults in order to control different volume flow rates for daytime and night-time operation; it is also possible to increase or reduce the air change rate (volume flow rate setpoint change), e.g. to influence the room temperature.

Using the BACnet or Modbus interface, an individual alarm management system can be set up by consolidating configurable EASYLAB alarms. The interface also enables the transfer of actual operating values such as volume flow rates and damper blade position for a controller or for all controllers in a room.

BACnet/IP mode and the webserver allow for trend logging, alarming and scheduling for selected data points. The integral microSD card is used for trend logging. The integral webserver is used to configure EM-IP, to access trend logs and event logs, and to enter controller data using the web UI.

The optional real time clock (RTC) expansion module can be used for trend logging or event logging if, for example, EM-IP is not integrated with a network of if no time server is available in the network.

Dimensions (B × H × T)

65 × 15 × 90 mm

Supply voltage (from the controller TCU3 or adapter module TAM)

5 V DC

Acceptable temperature range for storage

–10 to 70 °C

Acceptable temperature range for operation

10 – 50 °C

Maximum humidity, non-condensing, for storage and operation

<90 %

Protection level

IP 20

Persistent data store for firmware, logging objects and help files

2 GB microSD card


Expansion module to supplement an EASYLAB base component (controller TCU3 or adapter module TAM) with a BACnet/IP or Modbus/IP interface to link rooms or individual volume flow controllers to the central BMS.

Expansion module includes an interface for IP-based networks; switching between BACnet/IP and Modbus/IP is possible. All settings for alarming, trend logging, event logging, notifications and scheduling can be accessed and changed using the integral webserver.

Special characteristics

  • Ready for installation, can be easily connected to the main PCB
  • Interface for IP-based networks BACnet/IP and Modbus/IP
  • BACnet Application Specific Controller (B-ASC) according to Annex L
  • Connection for access to BACnet/IP network, Modbus/IP network or integral webserver
  • BACnet/IP Protocol Revision 7.0
  • Only standard BACnet objects or Modbus registers are used for communication
  • Data interface for an EASYLAB controller or for an EASYLAB room with different functional profiles
  • Multi functional Reset push button
  • All settings for alarming, trend logging, event logging, notifications and scheduling can be accessed and changed using the integral webserver (no configuration software required)
  • 2 GB microSD card for firmware, trend logging, event logging and alarming
  • With BACnet Broadcast Managment Device (BBMD) function
  • Foreign devices are supported
  • Firmware is updated using the webserver

Technical data

  • Dimensions (B × H × T): 65 × 15 × 90 mm
  • Supply voltage (from the controller TCU3 or adapter module TAM): 5 V DC
  • Acceptable temperature range for storage: –10 to 70 °C
  • Acceptable temperature range for operation: 10 to 50 °C
  • Maximum humidity, non-condensing, for storage and operation: <90 %
  • Protection level: IP 20
  • Persistent data store for firmware, logging objects and help files: 2 GB

Data points for a single controller

  • Volume flow rate actual and setpoint values
  • Damper blade position
  • Operating mode
  • Alarm/status messages
  • Total supply air and total extract air actual values (room), and all individual volume flow rate values
  • Evaluated damper blade positions for all controllers in a room
  • Number of controllers
  • Integration of volume flows


Additional data points for a fume cupboard controller

  • Operating mode default setting for the fume cupboard controller equipped with the expansion module
  • Selection of priority for operating mode default setting
  • Face velocity actual value and setpoint value (only for fume cupboard controllers with face velocity transducer, equipment function FH-VS)

Data points for an EASYLAB room

  • Operating mode default setting for the room: Just one data point is required to set the default operating mode for all controllers in a room
  • Selection of priority for operating mode default setting (central BMS or room)
  • Room operating mode
  • Volume flow rate setpoint change (by the central BMS, for example) for an external temperature or differential pressure control
  • Setpoint value switching for differential pressure control: Switching between two differential pressure setpoint values
  • Total supply air and total extract air actual values (room), and all individual volume flow rate values
  • Evaluated damper blade positions for all controllers in a room
  • Room differential pressure actual and setpoint values
  • Room pressure alarm
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs
  • Configurable consolidated alarm (operating statuses, hardware faults)

BACnet Interoperability Building Blocks Supported

  • Data Sharing-ReadProperty-B: DS-RP-B
  • Data Sharing-ReadProperty-Multiple-B: DS-RPM-B
  • Data Sharing-WriteProperty-B: DS-WP-B
  • Data Sharing-WritePropertyMultiple-B: DS-WPM-B
  • Data Sharing-COV-B: DS-COV-B


  • Alarm and Event-Notification-Internal-B: AE-N-I-B
  • Alarm and Event-Acknowledge-B: AE-ACK-B
  • Alarm and Event-Alarm-Summary-B: AE-ASUM-B
  • Alarm and Event-Enrollment-Summary-B: AE-ESUM-B
  • Alarm and Event-Event-Information-B: AE-INFO-B
  • Alarm and Event-Event-Log-Internal-B: AE-EL-I-B


  • Scheduling-Weekly-Schedule-Internal-B: SCHED-WS-I-B


  • Trending-Viewing-and-Modifying-Trends-Internal-B: T-VMT-I-B
  • Trending-Automatic-Trend-Retrieval-B: T-ATR-B


  • Device Management-Dynamic Device Binding-A: DM-DDB-A
  • Device Management-Dynamic Device Binding-B: DM-DDB-B
  • Device Management-Dynamic Object Binding-B: DM-DOB-B
  • Device Management-DeviceCommunicationControl-B: DM-DCC-B
  • Device Management-TimeSynchronization-B: DM-TS-B
  • Device Management-UTCTimeSynchronization-B: DM-UTC-B
  • Device Management-ReinitializeDevice-B: DM-RD-B
  • Device Management-List Manipulation-B: DM-LM-B
  • Device Management-Restart-B: DM-R-B

  • Any attachments are to be defined with the order code of the VAV terminal unit.
  • Retrofit possible

 

Single controller, EASYLAB room, BACnet interface, Modbus interface, Product details

  • Single controller
  • EASYLAB room
  • BACnet interface
  • Modbus interface
  • Product details
LonWorks, BACnet or Modbus interface on a single controller, e.g. fume cupboad controller 00183220_0
BMS central building management system
RMF Controller with active room management function
ROM Room operating mode, from the room control panel
IOM Individual operating mode, transmitted via BACnet or Modbus interface


Single controller

Interface for one EASYLAB controller

  • Local data interface for a fume cupboard controller, supply air controller, extract air controller, or adapter module TAM


Data points for a single controller

  • Volume flow rate actual and setpoint values
  • Damper blade position
  • Operating mode
  • Alarm/status messages
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs


Additional data points for a fume cupboard controller

  • Operating mode default setting for the fume cupboard controller equipped with the expansion module
  • Selection of priority for operating mode default setting
  • Face velocity actual value and setpoint value (only for fume cupboard controllers with face velocity transducer, equipment function FH-VS)

LonWorks, BACnet or Modbus interface for an EASYLAB room, e.g. on a room controller with active room management function 00183226_0
BMS central building management system
RMF Controller with active room management function
ROM Room operating mode, from the controller with room management function


EASYLAB room

Interface for one EASYLAB room

  • Local data interface for a TCU3 room controller (supply air or extract air) or TAM adapter module with active room management function
  • Room management function reduces the required number of network data points and hence the commissioning costs
  • Transmission of local data for the single controller and for the room


Data points for an EASYLAB room controller

  • Operating mode default setting for the room: Just one data point is required to set the default operating mode for all controllers in a room
  • Selection of priority for operating mode default setting (central BMS or room)
  • Room operating mode
  • Volume flow rate setpoint change (by the central BMS, for example) for an external temperature or differential pressure control
  • Setpoint value switching for differential pressure control: Switching between two differential pressure setpoint values
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Room differential pressure actual and setpoint values
  • Room pressure alarm
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs
  • Configurable consolidated alarm (operating statuses, hardware faults)
  • Control input signal for sun protection/blinds (to be provided by others)

BACnet interface

Application

EM-IP supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the BACnet protocol has been selected:


  • Native BACnet, i.e. the BACnet interface is implemented on the field module (EASYLAB volume flow controller)
  • External hardware components such as physical gateways are not required
  • BACnet interface documentation includes the following documents: Protocol Implementation Conformance Statement (PICS), BACnet Interoperability Building Blocks Supported (BIBBS), as well as a description of the device object and the supported objects

BACnet PICS (extract)

Category Data

Date

2011-07-20

Vendor name/Vendor identifier

TROX GmbH/329

Product name/Model no.

