Set flow rates
Application
If air is contaminated with dust, lint, sticky, moist or slightly aggressive particles: do not use an Easy controller
Construction
LMV-D3AL-F TR for LVC
Parts and characteristics
Interface
Control strategy
The volume flow controller works independent of the duct pressure
Operating modes
Operating mode variable volume flow rate, qvmin: minimum volume flow rate, qvmax: maximum volume flow rate
Commissioning
Air terminal units control the volume flow in a closed loop, which means: measurement – comparison – adjustment.
The volume flow rate is obtained by measuring a differential pressure. This is done with a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow rate is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal flow rate (qvNom).
The volume flow setpoint is specified by a higher-level controller (e.g. room temperature controller, air quality controller, building management system) or by switching contacts. Variable volume flow control can be set betweenvmin and qvmax. It is possible to override the room temperature control by forced switching, e.g. for a shut-off
The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator according to the control deviation.
Volume flow parameter qvmin and qvmaxcan be set on potentiometers.
Category
Easy controller for volume flow with potentiometer setting for qvmin, qvmax
Application
Control of a constant or variable volume flow rate setpoint
Area of application
Dynamic transducer for clean air in ventilation and air conditioning systems
Actuator
Installation orientation
Connection
Supply voltage
Interface/signalling
Interface information
Special functions
Parameter setting
Factory condition
TVR | – | D | / | 200 | / | D2 | / | Easy |
| | | | | | | | | | ||||
1 | 2 | 5 | 6 | 7 |
setting qvmin and qvmax on site with potentiometers
Type | TVR |
Acoustic cladding | With acoustic cladding |
Nominal size [mm] | 200 |
Accessories | Double lip seal both ends |
Attachments (control component) | Volume flow controller, dynamic, analogue interface, setting qvmin and qvmax on site with potentiometers |
Easy controllers for VAV terminal units
Part number | Type | VAV terminal units |
M466EU1 | LMV-D3AL-F TR (type 2) | LVC |
A00000082301 | TR0VE-024T-10l-DD15 (type 1) | TVE, TVE-Q |
M466ES1 | LMV-D3A-F TR (type 2) | TVR |
M466ES2 | LMV-D3A TR (type 2) | TZ-Silenzio, TA-Silenzio, TVZ, TVA |
A00000087445 | 327V-024T-15-004 (type 3) | TVJ (all dimensions) TVT (up to and including 1000 × 500) |
M466ES3 | SMV-D3A TR (type 2) | TVT from 1000 × 600 |
Easy controller LMV-D3AL-F TR for VAV terminal unit LVC
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC ± 20%, 50/60 Hz |
Supply voltage (DC) | 24 V DC -10/+20 % |
Power rating (AC) | 3.5 VA max. |
Power rating (DC) | 2 W max. |
Run time for 90° | 120 – 150 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU, low voltage to 2014/35/EU |
Easy controller TR0VE-024T-10l-DD15 for VAV terminal unit TVE and TVE-Q
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC ± 20%, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Connected load | Rating TVE DN 100 - 160: 4 VA TVE DN 200 - 400: 6 VA TVE-Q up to height 200: 4 W TVE-Q up to height 300: 6 W Power consumption (during operation) TVE DN 100 - 160: 2.5 W TVE DN 200 - 400: 3.5 W TVE-Q up to height 200: 2.5 W TVE-Q up to height 300: 3.5 W Power consumption (during idle state) 1 W |
Run time for 90° | 100 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 (with the terminal cover attached) |
EC conformity | EMC to 2014/30/EU |
Easy controller
For VAV control units TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC -10/+20 % |
Power rating (AC) | 5 VA max. |
Power rating (DC) | 2.5 W max. |
Run time for 90° | 110 – 150 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, 0.5 mA max. |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU |
Easy controller 327V-024T-15-004 for VAV terminal units TVJ (all dimensions), TVT (up to 1000 x 500)
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC ± 20%, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | 4 VA max. |
Power rating (DC) | 2 W max. |
Run time for 90° | 150 s |
Signal input setpoint value | 0 – 10 V DC, Ra > 100 kΩ |
Signal output actual value | 0 – 10 V DC, max. 5 mA |
IEC protection class | III (Protective extra-low voltage) |
Protection level | IP 42 (with the terminal cover attached) |
EC conformity | EMC to 2014/30/EU |
Easy controller SMV-D3A TR for VAV terminal unit TVT from NW 1000 x 600
Type of measurement/installation orientation | Dynamic measurements, any installation orientation |
Supply voltage (AC) | 24 V AC ± 20 %, 50/60 Hz |
Supply voltage (DC) | 24 V DC -10/+20 % |
Power rating (AC) | 6 VA max. |
Power rating (DC) | 3 W max. |
Run time for 90° | 110 – 150 s |
Setpoint value signal input | 0 – 10 V DC, Ra > 100 kΩ |
Actual value signal output | 0 – 10 V DC, max. 0,5 mA |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 20 |
EC conformity | EMC to 2014/30/EU |
Cut-out LED button
1 LED push button
Description of status LEDs and error messages regarding control components for terminal unit TVE, TVE-Q
Triggering a test function for Easy attachment group
Pressing the LED push button for > 2 s starts a test run.
The control damper is moved from the current position to the open and closed position. The volume flow controller then returns to control mode.
Explanation status and error messages via LED flashing signal for attachments with article number M466ES1, M466ES2, M466ES3, M466EU1
LED | Operating status |
OFF ▪ ▪ | No power Easy controller defect |
ON | Flow rate setpoint value has been reached |
▪ ▪ Blinking slowly (0.5 Hz) ▪ ▪ | Actual value ≠ setpoint value Controller is trying to achieve the setpoint or Test in progress Synchronisation in progress |
Blinking rapidly (2.5 Hz) | Direction of rotation has been changed |
Share page
Recommend this page
Recommend this page by sending a link by mail.
Share page
Thank you for your recommendation!
Your recommendation has been sent and should arrive shortly.
Contact
We are here for you
Please specify your message and type of request.
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
Thank you for your message!
Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +32(0)2 522 07 80 | E-mail: info@trox.be
Contact
We are here for you
Please specify your message and type of request.