Steel door with inspection window, pressure relief valve and cylinder rim lock(Profile cylinder on the opening side, cylinder rim lock on the closing side)
Application
Special characteristics
Nominal sizes
ST (single leaf)
ST-D (double leaf)
Any combination of B × H
Variants
Parts and characteristics
Attachments
Construction features
Materials and surfaces
Mineral wool
Maintenance
Functional description
Low-leakage steel doors are low-leakage separating elements for rooms or other enclosures.
When the door is being closed, i.e. when the double locking levers are being turned, the perimeter seal is fully pressed against the frame. As a consequence, the air leakage rate is extremely low even in case of high differential pressures.
Nominal sizes (single leaf) | 400 × 800 to 1100 × 2115 mm |
Nominal sizes (double leaf) | 1080 × 800 to 2280 × 2115 mm |
Maximum pressure on the opening side | 1000 Pa (reinforced construction: 2000 Pa) |
Weighted sound reduction index (with sound absorbing infill) | Single leaf door 43 – 46 dB, double leaf door 44 – 47 dB, doors on both sides of the wall opening 58 – 61 dB |
Weighted sound reduction index
ST-X, ST-X-V | 26 | 38 | 44 | 46 | 46 |
ST-D-X, ST-D-X-V | 28 | 41 | 45 | 49 | 46 |
2 × ST-X, ST-X-V, doors on both sides of the wall opening | 48 | 52 | 59 | 62 | 65 |
Low-leakage steel doors as separating elements for walk-in plant rooms, storage rooms, air handling units, filter chambers, or enclosures for machinery or electrical equipment.
Ready-to-install component that consists of a door leaf with double lever locking devices, absorption material, seal and hinges, and a frame.
Air leakage rate on the opening side is approx. 0.6 l/s or 2 m³/h at 1000 Pa (single leaf door).
Special characteristics
Materials and surfaces
Mineral wool
Technical data
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.
Order example: ST–R/800×1800/21/Z06
Hinge | Right side |
Sound insulating lining | Without |
Construction of door | Standard construction |
Nominal size | 800 × 1800 mm |
Door frame | Angle section, without fixing tabs |
Attachments | Standard construction with inspection window and cylinder rim lock |
Surface | Standard construction |
Order example: ST–D/1680×1800/21/Z06
Number of door leaves | Double leaf low-leakage steel door |
Sound insulating lining | Without |
Construction of door | Standard construction |
Nominal size | 1680 × 1800 mm |
Door frame | Angle section, without fixing tabs |
Attachments | Standard construction with inspection window and cylinder rim lock |
Surface | Standard construction |
ST
Variant
Parts and characteristics
Construction features
ST-V
Variant
Parts and characteristics
Construction features
ST-X
Variant
Parts and characteristics
Construction features
ST-X-V
Variant
Parts and characteristics
Construction features
ST-D
Variant
Parts and characteristics
Construction features
ST-D-V
Variant
Parts and characteristics
Construction features
ST-D-X
Variant
Parts and characteristics
Construction features
ST-D-X-V
Variant
Parts and characteristics
Construction features
ST, width, dimensions
<500 | B + 30 |
500 | 530 |
600 | 630 |
800 | 830 |
940 | 970 |
ST, height, dimensions
<1500 | H + 30 | 249.5 |
1500 | 1530 | 349.5 |
1600 | 1630 | 349.5 |
1800 | 1830 | 349.5 |
1940 | 1970 | 349.5 |
ST-D, width, dimensions
B < 1080 | (B – 20) ∕ 2 | B + 30 |
1080 | 530 | 1110 |
1280 | 630 | 1310 |
1680 | 830 | 1710 |
1960 | 970 | 1990 |
ST, ST-V, weights
1500 | 33 | 40 | 53 | 62 |
1600 | 34 | 41 | 54 | 64 |
1800 | 35 | 42 | 56 | 66 |
1940 | 36 | 43 | 57 | 67 |
ST-X, ST-X-V, weights
1500 | 36 | 43 | 58 | 68 |
1600 | 37 | 44 | 59 | 70 |
1800 | 38 | 46 | 61 | 71 |
1940 | 39 | 46 | 62 | 73 |
ST-D, ST-D-V, weights
1500 | 66 | 78 | 102 | 120 |
1600 | 68 | 81 | 106 | 123 |
1800 | 70 | 83 | 109 | 127 |
1940 | 72 | 86 | 113 | 131 |
ST-D-X, ST-D-X-V, weights
1500 | 72 | 86 | 113 | 131 |
1600 | 75 | 88 | 116 | 135 |
1800 | 77 | 91 | 119 | 139 |
1940 | 80 | 95 | 124 | 145 |
Installation and commissioning
Angle section frame, no. of fixing tabs or flange holes
1500 | 6 | 8 |
1600 | 6 | 8 |
1800 | 8 | 10 |
1940 | 8 | 10 |
U-channel door frame, dimensions
13 | 115 |
15 | 240 |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be