EM-IP/EM-IP

Application/Firmware Revison

1.0/1.0

BACnet Protocol Revision

7

Standardized Device Profile

BACnet Application Specific Controller (B-ASC)

Interoperability Building Blocks Supported

DS-RP-B, DS-WP-B, DS-RPM-B, DS-WPM-B, DS-COVU-B, AE-NI- B, AE-ACK-B, AE-ASUM-B, AE-ESUM-B, AE-INFO-B, AE-EL-I-B, SCHEDWS-I-B, T-VMT-I-B, T-ATR-B, DM-DDB-A, DM-DDB-B, DM-DOB_B, DM-DCC-B, DM-TS-B, DMUTC- B, DM-RD-B, DM-LM-B, DM-R-B

Segmentation Capability

No

Data Link Layer Options

TCP-IP 10/100 Mbit

Device Address Binding

No

Network Security Options

No

Character Sets Supported

ISO 10646 (UTF-8)


DeviceObject

Property Value Access

Object identifier

Device instance; default = 17493

WR, RD; E

Device name

Default = "Device17493"; project-specific description can be entered, 62 characters max.

WR, RD; E

Object type

Device (8)

RD

System_Status

OPERATIONAL (0)

RD

Vendor_Name

TROX GmbH

RD

Vendor_Identifier

329

RD

Model_Name

EM-IP

RD

Description

Default = “TROX EM-IP”; description can be entered, 126 characters max.

WR, RD; E

Location

Default = ""; description can be entered, 62 characters max.

WR, RD; E

Firmware_Revision

2.0

RD

Application_Software_Version

V2

RD

Protocol_Version

1

RD

Protocol_Revision

7

RD

Protocol Services Supported

Who-is, Who-has, Read-Property, Write-Property, Device-communication-control, Reinitialize-device

RD

Protocol_Object_Types_Supported

DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTISTATE_VALUE

RD

Object_List

EASYLAB: device, analog-value 1…31, binary-value 1…30, multistate-value 1…8

RD

Max_ADPU_Length_Accepted

1024

RD

Segmentation_Supported

NO_SEGMENTATION (3)

RD

APDU_Timeout

5000

RD

Number_Of_APDU_Retries

3

RD

Device_Address_Binding

RD

Database_Revision

0

RD


Multistate Value Objects

Instance Designation Unit Access
Instance Designation TCU3 TAM Access
Instance Designation Available with equipment function Access
Instance Designation FH RR RR RMF EC, SC TAM TAM RMF Access

MV-2

Mode


x



x

WR, RD

MV-3

ModeAct

x

x

x

x



RD

MV-4

RoomModeAct

x


x



x

RD

MV-5

SwitchPos

x






RD

MV-6

Sunblind

x


x



x

WR, RD

MV-7

SC_SetLockHighPrio







WR, RD

MV-8

SC_GetLockHighPrio







RD

MV-9

SC_SetPos







RD

MV-10

SC_GetPos







RD

MV-11

DampPosMaxState_FH

x

x

x

x

x

x

RD

MV-12

DampPosMinState_FH

x

x

x

x

x

x

RD

MV-13

DampPosMaxState_RE

x

x

x

x

x

x

RD

MV-14

DampPosMinState_RE

x

x

x

x

x

x

RD

MV-15

DampPosMaxState_TE

x

x

x

x

x

x

RD

MV-16

DampPosMinState_TE

x

x

x

x

x

x

RD

MV-17

DampPosMaxState_RS

x

x

x

x

x

x

RD

MV-18

DampPosMinState_RS

x

x

x

x

x

x

RD

MV-26

DampPosMaxState_EC

x

x

x

x

x

x

RD

MV-27

DampPosMinState_EC

x

x

x

x

x

x

RD

MV-28

DampPosMaxState_SC

x

x

x

x

x

x

RD

MV-29

DampPosMinState_SC

x

x

x

x

x

x

RD

MV-30

DampPosMaxState_TS

x

x

x

x

x

x

RD

MV-31

DampPosMinState_TS

x

x

x

x

x

x

RD

MV-32

DampPosMaxState_VE







RD

MV-33

DampPosMinState_VE







RD

MV-34

DampPosMaxState_VS







RD

MV-35

DampPosMinState_VS







RD

MV-36

DampPosMaxState_PKE







RD

MV-37

DampPosMinState_PKE







RD

MV-38

DampPosMaxState_PKS







RD

MV-39

DampPosMinState_PKS







RD

¹ only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Analogue Value Objects

Instance Designation Unit Access
Instance Designation Unit TCU3 TAM Access
Instance Designation Unit Available with equipment function Access
Instance Designation Unit FH RR RR RMF EC, SC TAM TAM RMF Access

AV-1

VolflowSet

l/s (87)

x

x

x

x



RD

AV-2

VolflowAct

l/s (87)

x

x

x

x



RD

AV-3

VolTotalExh

l/s (87)

x

x

x

x

x

x

RD

AV-4

VolTotalSup

l/s (87)

x

x

x

x

x

x

RD

AV-5

PressSet

Pa (53)



x



x

RD

AV-6

PressAct

Pa (53)



x



x

RD

AV-7

VelocitySet

m/s (74)

x






RD

AV-8

VelocityAct

m/s (74)

x






RD

AV-9

WireSensorPos

percent (98)

x






RD

AV-10

DampPos

percent (98)

x

x

x

x



RD

AV-11

DampPosMax_FH

percent (98)

x

x

x

x

x

x

RD

AV-12

DampPosMin_FH

percent (98)

x

x

x

x

x

x

RD

AV-13

DampPosMax_RE

percent (98)

x

x

x

x

x

x

RD

AV-14

DampPosMin_RE

percent (98)

x

x

x

x

x

x

RD

AV-15

DampPosMax_TE

percent (98)

x

x

x

x

x

x

RD

AV-16

DampPosMin_TE

percent (98)

x

x

x

x

x

x

RD

AV-17

DampPosMax_RS

percent (98)

x

x

x

x

x

x

RD

AV-18

DampPosMin_RS

percent (98)

x

x

x

x

x

x

RD

AV-19

VolOffset_T

percent (98)



x



x

WR, RD

AV-20

VolOffset_P

percent (98)



x



x

WR, RD

AV-21

SystemDevices

no units (95)

x

x

x

x

x

x

RD

AV-22

VolflowExh

l/s (87)

x

x

x


x

x

WR, RD

AV-23

VolflowSup

l/s (87)

x

x

x


x

x

WR, RD

AV-24

SC_SetPos

percent (98)







WR, RD

AV-25

SC_GetPos

percent (98)







