00133934_0
Explosion-proof actuator ExMax 15


00132578_0
Multileaf damper with explosion-proof actuator


00132558_0
Electric actuator


00132570_0
Pneumatic actuator


00132566_0
Solenoid valve


00133177_0
Limit switch


00133934_0
00132578_0
00132558_0
00132570_0
00132566_0
00133177_0

EXPLOSION-PROOF ACTUATORS  

For opening and closing multileaf dampers installed in potentially explosive atmospheres (ATEX)

Explosion-proof actuators for Type JZ, JZ-LL and JZ-HL multileaf dampers

  • ATEX-compliant construction and parts
  • Approved for gases, mists and vapours in zones 1 and 2, and for dusts in zones 21 and 22
  • Supply voltage 24 V AC/DC or 230 V AC
  • Pneumatic actuators with torque 8 – 70 Nm
  • Electric actuator with torque 15 or 30 Nm
  • Pneumatic: Double acting or single acting actuator for a positive lock connection with a multileaf damper
  • Electric: Spring return actuator for a positive lock connection with a multileaf damper


Optional equipment and accessories

  • Solenoid valve 24 V DC or 230 V AC
  • Limit switch

General information

Application 

  • Explosion-proof actuators for open/close switching 
  • Open/close switching of multileaf dampers type JZ, JZ-LL, JZHL 
  • For use in areas with potentially explosive atmospheres (ATEX) 
  • For multileaf dampers made of steel or stainless steel with bearing bushes made of brass or stainless steel 


Special characteristics 

ATEX marking and certification 

Approved for all gases, mists and vapours in zones 1 and 2, and for dusts in zones 21 and 22 

Classification 

Multileaf damper 

  • Test certificate: EPS 23 ATEX 2 307 X 
  • II 2 GD c 80 °C (T6) 

Subassembly: Multileaf damper with actuator 

  • Test certificate: EPS 23 ATEX 2 307 X 
  • II 2 GD or II 2/3 GD or II 3 GD 


Parts and characteristics 

Construction and selection of materials comply with the European Directives, ATEX (Atmosphère explosible) 

Electric 

  • Actuators with overload protection 
  • Control input signal: 2-wire control (3-point, open/close) 
  • Spring return actuator for damper blade safety function 
  • Auxiliary switch for capturing the end positions 
  • Crank handle for manual operation 

Pneumatic 

  • Pneumatic actuators, single-acting or double-acting 
  • Control input signal: 1-wire control via solenoid valve 
  • Optional limit switch for capturing the end positions 
  • Safety function with double-acting actuators, when power off 
  • Safety function with single-acting actuators (when pressure off)

Technical information

Function

  • Function

Functional description

The actuator moves the blades of a multileaf damper into OPEN or CLOSED position.


Electric spring return actuator

Control input signal with 2-wire control (3-point).


Double acting pneumatic actuators

The easiest way to generate the control input signal is electrically, using solenoid valves.

The multileaf damper is opened and closed with compressed air. For this purpose, the actuator has two tube connections. Compressed air is applied to one tube connection while the other connection remains open such that the air can escape from the corresponding chamber of the actuator. For the other direction of rotation, the process is reversed.


Single acting pneumatic actuators

The easiest way to generate the control input signal is electrically, using solenoid valves.

The multileaf damper is closed with compressed air and opened with spring force. The actuator has one tube connection. This tube connection is for compressed air. For the other direction of rotation the connection remains open.

Variants, Electric, Double acting, Single acting, Limit switch, Solenoid valves

  • Variants
  • ELECTRIC
  • DOUBLE ACTING
  • SINGLE ACTING
  • LIMIT SWITCH
  • SOLENOID VALVES

Any attachments are to be defined with the order code of the multileaf damper.

