Application
Parts and characteristics
Functional description
The actuator moves the damper blade mechanism to any position between minimum and maximum.
Minimum and maximum positions can be set on potentiometers.
The control input signal is a voltage signal. The output signal indicates the damper blade position rather than the volume flow rate actual value since the CAV controller does not perform any measurements.
Control options and effect of actuator action in case of factory setting
B70, B72 | Variable | Variable control | ||
B70, B72 | Min/Max | 1-wire control, 2-wire control | Vmin | Vmax |
E03 | Variable | Variable control |
Actuators LM24A-SR and LM24A-SR-F
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power consumption – load | 1 W |
Power consumption – idle | 0.4 W |
Power rating | 2 VA |
Torque | 5 Nm |
Running time for 90° | 150 s |
Position feedback | 2 – 10 V DC, 1 mA |
Control signal | 2 – 10 V DC, Ra > 100 kΩ |
Connecting cable | 4 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.5 kg |
Auxiliary switch S2A
Type of contact | 2 changeover contacts1) |
Max. switching voltage (AC) | 250 V AC |
Max. switching current (AC) | 3 A (resistive load); 0.5 A (inductive load) |
Max. switching voltage (DC) | 110 V DC |
Max. switching current (DC) | 0.5 A (resistive load); 0.2 A (inductive load) |
Connecting cable | 6 × 0.75 mm², 1 m long |
IEC protection class | II (protective insulation) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.250 kg |
1) If both auxiliary switches are used the switching voltages must be the same
Actuator 224C-024-02-003
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC ±20 % |
Power rating (AC) | 3 VA |
Power rating (DC) | 2 W |
Torque | 5 Nm |
Running time for 90° | 20 – 60 s |
Control signal | 0 – 10 V DC, Ra > 100 kΩ |
Connecting cable | 3 × 0.75 mm², 1 m long |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC according to 2014/30/EU, RoHS to 2011/65/EU |
Operating temperature | –30 to 50 °C |
Weight | 0.5 kg |
Any attachments are to be defined with the order code of the CAV controller.
B7*
Application
Variants
Parts and characteristics
Commissioning
B*2
Application
E03
Application
Parts and characteristics
Commissioning
Actuators for volume flow controllers Type RN or EN
B70 | M466DT6 | LM24A-SR-F | 24 V AC/DC |
| |
B72 | M466DT6 | LM24A-SR-F | 24 V AC/DC | M536AI3 | S2A |
Actuators for volume flow controllers Type VFC and for flow adjustment dampers Type VFR
E03 | M466EP7 | 224C-024-02-003 | Potentiometer | 24 V AC/DC |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be