RD

AV-26

DampPosMax_EC

percent (98)

x

x

x

x

x

x

RD

AV-27

DampPosMin_EC

percent (98)

x

x

x

x

x

x

RD

AV-28

DampPosMax_SC

percent (98)

x

x

x

x

x

x

RD

AV-29

DampPosMin_SC

percent (98)

x

x

x

x

x

x

RD

AV-30

DampPosMax_TS

percent (98)

x

x

x

x

x

x

RD

AV-31

DampPosMin_TS

percent (98)

x

x

x

x

x

x

RD

AV-32

Device_ID_0

no units (95)

x

x

x

x

x

x

RD

AV-33

Device_ID_1

no units (95)

x

x

x

x

x

x

RD

AV-34

Device_ID_2

no units (95)

x

x

x

x

x

x

RD

AV-35

Device_ID_3

no units (95)

x

x

x

x

x

x

RD

AV-36

Device_ID_4

no units (95)

x

x

x

x

x

x

RD

AV-37

Device_ID_5

no units (95)

x

x

x

x

x

x

RD

AV-38

Device_ID_6

no units (95)

x

x

x

x

x

x

RD

AV-39

Device_ID_7

no units (95)

x

x

x

x

x

x

RD

AV-40

Device_ID_8

no units (95)

x

x

x

x

x

x

RD

AV-41

Device_ID_9

no units (95)

x

x

x

x

x

x

RD

AV-42

Device_ID_10

no units (95)

x

x

x

x

x

x

RD

AV-43

Device_ID_11

no units (95)

x

x

x

x

x

x

RD

AV-44

Device_ID_12

no units (95)

x

x

x

x

x

x

RD

AV-45

Device_ID_13

no units (95)

x

x

x

x

x

x

RD

AV-46

Device_ID_14

no units (95)

x

x

x

x

x

x

RD

AV-47

Device_ID_15

no units (95)

x

x

x

x

x

x

RD

AV-48

Device_ID_16

no units (95)

x

x

x

x

x

x

RD

AV-49

Device_ID_17

no units (95)

x

x

x

x

x

x

RD

AV-50

Device_ID_18

no units (95)

x

x

x

x

x

x

RD

AV-51

Device_ID_19

no units (95)

x

x

x

x

x

x

RD

AV-52

Device_ID_20

no units (95)

x

x

x

x

x

x

RD

AV-53

Device_ID_21

no units (95)

x

x

x

x

x

x

RD

AV-54

Device_ID_22

no units (95)

x

x

x

x

x

x

RD

AV-55

Device_ID_23

no units (95)

x

x

x

x

x

x

RD

AV-56

VolflowAct_0

l/s (87)

x

x

x

x

x

x

RD

AV-57

VolflowAct_1

l/s (87)

x

x

x

x

x

x

RD

AV-58

VolflowAct_2

l/s (87)

x

x

x

x

x

x

RD

AV-59

VolflowAct_3

l/s (87)

x

x

x

x

x

x

RD

AV-60

VolflowAct_4

l/s (87)

x

x

x

x

x

x

RD

AV-61

VolflowAct_5

l/s (87)

x

x

x

x

x

x

RD

AV-62

VolflowAct_6

l/s (87)

x

x

x

x

x

x

RD

AV-63

VolflowAct_7

l/s (87)

x

x

x

x

x

x

RD

AV-64

VolflowAct_8

l/s (87)

x

x

x

x

x

x

RD

AV-65

VolflowAct_9

l/s (87)

x

x

x

x

x

x

RD

AV-66

VolflowAct_10

l/s (87)

x

x

x

x

x

x

RD

AV-67

VolflowAct_11

l/s (87)

x

x

x

x

x

x

RD

AV-68

VolflowAct_12

l/s (87)

x

x

x

x

x

x

RD

AV-69

VolflowAct_13

l/s (87)

x

x

x

x

x

x

RD

AV-70

VolflowAct_14

l/s (87)

x

x

x

x

x

x

RD

AV-71

VolflowAct_15

l/s (87)

x

x

x

x

x

x

RD

AV-72

VolflowAct_16

l/s (87)

x

x

x

x

x

x

RD

AV-73

VolflowAct_17

l/s (87)

x

x

x

x

x

x

RD

AV-74

VolflowAct_18

l/s (87)

x

x

x

x

x

x

RD

AV-75

VolflowAct_19

l/s (87)

x

x

x

x

x

x

RD

AV-76

VolflowAct_20

l/s (87)

x

x

x

x

x

x

RD

AV-77

VolflowAct_21

l/s (87)

x

x

x

x

x

x

RD

AV-78

VolflowAct_22

l/s (87)

x

x

x

x

x

x

RD

AV-79

VolflowAct_23

l/s (87)

x

x

x

x

x

x

RD

AV-80

VolflowSet_R

l/s (87)







WR, RD

AV-81

PressSet

Pa (53)







WR, RD

AV-82

Volt_AI2

volt (5)

x

x

x

x

x

x

RD

AV-83

Volt_AI3

volt (5)

x

x

x

x

x

x

RD

AV-84

Volt_AO2

volt (5)

x

x

x

x

x

x

WR, RD

AV-85

DampPosMaxValue_VE

percent (98)







RD

AV-86

DampPosMinValue_VE

percent (98)







RD

AV-87

DampPosMaxValue_VS

percent (98)







RD

AV-88

DampPosMinValue_VS

percent (98)







RD

AV-89

DampPosMaxValue_PKE

percent (98)







RD

AV-90

DampPosMinValue_PKE

percent (98)







RD

AV-91

DampPosMaxValue_PKS

percent (98)







RD

AV-92

DampPosMinValue_PKS

percent (98)







RD

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Binary Value Objects

Instance Designation Unit Access
Instance Designation TCU3 TAM Access
Instance Designation Available with equipment function Access
Instance Designation FH RR RR RMF EC, SC TAM TAM RMF Access

BV-1

LocalAlarm (COVU)

x

x

x

x

x

x

RD

BV-2

SummaryAlarm (COVU)



x



x

RD

BV-3

PressAlarm (COVU)



x



x

RD

BV-4

ManOP_Disable


x



x

WR, RD

BV-5

PressSetSel



x



x

WR, RD

BV-6

DI1

x

x

x

x

x

x

RD

BV-7

DI2

x

x

x

x

x

x

RD

BV-8

DI3

x

x

x

x

x

x

RD

BV-9

DI4

x

x

x

x

x

x

RD

BV-10

DI5

x

x

x

x

x

x

RD

BV-11

DI6

x

x

x

x

x

x

RD

BV-12

DO1

x

x

x

x

x

x

RD

BV-13

DO2

x

x

x

x

x

x

RD

BV-14

DO3

x

x

x

x

x

x

RD

BV-15

DO4

x

x

x

x

x

x

RD

BV-16

DO5

x

x

x

x

x

x

RD

BV-17

DO6

x

x

x

x

x

x

RD

BV-18

SC_Alarm







RD

BV-19

DO1_Set

x

x

x

x

x

x

WR, RD

BV-20

DO2_Set

x

x

x

x

x

x

WR, RD

BV-21

DO3_Set

x

x

x

x

x

x

WR, RD

BV-22

DO4_Set

x

x

x

x

x

x

WR, RD

BV-23

DO5_Set

x

x

x

x

x

x

WR, RD

BV-24

DO6_Set

x

x

x

x

x

x

WR, RD

BV-25

DO1_SetByLocal

x

x

x

x

x

x

RD

BV-26

DO2_SetByLocal

x

x

x

x

x

x

RD

BV-27

DO3_SetByLocal

x

x

x

x

x

x

RD

BV-28

DO4_SetByLocal

x

x

x

x

x

x

RD

BV-29

DO5_SetByLocal

x

x

x

x

x

x

RD

BV-30

DO6_SetByLocal

x

x

x

x

x

x

RD

BV-31

LocalAlarm_0

x

x

x

x

x

x

RD

BV-32

LocalAlarm_1

x

x

x

x

x

x

RD

BV-33

LocalAlarm_2

x

x

x

x

x

x

RD

BV-34

LocalAlarm_3

x

x

x

x

x

x

RD

BV-35

LocalAlarm_4

x

x

x

x

x

x

RD

BV-36

LocalAlarm_5

x

x

x

x

x

x

RD

BV-37

LocalAlarm_6

x

x

x

x

x

x

RD

BV-38

LocalAlarm_7

x

x

x

x

x

x

RD

BV-39

LocalAlarm_8

x

x

x

x

x

x

RD

BV-40

LocalAlarm_9

x

x

x

x

x

x

RD

BV-41

LocalAlarm_10

x

x

x

x

x

x

RD

BV-42

LocalAlarm_11

x

x

x

x

x

x

RD

BV-43

LocalAlarm_12

x

x

x

x

x

x

RD

BV-44

LocalAlarm_13

x

x

x

x

x

x

RD

BV-45

LocalAlarm_14

x

x

x

x

x

x

RD

BV-46

LocalAlarm_15

x

x

x

x

x

x

RD

BV-47

LocalAlarm_16

x

x

x

x

x

x

RD

BV-48

LocalAlarm_17

x

x

x

x

x

x

RD

BV-49

LocalAlarm_18

x

x

x

x

x

x

RD

BV-50

LocalAlarm_19

x

x

x

x

x

x

RD

BV-51

LocalAlarm_20

x

x

x

x

x

x

RD

BV-52

LocalAlarm_21

x

x

x

x

x

x

RD

BV-53

LocalAlarm_22

x

x

x

x

x

x

RD

BV-54

LocalAlarm_23

x

x

x

x

x

x

RD

¹ only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Modbus interface

Application

EM-IP supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the Modbus protocol has been selected:


  • Modbus is an open serial master-slave communication protocol which has become a de facto standard for the industry
  • The master (e.g. central BMS) can address a number of slaves (EASYLAB volume flow controllers) and use Modbus functions to request information from individual data points
  • Data access is based on numbered data registers which the master has to define in order to request data using Modbus functions
  • The slave responds by either returning the requested information or an exception code (error)
  • Example: The Read Holding Registers function (register no. 3) returns the volume flow rate actual value of the addressed controller
  • General information for a Modbus device can be read out using the Read Device Identification function

Modbus functions

Function no. Designation Meaning

1 (0x01)

Read Coils

Read states of 1 to 8 bits according to bit list

3 (0x03)

Read Holding Registers

Read several consecutive registers

4 (0x04)

Read Input Registers

Read several consecutive registers

5 (0x05)

Write Single Coil

Write state of a single bit

6 (0x06)

Write Single Register

Write single register


Exception codes

Codes Designation Meaning

1

Illegal Function Code

Unknown function or subfunction code

2

Illegal Data Address

Invalid register address

3

Illegal Data Value

Inconsistent coding for number of registers/bytes, data value

Exception codes (error codes) are returned in case of invalid function or register access.


Bit list for ReadCoil/WriteSingleCoil functions

Bit Unit Access
Bit TCU3 TAM Access
Bit Available with equipment function Access
No. Designation FH RR RR RMF EC, SC TAM TAM RMF Access

0

ManOP_Disable


x



x

WR, RD

1

PressSetSel



x



x

WR, RD

2

Local Alarm

x

x

x

x

x

x

RD

3

SummaryAlarm



x



x

RD

4

PressAlarm



x



x

RD

5

SC_SetlockHighPrio







WR, RD

6

SC_GetLockHighPrio







RD

7

SC_Alarm







RD

8

LocalAlarm_0

x

x

x

x

x

x

RD

9

LocalAlarm_1

x

x

x

x

x

x

RD

10

LocalAlarm_2

x

x

x

x

x

x

RD

11

LocalAlarm_3

x

x

x

x

x

x

RD

12

LocalAlarm_4

x

x

x

x

x

x

RD

13

LocalAlarm_5

x

x

x

x

x

x

RD

14

LocalAlarm_6

x

x

x

x

x

x

RD

15

LocalAlarm_7

x

x

x

x

x

x

RD

16

LocalAlarm_8

x

x

x

x

x

x

RD

17

LocalAlarm_9

x

x

x

x

x

x

RD

18

LocalAlarm_10

x

x

x

x

x

x

RD

19

LocalAlarm_11

x

x

x

x

x

x

RD

20

LocalAlarm_12

x

x

x

x

x

x

RD

21

LocalAlarm_13

x

x

x

x

x

x

RD

22

LocalAlarm_14

x

x

x

x

x

x

RD

23

LocalAlarm_15

x

x

x

x

x

x

RD

24

LocalAlarm_16

x

x

x

x

x

x

RD

25

LocalAlarm_17

x

x

x

x

x

x

RD

26

LocalAlarm_18

x

x

x

x

x

x

RD

27

LocalAlarm_19

x

x

x

x

x

x

RD

28

LocalAlarm_20

x

x

x

x

x

x

RD

29

LocalAlarm_21

x

x

x

x

x

x

RD

30

LocalAlarm_22

x

x

x

x

x

x

RD

31

LocalAlarm_23

x

x

x

x

x

x

RD

¹ only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Register list for Read***Registers and Write***Registers functions

Register Unit Access
Register TCU3 TAM Access
Register Available with equipment function Access
No. Designation FH RR RR RMF EC, SC TAM TAM RMF Access

0

Mode

 

x



x

WR, RD

1

ManOP_Disable

 

x



x

WR, RD

2

ModeAct

x

x

x

x



RD

3

VolflowAct

x

x

x

x



RD

4

VolflowSet

x

x

x

x



RD

5

VelocityAct

x

 





RD

6

VelocitySet

x

 





RD

7

VolTotalExh

x

x

x

x

x

x

RD

8

VolTotalSup

x

x

x

x

x

x

RD

9

VolOffset_T

 

 

x



x

WR, RD

10

VolOffset_P

 

 

x



x

WR, RD

11

PressAct

 

 

x



x

RD

12

PressSet

 

 

x



x

RD

13

PressSetSel

 

 

x



x

WR, RD

14

DampPos

x

x

x

x



RD

15

DampPosMax_FH - Value

x

x

x

x

x

x

RD

16

DampPosMax_FH - Status

x

x

x

x

x

x

RD

17

DampPosMin_FH - Value

x

x

x

x

x

x

RD

18

DampPosMin_FH - Status

x

x

x

x

x

x

RD

19

DampPosMax_RE - Value

x

x

x

x

x

x

RD

20

DampPosMax_RE - Status

x

x

x

x

x

x

RD

21

DampPosMin_RE - Value

x

x

x

x

x

x

RD

22

DampPosMin_RE - Status

x

x

x

x

x

x

RD

23

DampPosMax_TE - Value

x

x

x

x

x

x

RD

24

DampPosMax_TE - Status

x

x

x

x

x

x

RD

25

DampPosMin_TE - Value

x

x

x

x

x

x

RD

26

DampPosMin_TE - Status

x

x

x

x

x

x

RD

27

DampPosMax_RS - Value

x

x

x

x

x

x

RD

28

DampPosMax_RS - Status

x

x

x

x

x

x

RD

29

DampPosMin_RS - Value

x

x

x

x

x

x

RD

30

DampPosMin_RS - Status

x

x

x

x

x

x

RD

31

LocalAlarm

x

x

x

x

x

x

RD

32

SummaryAlarm

 

 

x



x

RD

33

PressAlarm

 

 

x



x

RD

34

WireSensorPos

x

 





RD

35

SwitchPos

x

 





RD

36

RoomModeAct

 

 

x



x

RD

37

SystemDevices

x

x

x

x

x

x

RD

38

SunBlind

 

 

x



x

WR, RD

39

StateDI

x

x

x

x

x

x

RD

40

StateDO

x

x

x

x

x

x

RD

41

VolflowExh

x

x

x


x

x

WR, RD

42

VolflowSup

x

x

x


x

x

WR, RD

43

SC_SetLockHighPrio







WR, RD

44

SC_GetLockHighPrio







RD

45

SC_SetPos - Value







WR, RD

46

SC_SetPos - Status







WR, RD

47

SC_GetPos







RD

48

SC_Alarm







RD

49

DampPosMax_EC - Value

x

x

x

x

x

x

RD

50

DampPosMax_EC - Status

x

x

x

x

x

x

RD

51

DampPosMin_EC - Value

x

x

x

x

x

x

RD

52

DampPosMin_EC - Status

x

x

x

x

x

x

RD

53

DampPosMax_SC - Value

x

x

x

x

x

x

RD

54

DampPosMax_SC - Status

x

x

x

x

x

x

RD

55

DampPosMin_SC - Value

x

x

x

x

x

x

RD

56

DampPosMin_SC - Status

x

x

x

x

x

x

RD

57

DampPosMax_TS - Value

x

x

x

x

x

x

RD

58

DampPosMax_TS - Status

x

x

x

x

x

x

RD

59

DampPosMin_TS - Value

x

x

x

x

x

x

RD

60

DampPosMin_TS - Status

x

x

x

x

x

x

RD

61

DO_Set

x

x

x

x

x

x

WR, RD

62

DO_SetByLocal

x

x

x

x

x

x

RD

63

LocalAlarm_* (0 – 7)

x

x

x

x

x

x

RD

64

LocalAlarm_* (8 – 15)

x

x

x

x

x

x

RD

65

LocalAlarm_* (16 – 23)