Electric explosion-proof spring return actuators for multileaf dampers

Order code detail Actuator Torque Supply voltage
Order code detail Part number Type Auxiliary switch Torque Supply voltage

Z1EX

M466EM1

ExMax15-SF

integrated

15 Nm

24 – 240 V

Z3EX

M466EM3

ExMax30-SF

integrated

30 Nm

24 – 240 V


Explosion-proof double acting pneumatic actuators for multileaf dampers

Order code detail Actuator Limit switch Torque at 6 bar Solenoid valve Damper blade safety function
Order code detail Part number Type Part number Torque at 6 bar Solenoid valve Damper blade safety function

Z60EX

M452DD0

DR030

35 Nm


Z61EX

M452DD0

DR030

35 Nm

24 V

Z62EX

M452DD0

DR030

35 Nm

230 V

Z63EX

M452DD0

DR030

2 × M536AJ3

35 Nm


Z64EX

M452DD0

DR030

2 × M536AJ3

35 Nm

24 V

Z65EX

M452DD0

DR030

2 × M536AJ3

35 Nm

230 V

Z66EX

M452DD1

DR060

70 Nm


Z67EX

M452DD1

DR060

70 Nm

24 V

Z68EX

M452DD1

DR060

70 Nm

230 V

Z69EX

M452DD1

DR060

2 × M536AJ3

70 Nm


Z70EX

M452DD1

DR060

2 × M536AJ3

70 Nm

24 V

Z71EX

M452DD1

DR060

2 × M536AJ3

70 Nm

230 V

① Power off to close/open

Operating pressure 1.2 – 6 bar


Explosion-proof single acting pneumatic actuators for multileaf dampers

Order code detail Actuator Limit switch Torque at 6 bar Solenoid valve Damper blade safety function
Order code detail Type Part number Torque at 6 bar Solenoid valve Damper blade safety function

Z72EX

SC060/SO060

30 Nm

Z73EX

SC060/SO060

30 Nm

24 V

Z74EX

SC060/SO060

30 Nm

230 V

Z75EX

SC060/SO060

2 × M536AJ3

30 Nm

Z76EX

SC060/SO060

2 × M536AJ3

30 Nm

24 V

Z77EX

SC060/SO060

2 × M536AJ3

30 Nm

230 V

① Power off to close/open

② Power off and pressure off to close/open

Operating pressure 6 bar


Application

  • Explosion-proof electric actuators for opening and closing
  • Opening and closing of Type JZ, JZ-LL, JZ-HL multileaf dampers
  • For use in potentially explosive atmospheres (ATEX)
  • For steel or stainless steel multileaf dampers with brass or stainless steel bearings

Variants

  • Z1EX: Explosion-proof actuator ExMax15-SF
  • Z3EX: Explosion-proof actuator ExMax30-SF

Safety function

  • NO: Power off to OPEN
  • NC: Power off to CLOSE

Parts and characteristics

  • Supply voltage 24 – 240 V AC/DC
  • Automatic voltage detection
  • Control input signal: 2-wire control (3-point)
  • Integral controlled heating
  • Two auxiliary switches with volt-free contacts for signalling or activating switch functions
  • Auxiliary switches, factory set switching points at 5° and 85°
  • Terminal box ExBox-Y/S

Explosion-proof actuator ExMax15-SF

Supply voltage (AC)

24 – 240 V AC ±10 %, 50/60 Hz

Supply voltage (DC)

24 – 240 V DC ±10 %,

Power rating (AC)

23 – 115 VA, depending on running time

Power rating (DC)

10 – 115 W, depending on running time

Torque

15 Nm

Motor running time for 90°

3, 15, 30, 60, 120 s, adjustable

Spring return time

3 – 10 s, adjustable

Control input signal

2-wire control (3-point)

Auxiliary switch: type of contact

2 changeover contacts1)

Max. switching voltage (AC)

250 V AC

Max. switching current (AC)

3 A (resistive load); 0.5 A (inductive load)

Max. switching voltage (DC)

24 V DC

Max. switching current (DC)

0.25 A (resistive load); 0.1 A (inductive load)

IEC protection class

I (protective earth)

Protection level

IP 66

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, ATEX to 2014/34/EU

Operating temperature

–40 to 40 °C

Weight

4.3 kg (including Ex Box)

1) If both auxiliary switches are used the switching voltages must be the same


Explosion-proof actuator ExMax30-SF

Supply voltage (AC)

24 – 240 V AC ±10 %, 50/60 Hz

Supply voltage (DC)

24 – 240 V DC ±10 %

Power rating (AC)

23 – 115 VA, depending on running time

Power rating (DC)

10 – 115 W, depending on running time

Torque

30 Nm

Motor running time for 90°

40, 60, 90, 120, 150 s, adjustable

Spring return time

20 s

Control input signal

2-wire control (3-point)

Auxiliary switch: type of contact

2 changeover contacts1)

Max. switching voltage (AC)

250 V AC

Max. switching current (AC)

3 A (resistive load); 0.5 A (inductive load)

Max. switching voltage (DC)

24 V DC

Max. switching current (DC)

0.25 A (resistive load); 0.1 A (inductive load)

IEC protection class

I (protective earth)

Protection level

IP 66

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, ATEX to 2014/34/EU

Operating temperature

–40 to 40 °C

Weight

10 kg (including Ex Box)

1) If both auxiliary switches are used the switching voltages must be the same


Application

  • Explosion-proof double acting pneumatic actuators for opening and closing
  • Opening and closing of Type JZ, JZ-LL, JZ-HL multileaf dampers
  • For use in potentially explosive atmospheres (ATEX)
  • For steel or stainless steel multileaf dampers with brass or stainless steel bearings

Variants

  • Z60EX, Z61EX, Z62EX, Z63EX, Z64EX, Z65EX: Actuator DR030
  • Z66EX, Z67EX, Z68EX, Z69EX, Z70EX, Z71EX: Actuator DR060

Safety function

Z61EX, Z62EX, Z64EX, Z65EX, Z67EX, Z68EX, Z70EX, Z71EX

  • NO: Power off to OPEN
  • NC: Power off to CLOSE

Parts and characteristics

Construction and materials comply with the EU directive and guidelines for use in potentially explosive atmospheres (ATEX)


  • Double acting pneumatic actuators
  • Control input signal: 1-wire control of a solenoid valve
  • Optional limit switch for capturing the end positions
  • Safety function (power off)

Pneumatic actuator DR030

Operating pressure

1.2 bar – 6.0 bar

Maximum pressure

8 bar

Torque at 6 bar

35 Nm

Running time for 90°

0.3 s

Air volume OPEN/CLOSE

0.16/0.26 l

Compressed air

Compressed air for instruments, free of oil, water and dust

Air connection

G 1/8"

Operating temperature

–40 to 80 °C

Weight

1.6 kg


DR030, Torque depending on operating pressure

Operating pressure [bar]

1.2

2.5

3

4

5

6

Torque [Nm]

8

15

18

24

29

35


Pneumatic actuator DR060

Operating pressure

1.2 bar – 6.0 bar

Maximum pressure

8 bar

Torque at 6 bar

70 Nm

Running time for 90°

0.5 s

Air volume OPEN/CLOSE

0.31/0.49 l

Compressed air

Compressed air for instruments, free of oil, water and dust

Air connection

G 1/8"

Operating temperature

–40 to 80 °C

Weight

2.7 kg


DR060, Torque depending on operating pressure

Operating pressure [bar]

1.2

2.5

3

4

5

6

Torque [Nm]

14

30

36

47

58

70


Application

  • Explosion-proof single acting pneumatic actuators for opening and closing
  • Opening and closing of Type JZ, JZ-LL, JZ-HL multileaf dampers
  • For use in potentially explosive atmospheres (ATEX)
  • For steel or stainless steel multileaf dampers with brass or stainless steel bearings

Variants

  • Z72EX, Z73EX, Z74EX, Z75EX, Z76EX, Z77EX: Actuator SC060, SO060

Safety function

Z72EX, Z75EX

  • NO: Pressure off to OPEN
  • NC: Pressure off to CLOSE


Z73EX, Z74EX, Z76EX, Z77EX

  • NO: Power off and pressure off to OPEN
  • NC: Power off and pressure off to CLOSED