x

x

x

x

x

x

RD

66

Device_ID_0

x

x

x

x

x

x

RD

67

Device_ID_1

x

x

x

x

x

x

RD

68

Device_ID_2

x

x

x

x

x

x

RD

69

Device_ID_3

x

x

x

x

x

x

RD

70

Device_ID_4

x

x

x

x

x

x

RD

71

Device_ID_5

x

x

x

x

x

x

RD

72

Device_ID_6

x

x

x

x

x

x

RD

73

Device_ID_7

x

x

x

x

x

x

RD

74

Device_ID_8

x

x

x

x

x

x

RD

75

Device_ID_9

x

x

x

x

x

x

RD

76

Device_ID_10

x

x

x

x

x

x

RD

77

Device_ID_11

x

x

x

x

x

x

RD

78

Device_ID_12

x

x

x

x

x

x

RD

79

Device_ID_13

x

x

x

x

x

x

RD

80

Device_ID_14

x

x

x

x

x

x

RD

81

Device_ID_15

x

x

x

x

x

x

RD

82

Device_ID_16

x

x

x

x

x

x

RD

83

Device_ID_17

x

x

x

x

x

x

RD

84

Device_ID_18

x

x

x

x

x

x

RD

85

Device_ID_19

x

x

x

x

x

x

RD

86

Device_ID_20

x

x

x

x

x

x

RD

87

Device_ID_21

x

x

x

x

x

x

RD

88

Device_ID_22

x

x

x

x

x

x

RD

89

Device_ID_23

x

x

x

x

x

x

RD

90

VolflowAct_0

x

x

x

x

x

x

RD

91

VolflowAct_1

x

x

x

x

x

x

RD

92

VolflowAct_2

x

x

x

x

x

x

RD

93

VolflowAct_3

x

x

x

x

x

x

RD

94

VolflowAct_4

x

x

x

x

x

x

RD

95

VolflowAct_5

x

x

x

x

x

x

RD

96

VolflowAct_6

x

x

x

x

x

x

RD

97

VolflowAct_7

x

x

x

x

x

x

RD

98

VolflowAct_8

x

x

x

x

x

x

RD

99

VolflowAct_9

x

x

x

x

x

x

RD

100

VolflowAct_10

x

x

x

x

x

x

RD

101

VolflowAct_11

x

x

x

x

x

x

RD

102

VolflowAct_12

x

x

x

x

x

x

RD

103

VolflowAct_13

x

x

x

x

x

x

RD

104

VolflowAct_14

x

x

x

x

x

x

RD

105

VolflowAct_15

x

x

x

x

x

x

RD

106

VolflowAct_16

x

x

x

x

x

x

RD

107

VolflowAct_17

x

x

x

x

x

x

RD

108

VolflowAct_18

x

x

x

x

x

x

RD

109

VolflowAct_19

x

x

x

x

x

x

RD

110

VolflowAct_20

x

x

x

x

x

x

RD

111

VolflowAct_21

x

x

x

x

x

x

RD

112

VolflowAct_22

x

x

x

x

x

x

RD

113

VolflowAct_23

x

x

x

x

x

x

RD

114

VolflowSet_R







WR, RD

115

PressSet







WR, RD

116

Volt_AI2

x

x

x

x

x

x

RD

117

Volt_AI3

x

x

x

x

x

x

RD

118

Volt_AO2

x

x

x

x

x

x

WR, RD

119

DampPosMax_VE - Value







RD

120

DampPosMax_VE - Status







RD

121

DampPosMin_VE - Value







RD

122

DampPosMin_VE - Status







RD

123

DampPosMax_VS - Value







RD

124

DampPosMax_VS - Status







RD

125

DampPosMin_VS - Value







RD

126

DampPosMin_VS - Status







RD

127

DampPosMax_PKE - Value







RD

128

DampPosMax_PKE - Status







RD

129

DampPosMin_PKE - Value







RD

130

DampPosMin_PKE - Status







RD

131

DampPosMax_PKS - Value







RD

132

DampPosMax_PKS - Status







RD

133

DampPosMin_PKS - Value







RD

134

DampPosMin_PKS - Status







RD

¹ only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Data points – detailed description

The following is a detailed description of the information that each data point provides; input variables and output variables are described separately:

  • Name of data point
  • Access as viewed from the central BMS
  • WR – Defaults for the volume flow controller or room, from the central BMS
  • RD – Data provided by the volume flow controller or room
  • List of volume flow controller equipment functions for which the variable is available
  • Unit of measure (applies only to BACnet objects of type Analogue Value Object)
  • Function and special functional values with their meaning
  • Access to the data point using a BACnet object or Modbus register

Input variables

Mode

BMS access: WR RD

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • FH: Operating mode default setting for a single fume cupboard controller, only with individual operating mode default setting (stand-alone operation)
  • RMF: Operating mode default setting for the entire EASYLAB room
  • The valid binding of the input variable results in a valid operating mode default setting via BACnet or Modbus
  • The invalid binding of an input variable or failure to set an operating mode default results in no operating mode default being set for the EASYLAB controller or room
  • Which operating mode is then used depends on the default options available on the controller


Functional values (BACnet / Modbus)

  • 1/0 = No default: The central BMS does not default an operating mode for the controller or room. The operating mode is set locally, e.g. on the room control panel, on the fume cupboard control panel, or using switch contacts. If the operating mode is not set locally, the controller activates standard mode.
  • 2/1 = Standard mode: Normal operation in the daytime (in Germany: usually according to DIN 1946, part 7, 25 m³/h extract air per m² main useful floor area)
  • 3/2 = Reduced operation: Low mode in comparison to standard mode, e.g. as a night-time setback
  • 4/3 = Increased operation: High mode in comparison to standard mode, e.g. in an emergency
  • 5/4 = Shut-off: Shut-off of the volume flow controller, e.g. to save energy at night or to shut down the system
  • 6/5 = OPEN position: Open position of the volume flow controller

Data point

  • BACnet: Multistate Value Object – Instance MV-2
  • Modbus: Register 0

Sunblind

BMS access: WR RD

Equipment functions: RR with RMF, TAM with RMF

from firmware version EM-BAC-MOD 2.0 and TCU3, TAM 3.0


Function

  • Control input signal for sun protection/blinds, connected to the controller or adapter module
  • Switch outputs DO5 and DO6 will be used
  • This BACnet or Modbus default overrides any other defaults from the local room control panel

Data point

BACnet: Multistate Value Object – Instance MV-6

  • 1 = No default
  • 2 = Close blinds (activate switch output DO6)
  • 3 = Open blinds (activate switch output DO5)

Modbus: Register 38

  • 0 = Close blinds
  • 1 = Open blinds
  • 0xFF = No default

SC_SetLockHighPrio

BMS access: WR RD


Function

  • Close and lock sash, high priority

Data point

  • BACnet: Multistate Value Object - Instance MV-7
  • Modbus: Bit list - bit 5 or register 43

VolOffset_T

BMS access: WR RD

Equipment functions: RR with RMF, TAM with RMF

Unit/value range: BACnet: percentage value in 0.5 % increments; Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Signalling of an external volume flow rate setpoint change, e.g. for adjusting the room air change rate or for external temperature control
  • The change signal is transferred as a percentage value of a volume flow rate change range that has been configured in the controller

Data point

  • BACnet: Analog Value Object – Instance AV-19
  • Modbus: Register 9

VolOffset_P

BMS access: WR RD

Equipment functions: RR with RMF, TAM with RMF

Unit/value range: BACnet: percentage value in 0.5 % increments; Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Signalling of a flow rate setpoint change for external differential pressure control
  • The change signal is transferred as a percentage value of a volume flow rate change range that has been configured in the controller

Data point

  • BACnet: Analog Value Object – Instance AV-20
  • Modbus: Register 10

VolflowExh

BMS access: WR RD

Equipment functions: FH, RR, RR with RMF, TAM, TAM with RMF

Unit: l/s

from firmware version EM-BAC-MOD 2.0 and TCU3, TAM 3.0


Function

  • Integration of an extract air flow into the room balance of the EASYLAB system
  • This default volume flow is considered for all volume flow calculations (balance and setpoint values)

Data point

  • BACnet: Analog Value Object – Instance AV-22
  • Modbus: Register 41

VolflowSup

BMS access: WR RD

Equipment functions: FH, RR, RR with RMF, TAM, TAM with RMF

Unit: l/s

from firmware version EM-BAC-MOD 2.0 and TCU3, TAM 3.0


Function

  • Integration of a supply air flow into the room balance of the EASYLAB system
  • This default volume flow is considered for all volume flow calculations (balance and setpoint values)

Data point

  • BACnet: Analog Value Object – Instance AV-23
  • Modbus: Register 42

SC_SetPos

BMS access: WR RD


Function

  • Default setting from central BMS: Close sash

Data point

  • BACnet: Analogue Value Object - Instance AV-24
  • Modbus: Register 45 (value) and register 46 (event state)

VolflowSet_R

BMS access: WR RD

Unit: l/s

from firmware version EM-BAC-MOD 4.0, EM-IP 2.0


Function

  • Default setting of volume flow rate setpoint (room), only for standard mode

Data point

  • BACnet: Analog Value Object – Instance AV-80
  • Modbus: Register 114

PressSet

BMS access: WR RD

Unit: Pa

from firmware version EM-BAC-MOD 4.0, EM-IP 2.0


Function

  • Local default setting of room pressure or duct pressure setpoint value

Data point

  • BACnet: Analog Value Object – Instance AV-81
  • Modbus: Register 115

Volt_AO2

BMS access: WR RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: V DC

from firmware version EM-BAC-MOD 4.0, EM-IP 2.0 and TCU3, TAM 7.0


Function

  • Default setting of voltage for analogue output AO2
  • 0 – 10 V DC, in increments of 0.1 V

Data point

  • BACnet: Analog Value Object – Instance AV-84
  • Modbus: Register 118

ManOp_Disable

BMS access: WR RD

Equipment functions: FH, RR with RMF, TAM with RMF


Function

  • Enabling/disabling manual control
  • Upon enabling manual control the corresponding symbol appears on the control panel
  • For further information on manual control please refer to the EASYLAB design manual.
  • FH: Operating mode default setting for a fume cupboard controller, only with individual operating mode default setting (stand-alone operation)
  • RMF: Operating mode default setting for the entire EASYLAB room


Functional values

  • 0: Manual control has been enabled on the control panel; operating mode defaults set on DI override BACnet or Modbus defaults.
  • 1: Manual control has been disabled on the control panel; operating mode default settings from BACnet or Modbus have the highest priority

Data point

  • BACnet: Binary Value Object – Instance BV-4
  • Modbus: Bit list – bit 0 or register 1

PressSetSel

BMS access: WR RD

Equipment functions: RR with RMF, TAM with RMF


Function

  • If room pressure control of the EASYLAB system is active, this is the input for switching between two differential pressure setpoint values that are stored in the room management function


Functional values

  • 0: Use differential pressure setpoint 1
  • 1: Use differential pressure setpoint 2

Data point

  • BACnet: Binary Value Object – Instance BV-5
  • Modbus: Bit list – bit 1 or register 13

DO*_Set (BACnet), DO_Set (Modbus)

BMS access: WR RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Ansteuerung der nicht benutzten Schaltausgänge DO1 – DO6 des Reglers oder Adaptermoduls

Data point

BACnet: Binary Value Object – Instance BV-19 (DO1_Set) – Instance BV-24 (DO6_Set)

  • 0 = output inactive
  • 1 = output active

Modbus: Register 61 – bit 0 (DO1_Set) – bit 5 (DO6_Set)

  • Bit not set = output inactive
  • Bit set = output active

Output variables

ModeAct

BMS access: RD

Equipment functions: FH, RR, RR with RMF, EC, SC


Function

  • Output of the operating mode for the volume flow controller
  • For more information on each operating mode see the description of the 'Mode' input variable


Functional values (BACnet / Modbus)

  • 1/0 = No default
  • 2/1 = Standard mode
  • 3/2 = Reduced operation
  • 4/3 = Increased operation
  • 5/4 = Shut-off
  • 6/5 = OPEN position

Data point

  • BACnet: Multistate Value Object – Instance MV-3
  • Modbus: Register 2

RoomModeAct

BMS access: RD

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of the room operating mode
  • For more information on each operating mode see the description of the 'Mode' input variable


Functional values (BACnet / Modbus)

  • 1/0 = No default
  • 2/1 = Standard mode
  • 3/2 = Reduced operation
  • 4/3 = Increased operation
  • 5/4 = Shut-off
  • 6/5 = OPEN position

Data point

  • BACnet: Multistate Value Object – Instance MV-4
  • Modbus: Register 36

SwitchPos

BMS access: RD

Equipment function: FH


Function

  • Output of the current switching step of the fume cupboard as a numeric value if the fume cupboard controller is equipped with switch contacts for 2-point or 3-point control (FH2P, FH-3P)

Data point

BACnet: Multistate Value Object – Instance MV-5

  • 1 = invalid state
  • 2 = switching step 1
  • 3 = switching step 2
  • 4 = switching step 3

Modbus:Register 35

  • 0 = invalid state
  • 1 = switching step 1
  • 2 = switching step 2
  • 3 = switching step 3

SC_GetLockHighPrio

BMS access: RD


Function

  • Signal that sash has been locked, high priority

Data point

  • BACnet: Multistate Value Object - Instance MV-8
  • Modbus: Bit list - bit 6 or register 44

VolflowSet

BMS access: RD

Equipment functions: FH, RR, RR with RMF, EC, SC

Unit: l/s


Function

  • Output of the volume flow rate setpoint value for the volume flow controller

Data point

  • BACnet: Analog Value Object – Instance AV-1
  • Modbus: Register 4

VolflowAct

BMS access: RD

Equipment functions: FH, RR, RR with RMF, EC, SC

Unit: l/s


Function

  • Output of the volume flow rate actual value of the volume flow controller

Data point

  • BACnet: Analog Value Object – Instance AV-2
  • Modbus: Register 3

VolTotalExh

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: l/s


Function

  • Output of the total extract air volume flow rate of an EASYLAB room
  • This includes the extract air volume flow rates of all fume cupboards and extract air contollers as well as any additional extract air volume flow rates (constant and variable) from other controllers.

Data point

  • BACnet: Analog Value Object – Instance AV-3
  • Modbus: Register 7

VolTotalSup

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: l/s


Function

  • Output of the total supply air flow rate of an EASYLAB room
  • This includes the supply air volume flow rates of all supply air controllers as well as the additional supply air volume flow rates (constant and variable)

Data point

  • BACnet: Analog Value Object – Instance AV-4
  • Modbus: Register 8

PressSet

BMS access: RD

Equipment functions: RR with RMF, TAM with RMF

Unit: Pa


Function

  • Output of the differential pressure setpoint value within the EASYLAB system

Data point

  • BACnet: Analog Value Object – Instance AV-5
  • Modbus: Register 12

PressAct

BMS access: RD

Equipment functions: RR with RMF, TAM with RMF

Unit: Pa


Function

  • Output of the differential pressure actual value within the EASYLAB system
  • The actual value is recorded by a differential pressure transducer connected to the RR with RMF or to the TAM with RMF

Data point

  • BACnet: Analog Value Object – Instance AV-6
  • Modbus: Register 11

VelocitySet

BMS access: RD

Equipment function: FH

Unit: m/s


Function

  • Output of the face velocity setpoint value if the fume cupboard controller is equipped with a face velocity transducer (FH-VS)

Data point

  • BACnet: Analog Value Object – Instance AV-7
  • Modbus: Register 6

VelocityAct

BMS access: RD

Equipment function: FH

Unit: m/s


Function

  • Output of the face velocity actual value if the fume cupboard controller is equipped with a face velocity transducer (FH-VS)

Data point

  • BACnet: Analog Value Object – Instance AV-8
  • Modbus: Register 5

WireSensorPos

BMS access: RD

Equipment function: FH

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of sash position of the fume cupboard as a percentage value between closed position (0 %) and open position (100 %) if the fume cupboard controller is equipped with a sash distance sensor (FH-DS, FH-DV)