Parts and characteristics

Construction and materials comply with the EU directive and guidelines for use in potentially explosive atmospheres (ATEX)


  • Single acting pneumatic actuators
  • Control input signal: 1-wire control of a solenoid valve
  • Optional limit switch for capturing the end positions
  • Safety function (pressure off)

Pneumatic actuator SC060, SO060

Operating pressure

6.0 bar

Maximum pressure

6 bar

Torque at 6 bar

30 Nm

Running time for 90°

0.5 s

Air volume OPEN/CLOSE

0.31/0.49 l

Compressed air

Compressed air for instruments, free of oil, water and dust

Air connection

G 1/8"

Operating temperature

–40 to 80 °C

Weight

3.2 kg


Application

  • Limit switch: Bartec limit switch
  • Volt-free contacts for signalling or activating switch functions

Variants

  • Z63EX, Z64EX, Z65EX, Z69EX, Z70EX, Z71EX, Z75EX, Z76EX, Z77EX: Limit switch

Parts and characteristics

  • Two limit switches, screwed onto a console of the multileaf damper
  • Actuated with a lever on the external linkage

Explosion-proof limit switch (Bartec)

Type of contact

1 changeover contacts

Max. switching voltage (AC)

400 V AC

Max. switching current (AC)

3 A (resistive load); 3 A at 250 V AC (inductive load)

Max. switching voltage (DC)

250 V DC

Max. switching current (DC)

0.4 A (resistive load); 0.03 A (inductive load)

IEC protection class

II (protective insulation)

Protection level

IP 66

EC conformity

ATEX to 2014/34/EU, RoHS to 2011/65/EU

Weight

0.2 kg


Application

  • Explosion-proof solenoid valves with connector

Variants

  • Z61EX, Z64EX, Z67EX, Z70EX, Z73EX, Z76EX: Solenoid valve Type 6519 Namur 24 V Ex
  • Z62EX, Z65EX, Z68EX, Z71EX, Z74EX, Z77EX: Solenoid valve Type 6519 Namur 230 V Ex

Safety function

Z61EX, Z62EX, Z64EX, Z65EX, Z67EX, Z68EX, Z70EX, Z71EX

  • NO: Power off to OPEN
  • NC: Power off to CLOSE


Z73EX, Z74EX, Z76EX, Z77EX

  • NO: Power off and pressure off to OPEN
  • NC: Power off and pressure off to CLOSED

Parts and characteristics

  • Supply voltage 24 V DC or 230 V AC
  • Control input signal: Supply voltage on/off
  • Connector with connecting cable
  • Namur interface for direct assembly on the pneumatic actuator

Explosion-proof solenoid valve 24 V EEx m

Supply voltage

24 V DC ± 10 %

Power rating

3 W

Pressure range

1.2 – 8.0 bar

Flow rate Q Nn

900 l/min

Compressed air

Containing oil, oil-free, or nitrogen or instrument air

Air connection

G 1/8"

IEC protection class

III (protective extra-low voltage)

Protection level

With IP 65 connector

EC conformity

EMC to 2014/30/EU, ATEX to 2014/34/EU

Operating temperature

–25 to 55 °C

Weight

0.46 kg


Explosion-proof solenoid valve 230 V EEx m

Supply voltage

230 V AC ± 10 %

Power rating

3 W

Pressure range

1.2 – 8.0 bar

Flow rate Q Nn

900 l/min

Compressed air

Containing oil, oil-free, or nitrogen or instrument air

Air connection

G 1/8"

IEC protection class

II (protective insulation)

Protection level

With IP 65 connector

EC conformity

EMC to 2014/30/EU, low voltage to 2014/35/EU, ATEX to 2014/34/EU

Operating temperature

–25 to 55 °C

Weight

0.46 kg


Downloads

product information

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Contact

We are here for you

Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be