Data point

  • BACnet: Analog Value Object – Instance AV-9
  • Modbus: Register 34

SystemDevices

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Number of identified EASYLAB system components

Data point

  • BACnet: Analog Value Object – Instance AV-21
  • Modbus Register 37

SC_GetPos

BMS access: RD


Function

  • Signals the sash position

Data point

  • BACnet: Analogue Value Object - Instance AV-25
  • Modbus: Register 47

Device_ID_*

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the Device ID of the device being addressed (0 – 23)
  • The Device_ID_* data points (0 – 23) of the EM-IP expansion module contain the Device ID of each controller (1 – 24)
  • Controllers are automatically assigned a Device ID as part of the configuration procedure
  • Controllers are automatically assigned to the data points
  • If any variables, e.g. VolflowAct_* and LocalAlarm_* or others, have the same slot (*), they are associated with the same controller, which is being addressed


Example

  • A controller has Device ID 5
  • When you switch on the supply voltage, the expansion module assigns a free slot to that device, let's say slot 8
  • As a consequence, Device_ID_8 will receive value 5, and the VolflowAct_8 and LocalAlarm_8 variables will receive the current values for controller 5

Data point

BACnet: Analogue Value Object – Instance AV-32 (Device_ID_0) – Instance AV-55 (Device_ID_23)

Modbus: Register 66 – 89

VolflowAct_*

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: l/s


Function

  • Output of the volume flow rate actual value for the controller being addressed (0 – 23)

Data point

BACnet: Analogue Value Object – Instance AV-56 (VolFlowAct_0) – Instance AV-79 (VolFlowAct_23)

Modbus: Register 90 (VolFlowAct_0) – 113 (VolFlowAct_23)

Volt_AI2

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: V DC

from firmware version EM-BAC-MOD 4.0, EM-IP 2.0 and TCU3, TAM 7.0


Function

  • Output of the voltage at analogue input AI2
  • 0 – 10 V DC, in increments of 0.1 V

Data point

  • BACnet: Analog Value Object – Instance AV-82
  • Modbus: Register 116

Volt_AI3

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: V DC

from firmware version EM-BAC-MOD 4.0, EM-IP 2.0 and TCU3, TAM 7.0


Function

  • Output of the voltage at analogue input AI3
  • 0 – 10 V DC, in increments of 0.1 V

Data point

  • BACnet: Analog Value Object – Instance AV-83
  • Modbus: Register 117

LocalAlarm

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of a local alarm for a fume cupboard controller, extract air controller, supply air controller, room controller or TAM
  • Alarm conditions can be defined using the EasyConnect configuration software


Functional values

  • 0 = No local alarm
  • 1 = Local alarm

Data point

  • BACnet: Binary Value Object – Instance BV-1 (BIBBS-DS-COVU-B Change of value reporting)
  • Modbus: Bit list - bit 2 or register 31

SummaryAlarm

BMS access: RD

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of a consolidated alarm
  • An alarm signal is generated when a controller emits an alarm or fault message.
  • Alarm conditions can be defined using the EasyConnect configuration software
  • Standard configuration: volume flow rate alarm


Functional values

  • 0 = No consolidated alarm
  • 1 = Consolidated alarm

Data point

  • BACnet: Binary Value Object – Instance 2 (BIBBS-DS-COVU-B Change of value reporting)
  • Modbus: Bit list - bit 3 or register 32

PressAlarm

BMS access: RD

Equipment functions: RR with RMF, TAM with RMF


Function

  • Output of a room pressure alarm when room pressure control is active
  • Alarm conditions can be defined using the EasyConnect configuration software


Functional values

  • 0 = No differential pressure alarm
  • 1 = Differential pressure alarm

Data point

  • BACnet: Binary Value Object – Instance BV-3 (BIBBS-DS-COVU-B Change of value reporting)
  • Modbus: Bit list - bit 4 or register 33

DI* (BACnet), StateDI (Modbus)

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

from firmware version EM-BAC-MOD 2.0 and TCU3, TAM 3.0


Function

  • Status of digital inputs DI1 – DI6 of the controller or adapter module

Data point

BACnet: Binary Value Object – Instance BV-6 (DI1) – Instance BV-11 (DI6)

  • 0 = inactive
  • 1 = active

Modbus: Register 39 – bit 0 (DI1) – bit 5 (DI6)

  • Bit not set = inactive
  • Bit set = active

DO* (BACnet), StateDO (Modbus)

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

from firmware version EM-BAC-MOD 2.0 and TCU3, TAM 3.0


Function

  • Status of digital outputs DO1 – DO6 of the controller or adapter module

Data point

BACnet: Binary Value Object – Instance BV-12 (DO1) – Instance BV-17 (DO6)

  • 0 = output inactive
  • 1 = output active

Modbus: Register 40 – bit 0 (DO1) – bit 5 (DO6)

  • Bit not set = output inactive
  • Bit set = output active

SC_Alarm

BMS access: RD


Function

  • Output for automatic sash device signal

Data point

  • BACnet: Binary Value Object – Instance BV-18
  • Modbus: Bit list – bit 7 or register 48


DampPosMaxState_FH

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the fume cupboard controller with the widest open damper blade 4
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-11
  • Modbus: Register 16

DampPosMinState_FH

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the fume cupboard controller with the least wide open damper blade 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-12
  • Modbus: Register 18

DampPosMaxState_RE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the room extract air controller with the widest open damper blade 4
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-13
  • Modbus: Register 20

DampPosMinState_RE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the room extract air controller with the least wide open damper blade 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-14
  • Modbus: Register 22

DampPosMaxState_TE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the fume cupboard, extract air or room extract air controller with the widest open damper blade 4
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-15
  • Modbus: Register 24

DampPosMinState_TE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the fume cupboard, extract air or room extract air controller with the least wide open damper blade 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-16
  • Modbus: Register 26

DampPosMaxState_RS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the room supply air controller with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-17
  • Modbus: Register 28

DampPosMinState_RS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the room supply air controller with the least wide open damper blade 5

Data point

  • BACnet: Multistate Value Object – Instance MV-18
  • Modbus: Register 30

DampPosMaxState_EC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the extract air controller with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-26
  • Modbus: Register 50

DampPosMinState_EC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the extract air controller with the least wide open damper blade 5

Data point

  • BACnet: Multistate Value Object – Instance MV-27
  • Modbus: Register 52

DampPosMaxState_SC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the supply air controller with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-28
  • Modbus: Register 54

DampPosMinState_SC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the supply air controller with the least wide open damper blade 5

Data point

  • BACnet: Multistate Value Object – Instance MV-29
  • Modbus: Register 56

DampPosMaxState_TS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the supply air or room supply air controller with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-30
  • Modbus: Register 58

DampPosMinState_TS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF


Function

  • Output of the status of the supply air or room supply air controller with the least wide open damper blade 5

Data point

  • BACnet: Multistate Value Object – Instance MV-31
  • Modbus: Register 60

DampPosMaxState_VE

BMS access: RD


Function

  • Output of the status of the Universal extract air controller with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-32
  • Modbus: Register 120

DampPosMinState_VE

BMS access: RD


Function

  • Output of the status of the Universal extract air controller with the least wide open damper blade 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-33
  • Modbus: Register 122

DampPosMaxState_VS

BMS access: RD


Function

  • Output of the status of the Universal supply air controller with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-34
  • Modbus: Register 124

DampPosMinState_VS

BMS access: RD


Function

  • Output of the status of the Universal supply air controller with the least wide open damper blade 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Multistate Value Object – Instance MV-35
  • Modbus: Register 126

DampPosMaxState_PKE

BMS access: RD


Function

  • Output of the status of the Universal differential pressure controller – extract air – with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-36
  • Modbus: Register 128

DampPosMinState_PKE

BMS access: RD


Function

  • Output of the status of the Universal differential pressure controller – extract air – with the least wide open damper blade 5

Data point

  • BACnet: Multistate Value Object – Instance MV-37
  • Modbus: Register 130

DampPosMaxState_PKS

BMS access: RD


Function

  • Output of the status of the Universal differential pressure controller – supply air – with the widest open damper blade 4

Data point

  • BACnet: Multistate Value Object – Instance MV-38
  • Modbus: Register 132

DampPosMinState_PKS

BMS access: RD


Function

  • Output of the status of the Universal differential pressure controller – supply air – with the least wide open damper blade 5

Data point

  • BACnet: Multistate Value Object – Instance MV-39
  • Modbus: Register 134

DampPos

BMS access: RD

Equipment functions: FH, RR, RR with RMF, EC, SC

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position¹

Data point

  • BACnet: Analog Value Object – Instance AV-10
  • Modbus: Register 14

DampPosMaxFH

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the fume cupboard controller with the widest open damper blade 1, 2, 4
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Analog Value Object – Instance AV-11 – value and event state
  • Modbus: Register 15 (value) and register 16 (event state)

DampPosMin_FH

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the fume cupboard controller with the least wide open damper blade 1, 2, 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Analog Value Object – Instance AV-12 – value and event state
  • Modbus: Register 17 (value) and register 18 (event state)

DampPosMax_RE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the room extract air controller with the widest open damper blade 1, 2, 4
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Analog Value Object – Instance AV-13 – value and event state
  • Modbus: Register 19 (value) and register 20 (event state)

DampPosMin_RE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the room extract air controller with the least wide open damper blade 1, 2, 5
  • For the evaluation of the damper blade positions in separate extract air systems (2 fans), i.e. fume cupboard extract air and room extract air

Data point

  • BACnet: Analog Value Object – Instance AV-14 – value and event state
  • Modbus: Register 21 (value) and register 22 (event state)

DampPosMax_TE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the fume cupboard, extract air or room extract air controller with the widest open damper blade 1, 3, 4
  • For the evaluation of the damper blade positions in the extract air system (1 fan) for fume cupboard and room extract air

Data point

  • BACnet: Analog Value Object – Instance AV-15 – value and event state
  • Modbus: Register 23 (value) and register 24 (event state)

DampPosMin_TE

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the fume cupboard, extract air or room extract air controller with the least wide open damper blade 1, 3, 5
  • For the evaluation of the damper blade positions in the extract air system (1 fan) for fume cupboard and room extract air

Data point

  • BACnet: Analog Value Object – Instance AV-16 – value and event state
  • Modbus: Register 25 (value) and register 26 (event state)

DampPosMax_RS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the room supply air controller with the widest open damper blade 1, 4

Data point

  • BACnet: Analog Value Object – Instance AV-17 – value and event state
  • Modbus: Register 27 (value) and register 28 (event state)

DampPosMin_RS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)


Function

  • Output of the damper blade position of the room supply air controller with the least wide open damper blade 1, 5

Data point

  • BACnet: Analog Value Object – Instance AV-18 – value and event state
  • Modbus: Register 29 (value) and register 30 (event state)

DampPosMax_EC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the room extract air controller with the widest open damper blade 1, 4

Data point

  • BACnet: Analog Value Object – Instance AV-26 – value and event state
  • Modbus: Register 49 (value) and register 50 (event state)

DampPosMin_EC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the room extract air controller with the least wide open damper blade 1, 5

Data point

  • BACnet: Analog Value Object – Instance AV-27 – value and event state
  • Modbus: Register 51 (value) and register 52 (event state)

DampPosMax_SC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the supply air controller with the widest open damper blade 1, 4

Data point

  • BACnet: Analog Value Object – Instance AV-28 – value and event state
  • Modbus: Register 53 (value) and register 54 (event state)

DampPosMinSC

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the supply air controller with the least wide open damper blade 1, 5

Data point

  • BACnet: Analog Value Object – Instance AV-29 – value and event state
  • Modbus: Register 55 (value) and register 56 (event state)

DampPosMax_TS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the supply air or room supply air controller with the widest open damper blade 1, 4

Data point

  • BACnet: Analog Value Object – Instance AV-30 – value and event state
  • Modbus: Register 57 (value) and register 58 (event state)

DampPosMin_TS

BMS access: RD

Equipment function: FH, RR, RR with RMF, EC, SC, TAM, TAM with RMF

Unit: %

Value range:

  • BACnet: percentage value in 0.5 % increments
  • Modbus: 0 – 200 (200 corresponds to 100 %)

from firmware version EM-BAC-MOD 3.0 and TCU3, TAM 5.0


Function

  • Output of the damper blade position of the supply air or room supply air controller with the least wide open damper blade 1, 5

Data point

  • BACnet: Analog Value Object – Instance AV-31 – value and event state
  • Modbus: Register 59 (value) and register 60 (event state)

DamPosMaxValue_VE

Data point

  • BACnet: Analog Value Object – Instance AV-85 – value and event state
  • Modbus: Register 119 (value) and register 120 (event state)

DamPosMinValue_VE

Data point

  • BACnet: Analog Value Object – Instance AV-86 – value and event state
  • Modbus: Register 121 (value) and register 122 (event state)

DamPosMaxValue_VS

Data point

  • BACnet: Analog Value Object – Instance AV-87 – value and event state
  • Modbus: Register 123 (value) and register 124 (event state)

DamPosMinValue_VS

Data point

  • BACnet: Analog Value Object – Instance AV-88 – value and event state
  • Modbus: Register 125 (value) and register 126 (event state)

DamPosMaxValue_PKE

Data point

  • BACnet: Analog Value Object – Instance AV-89 – value and event state
  • Modbus: Register 127 (value) and register 128 (event state)

DamPosMinValue_PKE

Data point

  • BACnet: Analog Value Object – Instance AV-90 – value and event state
  • Modbus: Register 129 (value) and register 130 (event state)

DamPosMaxValue_PKS

Data point

  • BACnet: Analog Value Object – Instance AV-91 – value and event state
  • Modbus: Register 131 (value) and register 132 (event state)

DamPosMinValue_PKS

Data point

  • BACnet: Analog Value Object – Instance AV-92 – value and event state
  • Modbus: Register 133 (value) and register 134 (event state)

1 Damper blade positions DampPos**_** are transmitted as a percentage value between 0% (closed) and 100% (open).

2 The output variables DampPosMax_FH, DampPosMin_FH, DampPosMax_EC, and DampPosMin_EC, as well as DampPosMax_RE and DampPosMin_RE are provided for the evaluation of the damper blade positions in separate extract air systems (3 fans) for fume cupboards, extract air and room extract air.

3 The output variables DampPosMax_TE and DampPosMin_TE are provided for the evaluation of the damper blade positions in the extract air system (1 fan) for fume cupboard, extract air and room extract air.

4 Status information for damper blade positions DampPosMax_**

BACnet

  • Functional value = –1 (FF): All damper blades in OPEN position (special operating mode, value  = 100%). Override not possible
  • Functional value = 2: All damper blades in standard operating mode. Override possible
  • Functional value = 3: At least one damper blade in OPEN mode (special operating mode)

Modbus

  • Event state = 0: All damper blades in standard operating mode. Override possible
  • Event state = –1 (FF): All damper blades in OPEN position (special operating mode, value  = 100 %). Override not possible
  • Event state = 1: At least one damper blade in OPEN position (special operating mode)

5 Status information for damper blade positions DampPosMin_**

BACnet

  • Functional value = –1: All damper blades in shut-off mode (special operating mode, value = 0%). Override not possible
  • Functional value = 2: All damper blades in standard operating mode. Override possible
  • Functional value = 3: At least one damper blade in shut-off mode (special operating mode)

Modbus

  • Event state = 0: All damper blades in standard operating mode. Override possible
  • Event state = –1 (FF): All damper blades in shut-off mode (special operating mode, value  = 0 %). Override not possible
  • Event state = 1: At least one damper blade in shut-off mode (special operating mode)

Installation details

  • Installation details

Installation and commissioning

Installation

  • As attachment for the EASYLAB base component: factory mounted
  • For retrofitting: Mount the expansion module into the base casing


Commissioning

  • The EASYLAB controller identifies the expansion module automatically
  • Use the Ethernet patch cable to connect the configuration computer with an active DHCP client or adapted IP address to the EM-IP module
  • Complete and save the configuration using the personal computer and the web UI
  • Restart EM-IP using the Reset push button or web UI and connect it to the target network (BACnet/IP, Modbus/IP or Ethernet network)

Downloads

product information

certificates

operation manuals

software

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be